2. Instruction to use
1) Supply power source
①Supply the power source after checking the wire connection.
②After supplying the power source, LED indicator shows number increasing such as “00”→”11”→”22”
→”33”→・・・ and in 10 seconds, it stops increasing the number and shows the number of counts.
(The number of counts means the number of lightning current that CT detected.)
③Push “reset”button to return to zero on LED indicator.
2) Operating
①When lightning current of more than operating current flows through CT (Max. 20kA(8/20μs)), LED
indicator shows 1 number rise up and signal contact becomes “close”(500ms).
②Each operating time is about 1 seconds.
③The number of counts is memorized even if power supply stops. After power supplies, LED indicator
shows the number of counts memorized before.
④LED indicator can show 254 counts maximum.
⑤Dot shown in below figure is used to indicate more than 100 counts or 200 counts.
⑥Even if LED indicator shows more than 255 counts, signal contact becomes “close”(500ms) when the
lightning current of more than operating current flows through CT.
3) Operation check
①When pushing “Test”button, indicator counts one increasing and signal contact becomes “close”
(500ms).
②Push “Test”button continuously with the interval of 1second.
③Push “reset”button to return to zero on LED indicator.
・After power fail recovery, the indicator shows the number increasing such as 「00」→
「11」→「22」・・・. Until stop increasing the number, this product cannot operate when it
detects the lightning current. And it is no use to push “Test”and “Reset”button in this condition.
3.Notice
・Operating voltage range should be AC90V~240V(50/60Hz). Do not use in out of this range.
・This product has no function as the arrester. Supply power source from the earth side of the SPD.
・Maximum measurement current should be 20kA(8/20μs). It might be broken by large lightning current
such as direct lightning strikes.
・This product can be used only indoor. Do not use outdoor or in the place where it is splashed with water.
・Handle this product carefully to prevent mechanical shock. It may cause breaking or damage.
・A malfunction might occur when this product is installed in the place where switching surge is
synchronized on power source for it or CT receives the induction of noise.
・Operating current in this manual means the current value with the shape of 8/20μs.
・It is not necessary to do maintenance, but push “Test”button to check the operation once a year.
Indicator showing of the number of counts
Indication of when supplying power source
(Example of 5 counts)