Ovation 214 User manual

User's Guide
Read this
g
uide carefull
y
before usin
g
the controller.
OVATION 214
Temperature Controller
890-00045
rev.00

2OVATION214 rev.00
OVATION 214
TABLE OF CONTENTS
Page
TABLE OF CONTENTS................................................................ 2
PRECAUTIONS .......................................................................... 3
FEATURES ................................................................................ 4
LOCATION OF THE CONTROLS .................................................. 6
Controller Status LEDS .......................................................... 7
Internal Switches.................................................................. 7
INSTALLATION ......................................................................... 8
Mounting Instructions............................................................ 8
Connections ......................................................................... 8
Motor Types ........................................................................ 9
Temperature Probes ........................................................... 10
CHANGING THE PARAMETER SETTINGS................................... 12
Using the Display ................................................................ 12
Locking the Parameter Settings............................................ 13
TEMPERATURE SETTINGS........................................................ 14
Temperature Units .............................................................. 14
Viewing Temperatures ........................................................ 14
Temperature Set Point ........................................................ 17
Temperature Ramp ............................................................. 18
VENTILATION SETTINGS ......................................................... 22
Cooling Operation ............................................................... 22
Minimum Ventilation Cycle .................................................. 25
Minimum Ventilation Cycle Settings ...................................... 25
Humidity Compensation ....................................................... 27
Minimum Ventilation Speed Ramp ......................................... 30
Differential Settings ............................................................ 34
De-icing of Stage 2 Fans...................................................... 37
Mist Cooling....................................................................... 39
NATURAL VENTILATION.......................................................... 42
Principle of Operation.......................................................... 42
Settings............................................................................. 45
HEATER SETTINGS .................................................................. 48
ALARM SETTINGS .................................................................. 52
TEST MODE ............................................................................ 54
TROUBLESHOOTING GUIDE ..................................................... 55
TECHNICAL SPECIFICATIONS .................................................. 59
FACTORY SETTINGS ............................................................... 60
MEMORY CARD ...................................................................... 61
GLOSSARY............................................................................. 64

3
OVATION214 rev.00
OVATION 214
Westronglyrecommendinstalling supplementarynatural ven-
tilationaswell as a back-up thermostat on at least one cooling
stage (refer to the wiring diagram enclosed with this user's
manual to connect the thermostat).
Although fuses at the input and outputs of the controller
protect its circuits in case of an overload or overvoltage,
we recommend installing an additional protection device on
the controller's supply circuit.
The room temperature where the controller is located MUST
ALWAYS REMAIN BETWEEN 32°F AND 104°F (0°C TO
40°C).
To avoid exposing the controller to harmful gases or exces-
sive humidity, it is preferable to install it in a corridor.
DO NOT SPRAY WATER ON THE CONTROLLER
PRECAUTIONS
FOR CUSTOMER USE
Enter the serial number located on the
side of the controller below for future
reference.
Model number: OVATION 214
Serial number:

4OVATION214 rev.00
OVATION 214
FEATURES
The OVATION 214 is an electronic device used for environmental control
in livestock buildings. It allows the user to maintain a specified target
temperature by controlling the operation of ventilation and heating equip-
ment. Two stages of variable speed fans, two stages of constant speed
fans, one curtain as well as foggers and heaters can be connected to the
controller.
The main features of the OVATION 214 are as follows:
FIVE-DIGIT DISPLAY
A five-digit display provides a high level of accuracy, allowing the user to
specify a temperature to within one tenth of a degree (in Fahrenheit or
Celsius units).
PILOT LIGHTS
Pilot lights indicating the state of outputs allow the user to monitor the
operation of the system without having to enter the building.
MINIMUM VENTILATION CYCLE
When ventilation is not required for cooling, the first stage fans can be
operated either continuously or intermittently to reduce the level of hu-
midity and supply oxygen to the room.
RAMPING FUNCTIONS
Ramping functions provide an automatic adjustment of the set point and
minimum ventilation fan speed over a given period of time.
CHOICE OF TEN MOTOR TYPES
The variation in motor speed resulting from a change in voltage will de-
pend on the make and capacity of the motor. In order to achieve a high
degree of compatibility between controller and motor, the user can choose
from among ten different motor types, thus ensuring that the correct volt-
age is supplied.
HIGH/LOW TEMPERATURE ALARM OUTPUT
HUMIDITY COMPENSATION
The stage 1 minimum speed can be adjusted automatically as a function
of relative humidity. As humidity increases, the minimum speed of stage
1 fans increases proportionally to compensate for the change.

5
OVATION214 rev.00
OVATION 214
ZONED OR CASCADING HEATERS
FULL-SPEED FAN START-UP
In order to overcome the inertia of the ventilation system components and
de-ice the fan blades in cold weather conditions, the controller supplies
maximum voltage to the variable speed fans during the 2 seconds imme-
diately following each start-up.
DE-ICING CYCLE
A de-icing cycle is provided for de-icing stage 2 variable-speed fans in
cold weather conditions.
FOUR INDEPENDENT TEMPERATURE PROBE INPUTS
Up to four temperature probes can be connected to the controller in order
to obtain a more accurate reading of the average room temperature and a
faster reaction time.
OUTSIDE TEMPERATURE COMPENSATION ON CURTAIN SPEED
Curtain opening and closing times can be decreased as a function of out-
side temperature.
OVERLOAD AND OVERVOLTAGE PROTECTION
Fuses are installed at the input and outputs of the controller to protect its
circuitry in the case of an overload or overvoltage.
MEMORY CARD:
A memory card is used to create a copy of your controller's parameters.
COMPUTER CONTROL
The controller can be connected to a computer, thus making it possible to
centralize the management of information and diversify control strategies.
CONTROL OF AIR INLET MOVEMENT
If the OVATION 214 is used in combination with a DWR-F-1A controller,
the movement of the air inlets can be coordinated with the operation of
the fans using a potentiometer located on the panel drive. This allows the
air inlets to be adjusted correctly, without the influence of uncontrollable
factors such as wind or air from adjoining rooms.
TEST MODE
A test mode allows you to simulate temperature changes and verify con-
troller performance.

6OVATION214 rev.00
OVATION 214
LOCATION OF THE CONTROLS
',*,7$/
',63/$<
6&5((1
0$,1
0(18
67$786
/('6

7
OVATION214 rev.00
OVATION 214
Controller Status LEDS
Internal Switches
Internal switches are located on the inside of
thefrontcover.Allswitchesareset to OFF when
the controller is shipped from the factory,
#OFF ON
1 Unlocked parameters Locked parameters
2 Fahrenheit degrees Celsius degrees
3 Probe 2 disabled Probe 2 enabled
4 Probe 3 disabled Probe 3 enabled
5 Probe 4 disabled Probe 4 enabled
6 2 heaters & 0 mist 1 heater & 1 mist
7 Adjustable hysteresis Fixhysteresis of 2.0°F
8 Cascading heaters Zoned heaters
9 De-icing disabled De-icing enabled
10
11
12 Switchfrom OFF to ON to acces the transfer menu
Reserved
Reserved
LED MEANING
VARIABLE STAGE 1 Turns on when variable stage 1 fans are on.
VARIABLE STAGE 2 Turns on when variable stage 2 fans are on.
STAGE 3 Turns on when stage 3 is on.
STAGE 4 Turns on when stage 4 is on.
MIST Turns on when the mist output is on.
CURTAIN OPEN Turns on when the curtain opens.
CURTAIN CLOSE Turns on when the curtain closes.
HEATER 1 Turns on when heating output 1 is on.
HEATER 2 Turns on when heating output 2 is on.
RH COMPENSATION Turns on when a RH compensation function is on.
TEMP RAMP Turns on when the temperature ramp function is activated.
MIN SPEED RAMP Turns on when the minimum speed ramp function is activated.
PROBE DEFECT Turns on when a probe is defective.
ALARM Turns on when an alarm condition is detected.

8OVATION214 rev.00
OVATION 214
INSTALLATION
Mounting Instructions
Open the latch and lift the cover. Remove the black caps located on
each of the four mounting holes. Mount the enclosure on the wall
using four screws. Be sure the electrical knockouts are at the bottom
of the enclosure in order to prevent water from entering the control-
ler. Insert the screws in the mounting holes and tighten. Fasten the
four black caps provided with the controller onto the four mounting
holes. The enclosure must be mounted in a location that will allow the
cover to be completely opened right up against the wall.
Connections
To connect the controller, refer to the wiring diagram enclosed with
this user's manual.
Set the voltage switch to the appropriate voltage.
Use the electrical knockouts provided at the bottom of the
enclosure. Do not make additional holes in the enclosure,
particularly on the side of the enclosure when using a com-
puter communications module.
It may be necessary to install a transformer in order to sup-
ply the appropriate voltage to the heating unit.
ALARM CONNECTION: There are two types of alarms on the mar-
ket. One type activates when current is cut off at its input, whereas
the other activates when current is supplied at its input. For an alarm
of the first type, use the NO terminal as shown on the wiring dia-
gram. For an alarm of the second type, use the NC terminal.
:$51,1*
ALLWIRINGMUSTBEDONEBYANAUTHORIZEDELECTRI-
CIANANDMUSTCOMPLYWITHAPPLICABLECODES,LAWS
ANDREGULATIONS.BESUREPOWERISOFFBEFOREDOING
ANYWIRING TOAVOID ELECTRICALSHOCKS ANDEQUIP-
MENTDAMAGE.

9
OVATION214 rev.00
OVATION 214
Motor Types
The relationship between the voltage supplied to a motor and its
operating speed is described by a motor curve. This curve varies
with the make and capacity of the motor. The various motors avail-
able in the industry have been divided into ten categories and the
controller has been programmed with a different motor curve for
each of these categories. To ensure that the controller supplies the
correct voltages, an appropriate curve must be selected for stage 1
and stage 2 according to the type of fan motors used.
1
Selecting a Motor Type for Stage 1 and Stage 2
Refer to the list of motors enclosed with this user's to choose the
proper motor type.
• Set the function to STAGE 1 MOTOR TYPE or to STAGE 2
MOTOR TYPE.The motor type of the selected stage is dis-
played, alternating with the letters "tYPE".
• Press the push-button once. The motor type flashes.
• Use the adjustment knob to adjust the motor type to the
desired value.
• Press the push-button once again to validate the new value.

10 OVATION214 rev.00
OVATION 214
Temperature Probes
1
Connecting the Probes
The controller is supplied with one temperature probe connected to
input # 1. Up to three additional probes can be connected to the
controller in order to obtain a more accurate reading of the average
room temperature and a faster reaction time.
• Use inputs # 2, 3 and 4 to connect additional probes, as
shown on the wiroing diagram enclosed.
CAUTION: Probes operate at low voltage and are isolated from the
supply. Be sure that probe cables remain isolated from all high volt-
age sources. In particular, do not route the probe cables through the
same electrical knockout as other cables. Do not connect the shield
from the probe cable to a terminal or a ground.
Switches are used to activate or deactivate the additional probes
connected to the controller.
• Activate each additional probe by setting
the appropriate switch to ON:
- Switch # 3 activates the probe connected
to input # 2.
- Switch # 4 activates the probe connected
to input # 3.
- Switch # 5 activates the probe connected
to input # 4.
ON
OFF

11
OVATION214 rev.00
OVATION 214
2
Extending the Probes
Each probe can be extended up to 500 feet (150 meters). To
extend a probe:
• Use a shielded cable of outside diameter between 0.245
and 0.260 in (6.22 and 6.60 mm) (the cable dimensions
should not be under 18 AWG) to ensure the cable entry
is liquid tight. Do not ground the shielding.
• It is preferable to solder the cable joint to ensure a proper
contact between the two cables.
CAUTION: Do not run probe cables next to other power cables.
When crossing over other cables, cross at 90°.
3
Defective Probes
If a defective probe is detected, the Defective Probe Pilot Light
turns on. Theroom temperatureshown on thedisplay corresponds
to the average temperature measured by the probes in working
condition.
To identify the defective probe:
• Set the function to PROBE TEMP / MIN / MAX.If the
probe connected to input # 1 is not defective, the let-
ters "PR1" are displayed, alternating with the on/off
state of the probe and the temperature measured by
the probe. If the probe is defective, the letters "PR1"
are displayed, alternating with the state of the probe
and the letter "P".
• Press the push-button to step to the following probe.
• Proceed as explained above to make sure all probes are
in working order.

12 OVATION214 rev.00
OVATION 214
CHANGING THE PARAMETER SETTINGS
Using the Display
Flashing Values:
The display will flash in certain cases
and not in others. The flashing indi-
cates that the value shown can be
adjusted. A value that is not flashing
cannot be adjusted.
Relative and Absolute Values:
Some parameter adjustments are displayed both as a relative value
and an absolute temperature. This applies all heating and cooling
differentials, the mist differential and the heater offset. The pa-
rameter is first displayed as a relative value. The corresponding
absolute temperature is displayed after six seconds if no action is
taken by the user. The absolute value is the temperature at which
the stage turns on (except in the case of the heater and mist
offsets where the value displayed is the temperature at which
the stage turns off). If the user turns the adjustment knob, the
relative value reappears. For example, when the user turns the
selection knob to a differential position, i.e. DIFFERENTIALS 3-4,
the sequence is as follows:
(i) The current differential for stage 3 flashes on the display,
alternating with "3 dIF".
(ii) If, after about 6 seconds, no action is taken by the user, the
absolute temperature value is displayed, alternating with "St 3 On".
In this case, the absolute value is: Set Point + Bandwidth 1 +
Offset 2 + Bandwidth 2 + Differential 3.

13
OVATION214 rev.00
OVATION 214
(iii) When the user turns the adjustment knob to make an adjustment
to the stage 3 differential, the relative value reappears on the dis-
play.
Locking the Parameter Settings
The parameter settings can be locked to prevent accidentally modi-
fying them. When the settings are locked, only the temperature set
point and the Stage 1 minimum ventilation speed can be modified (as
long as the temperature ramp and the minimum ventilation speed
ramp are deactivated respectively).
To lock the parameter settings:
• Set internal switch # 1 to ON. The Locked
Parameter Pilot Light turns on.
To unlock the parameter settings:
• Set internal switch # 1 to OFF. The Locked
Parameter Pilot Light turns off.
ON
OFF
ON
OFF

14 OVATION214 rev.00
OVATION 214
TEMPERATURE SETTINGS
Temperature Units
Temperatures can be displayed in either Celsius or Fahrenheit units
• Set internal switch # 2 to the desired position:
ON: to display temperatures in Celsius units.
OFF: to display temperatures in Fahrenheit units.
Viewing Temperatures
1
Viewing the Room Temperature
The room temperature is the average value of all temperatures
measured by activated probes in proper operating condition.
• Set the function to ROOM TEMP MIN / MAX. The aver-
age room temperature is displayed.
2
Viewing the Outside Temperature
• Set selection knob to OUTSIDE TEMPERATURE. The out-
side temperature is displayed.
ON
OFF
2

15
OVATION214 rev.00
OVATION 214
3
Viewing Probe Temperatures
The controller can display probe temperatures individually. Probes
can also be turned on or off to control the temperature in different
parts of the building.
• Set the function to PROBE TEMP / MIN / MAX. The tem-
perature reading of probe 1 is displayed, alternating with the
letters "Pr 1" and the on/off state of the probe.
• For each additional probe, press the push-button. The tem-
perature reading of probe x is displayed, alternating with the
letters "Pr x" and the on/off state of the probe, etc.
4
Viewing Min/Max Temperatures
Follow this procedure to see the lowest and highest room tempera-
ture values that have been recorded since the last reset.
• Set the function to ROOM TEMP MIN / MAX or OUTSIDE
TEMP/SET POINT.The correspondingtemperatureis displayed.
• Turn the adjustment knob clockwise by one notch. The maxi-
mum room temperature is displayed, alternating with the let-
ters "Hi".
• Turn the adjustment knob counterclockwise one notch. The
room temperature is displayed once again.
• Turn the adjustment knob counterclockwise one notch fur-
ther. The minimum room temperature flashes on the display,
alternating with the letters "Lo". If any minimum or maxi-
mum temperature reading is out of range, the controller dis-
plays the letter "P" instead of displaying a temperature.
NOTE: If you let the display flash for more than 10 seconds, the
controller resets the min and max temperatures currently in memory
(the display stops flashing to indicate the reset has been done).

16 OVATION214 rev.00
OVATION 214
5
Viewing Min/Max Probe Temperatures
Follow this procedure to see the lowest and highest temperature read-
ings that have been recorded by each probe since the last reset.
• Set the function to PROBE TEMP / MIN / MAX. The tem-
perature reading of probe 1 is displayed, alternating with the
letters "Pr 1" and the on/off state of the probe.
• Turn the adjustment knob clockwise by one notch. The maxi-
mum temperature of probe 1 is displayed, alternating with
the letters "Pr1 Hi".
• Turn the adjustment knob counterclockwise one notch. The
current temperature of probe 1 is displayed once again.
• Turn the adjustment knob counterclockwise one notch fur-
ther. The minimum temperature of probe 1 flashes on the
display, alternating with the letters "Pr1 Lo".
• Turn the adjustment knob clockwise by one notch. The cur-
rent temperature of probe 1 is displayed once again.
• Press the push-button to select another probe then proceed
as explained above to see the minimum and maximum tem-
perature readings of the desired probe.
NOTE: If you let the display flash for more than 10 seconds, the
controller resets the minimum and maximum temperatures of the
selected probe (the display stops flashing to indicate that the reset
has been done).

17
OVATION214 rev.00
OVATION 214
Temperature Set Point
The temperature set point is the target room temperature. It can be
adjusted between -40.0°F and 120.0°F (-40.0°C and 48.9°C).
Adjusting the Temperature Set Point
• Set the function to SET POINT/TEMP RAMP. The current
set point flashes on the display.
• Use the adjustment knob to adjust the set point to the de-
sired value.
NOTE: The temperature set point can only be adjusted while the
temperature ramp is deactivated (see following section).

18 OVATION214 rev.00
OVATION 214
The user can define a temperature ramp to adjust the set point auto-
matically over a given time period.
A ramp is defined using ten points. Each point specifies a day number
and a set point for that day. Once the points of the ramp are defined,
the ramp must be activated. The controller will change the tempera-
ture set point every hour in a linear fashion between consecutive points
of the ramp. When the last point of the ramp is reached, the tempera-
ture set point for that day is maintained until the ramp is reactivated.
NOTES :
i) All ten points of the ramp must be specified. If ten points are not
needed, repeat the last temperature value for each unnecessary point.
ii) Certain restrictions apply to reduce the risk of errors:
- The highest possible day number is 255.
- Decreasing day numbers are not allowed.
- Increasing temperatures are not allowed.
- The temperature variation cannot exceed 3°F (1.6°C) per day.
Temperature Ramp
T° 1
SET POINT
TEMPERATURE
DAY
S
T° 2
T° 3
T° 4
T° 5
T° 6
DAY 4 DAY 15 DAY 21 DAY 30 DAY 36 DAY 55DAY 45 DAY70 DAY 100DAY 80
T°7
T°8
T° 9
T° 10

19
OVATION214 rev.00
OVATION 214
1
Specifying the Ramp
The points of the ramp can only be modified while the ramp is dis-
abled. Refer to the 4th section of this chapter to disable the ramp.
• Set the function to SET POINT/TEMP RAMP. The current
temperature set point flashes on the display – the value does
not flash if the ramp is activated. Refer to the 4th section of
this chapter to disable the ramp.
Repeat the following steps for each of the ten points (point 0
to point 9):
• Press the push-button. The day number of the first point of
the ramp (point 0) is displayed "d0 x" (where "x" is the day
number).
• Using the adjustment knob, set the day number of the first
point of the ramp to the desired value.
• Press the push-button once again. The temperature set point
associated with the first point of the ramp (point 0) is dis-
played "t0".
• Using the adjustment knob, adjust the set point of the first
point of the ramp to the desired value.
Once all points of the ramp are defined, activate the ramp as ex-
plained below.

20 OVATION214 rev.00
OVATION 214
2
Activating the Temperature Ramp
If you have just finished specifying the points on the ramp:
• Press the push-button once again. The word OFF flashes on
the display.
• Turn the adjustment knob clockwise one notch. The word
ON flashes on the display and the Temperature Ramp Pilot
Light turns on, indicating that the temperature ramp is now
activated.
If you have previously defined the points on the ramp:
• Set the function to SET POINT/TEMP RAMP. The current
temperature set point flashes on the display.
• Press the push-button to display all points of the ramp until
the word OFF appears (twenty-one clicks).
• Turn the adjustment knob clockwise one notch. The word
ON flashes on the display and the Temperature Ramp Pilot
Light is lit, indicating that the temperature ramp is now acti-
vated.
Table of contents