Panduit CDE3 User manual

For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2016 V00029KB
Page 1 of 6
Component Guide
TOOL LIST
#2 Philliips Screwdriver
5/16” Socket Wrench
3/8” Socket Wrench
1/4” Socket Driver
(1) Hardware Kit
(not shown)
(1) Switch Support Bracket
CDE3
(installed in Net-Access
Server Cabinet)
Modular ToR Switch Inlet Duct
(CDE3)
Cisco Nexus 3900 Series Switch
(reference)
(2) Chassis Side Bracket
(1) Switch Ducting
(with hinged perforated door)

For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2016 V00029KB
Page 2 of 6
Determine Location of Switch Ducting and Switch Support Bracket
NOTES: Front to back span of equipment rails may need to be adjusted to accomodate your switch. Front to rear rail spacing
requirements range from 24.0" TO 30.5". Equipment installed directly below CDE3 may impede routing of switch power cord if installed
prior to CDE3.
Switch Ducting and Switch Support Bracket components of CDE3 require (4) rack spaces for installation. Switch Ducting and Switch Sup-
port Bracket are to be installed at the same vertical rack position. CDE3 components are to be installed prior to switch installation and are
designed to support the switch. (CDE3 ducting system ONLY requires use of primary Cisco rack mount brackets. Cisco supplied switch
cradle or extension brackets are not compatible with CDE3.)
Grounding Cage Nut
(green)
Cage Nut
(installed)
Intended
Mounting
Location
(4 rack spaces)
3 RU Switch
(reference; port side of
switch faces Hot Aisle)
Install Cage Nuts
Insert (3) cage nuts per Front and Rear equipment rail at CDE3 component mounting locations (12 total cage nuts are to be installed). (1)
grounding cage nut (green) must be installed in (1) Front and (1) Rear equipment rail opposite each other on Left or Right Hand side. The
view below depicts cage nut locations for front and rear equipment rails on Left Hand Side of Cabinet
Switch Ducting
Switch Support Bracket
Intended
Mounting
Location
(4 rack spaces)
Intended Mounting Location
(4 rack spaces)
Perforated Door of Switch Ducting
(faces Cold Aisle)
FRONT OF
CABINET
REAR OF
CABINET
FRONT OF
CABINET REAR OF
CABINET

For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2016 V00029KB
Page 3 of 6
Install Switch Ducting
Position Switch Ducting so that the perforated door of ducting faces the cold aisle and the mounting holes of Switch Ducting align with cage
nuts in equipment rails (installed on page 2). Secure Switch Ducting to equipment rails using (5) #12-24 Phillips screw, (5) #12 External
Tooth Washers and (1) hex head grounding screw (green; use 5/16” socket wrench) on front rail. Ensure that hex head grounding screws
fasten into grounding cage nuts.
(1) #12-24 Hex Head
Grounding Screws
(use 5/16” socket wrench)
Switch Ducting
Perforated Door of Switch Ducting
(faces Cold Aisle)
Install Switch Support Bracket
Position Switch Support Bracket so that the mounting holes of Switch Support Bracket align with cage nuts in equipment rails (installed on
page 2). Secure Switch Support Bracket to Rear equipment rails using (5) #12-24 Phillips screw, (5) #12 External Tooth Washers. (1) hex
head grounding screw (green; use 5/16” socket wrench) on rear rail. Ensure that hex head grounding screws fasten into grounding cage
nuts.
Grounding Cage Nut
(green)
Cage Nuts
(installed)
(5) #12-24 Phillips Screws
(1) #12-24 Hex Head
Grounding Screws
(use 5/16” socket wrench)
Cage Nuts
(installed)
Grounding Cage Nut
(green)
Switch Support
Bracket
FRONT OF
CABINET REAR OF
CABINET
FRONT OF
CABINET
(5) #12 External Tooth Washers
(5) #12-24 Phillips Screws
(5) #12 External Tooth Washers

For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2016 V00029KB
Page 4 of 6
Routing of Switch Power Cable
NOTE: Dashed outline of 3 RU Switch is shown for power cord routing reference only.
DO NOT INSTALL SWITCH AT THIS TIME. Cabinet and equipment rails are not shown to add clarity to view.
Prior to switch installation, route power cord through Switch Ducting and Switch Support Bracket as shown. Slit grommet(s) along guide
lines as needed to allow for power cord pass-through. Use bridge features on Switch Support Bracket as tie-down point(s) to secure
switch power cord to Switch Support Bracket with cable tie.
Switch Ducting
Switch
Support
Bracket
Install Switch
NOTE: Cabinet and equipment rails are not shown to add clarity to view.
Slide the 3 RU Switch onto positioning flanges of Switch Support Bracket. Carefully insert inlet side of switch into rear opening of Switch
Ducting. Position holes of 3 RU Switch rack mount brackets over threaded studs of Switch Support Bracket. Secure switch to Switch
Support Bracket with (6) #10-32 acorn nuts (use 3/8” socket wrench), (6) #10 External Tooth Washers
Switch Power Cord
(to rear-mounted power
outlet unit)
FRONT OF CABINET
Slit Grommet(s) along guide lines as needed
to allow for power cord pass-through
Bridge Feature
(use as tie-down
point for cable tie)
FRONT OF CABINET
3 RU Switch
(reference; port side of
switch faces Hot Aisle)
Positioning
Flange
Rear Opening of
Switch Ducting
(6) #10-32 Acorn Nuts
(use 3/8” socket wrench)
Positioning
Flange
Switch Power Cord
REAR OF
CABINET
(6) #10 External Tooth
Washers

For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2016 V00029KB
Page 5 of 6
Install Chassis Side Brackets
Install Chassis Side Bracket on 3900 Series Switch by Aligning the holes in the Chassis Side Bracket. Carefully Insert Inlet side of Switch
Inside front opening of Switch Ducting.
Cage Nuts
(installed)
(5) #12-24 Phillips Screws
Middle Support
Bracket
REAR OF
CABINET
Install Switch Support Bracket Day 2
Position Switch Supports Bracket with middle support bracket removed. Align the mounting holes of Switch Support Bracket with cage nuts
in equipment rails (installed on page 2). Secure Switch Support Brackets to Rear equipment rails using (5) #12-24 Phillips screw, (5) #12
External Tooth Washers. (1) hex head grounding screw (green; use 5/16” socket wrench) on rear rail. Ensure that hex head grounding
screws fasten into grounding cage nuts. Install Middle Support Bracket using (4) #12-24 Phillips screw, (4) #12 External Tooth Washers.
(5) #12 External Tooth Washers
Switch Support
Brackets
(4) #12-24 Phillips
Screws
(4) #12 External Tooth
Washers
Switch Ducting
Cisco Nexus 3900 Series Switch
(reference)
Standard Chassis Mounting Brackets
Removed
FRONT OF
CABINET
FRONT OF
CABINET
Chassis Side Brackets
(1) #12-24 Hex Head
Grounding Screws
(use 5/16” socket wrench)
Grounding Cage Nut
(green)

INSTALLATION INSTRUCTIONS
© Panduit Corp. 2016 V00029KB
E-mail:
Phone:
866-405-6654
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp www.panduit.com
Page 6 of 6
Secure Switch to Switch Ducting
NOTE: Top cover of Switch Ducting removed for clarity
Center Slots in Chassis Side Brackets with holes located on both sides of the Switch Ducting. Secure Chassis Side Brackets to switch
ducting using (4) #12-24 Phillips screw, (4) #12 External Tooth Washer.
Switch Ducting
Perforated Door of Switch Ducting
(faces Cold Aisle)
(4) #12-24 Phillips Screw
FRONT OF
CABINET
(2) Chassis Side
Bracket
(4) #12 External Tooth Washer
Cisco Nexus 3900 Series Switch
(reference)