Panduit UTFMRDU Instruction Manual

Panduit 5 kVA 208 to 120 VAC Step-Down
Transformer
User’s Guide and Installation Manual V2.0
Model(s): UTFMRDU

UPS STEP-DOWN TRANSFORMER USER MANUAL
1
Table of Contents
Section 1: Important Safety Instructions..........................................................................2
Handling Instructions................................................................................................2
Preparation ..............................................................................................................2
Equipment Installation Location ...............................................................................3
Equipment Connection.............................................................................................3
Maintenance Information..........................................................................................3
Storage Information..................................................................................................3
Section 2: Mounting and Installation Instructions ............................................................4
Rack Mounting.........................................................................................................4
Four-Post Rack Mounting ........................................................................................5
Tower Mounting .......................................................................................................8
Section 3 –Transformer Overview and Features............................................................9
Key Features...............................................................................................................9
Step-Down Transformer Physical Features and Accessories......................................9
Physical Features.....................................................................................................9
Specifications................................................................................................................13
Appendix A: Troubleshooting........................................................................................15
Appendix B: What’s Included: Step-Down Transformer (UTFMRDU) ...........................17
Warranty Information.................................................................................................17
WARRANTY REGISTRATION
Visit: https://www.panduit.com/en/support/product-registration.html

UPS STEP-DOWN TRANSFORMER USER MANUAL
2
Section 1: Important Safety Instructions
Please comply with all warnings and operating instructions. Save this manual for future
reference. Carefully read and follow these instructions before installing the unit. Do not
operate this unit before reading through all safety information and operating instructions
carefully.
Dangerous voltages and high temperatures may exist inside the Step-Down Transformer.
During the installation, operation, and maintenance of these units, please abide by the local
safety rules and relative laws. Failure to do so may result in personnel injury or equipment
damage. Safety instructions in this manual act as a supplement for the local safety rules. No
liability is assumed for not following the safety rules.
Handling Instructions
CAUTION!
The Transformer is extremely heavy! Use caution during installation.
Before moving the Step-Down Transformer, be sure to use the original packaging materials to
prevent or reduce the possibility of personal injury or damage to the product. Follow the lifting
guidelines as shown in the figure below.
This product may expose you to chemicals including Nickel (Metallic), which is known to the State of California to
cause cancer and birth defects or other reproductive harm. For more information, go to www.P65Warnings.ca.gov.
Preparation
•Only install and operate the transformer indoors.
•Do not install the transformer in excessively humid environments.
•Do not install the transformer in excessive heat or in direct sunlight.
•Do not install the transformer in an area with dense or conductive particulates.
•Do not block ventilation holes in the transformer housing or front faceplate.
•It is recommended to mount the transformer unit near the bottom of the rack due to
the physical weight of these units. Refer to Section 2: Mounting and Installation
Instructions for suggestions.

UPS STEP-DOWN TRANSFORMER USER MANUAL
3
Equipment Installation Location
•The transformer must be installed in an indoor environment with a temperature range
from 0°C to 40°C.
•The transformer must be installed in an environment with a relative humidity from 0%
to 95%, non-condensing.
•The transformer should be installed in an environment with an altitude of 1000 meters
(3,281ft.) or lower with no derating.
•The transformer internal cooling is dependent on the system fan, so it should be kept in
a good air ventilated area.
Equipment Connection
•The power input on the transformer must be connect only to a circuit provided with
branch circuit overcurrent protection in accordance with the National Electrical Code,
ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1.
•Branch circuit protection will be provided by building installation.
•The transformer may be installed and operated by a trained qualified layman.
•Only use the input cable supplied with the transformer.
•Input power is restricted to 208 VAC.
•WARNING: Do not use 240 VAC to power the transformer.
•Connect the transformer only to an earth-grounded outlet that is easily accessible and
near the transformer unit.
•Attach protective grounding wire to the grounding screw located on the transformer
rear panel. The recommended grounding-wire gauge is 10 mm2
•Do not connect appliances or devices that would overload the transformer according to
the rated load capacity.
•Use only UL, VDE, CE certified power cables to connect the loads to the transformer.
Maintenance Information
•The transformer contains no user-serviceable internal components and does not require
routine maintenance.
•For other performance issues see Appendix A: Troubleshooting.
Storage Information
•When moving or storing the transformer, place it in an upright position in the original
packaging and keep it in a dry environment.

UPS STEP-DOWN TRANSFORMER USER MANUAL
4
Section 2: Mounting and Installation Instructions
Rack Mounting
•It is recommended to mount the transformer in a four-post rack.
•Mounting brackets and a rail kit are included with the transformer for four-post rack
mounting.
•If the included hardware is not suitable for your rack, contact the rack manufacturer to
obtain proper mounting accessories.
•It is recommended to mount the transformer near the bottom of the rack.
•Suggested positions for planning installation when used with the Panduit 5-10kVA UPS
systems are shown in the image(s) below.
Figure 1 Transformer Location between the 5-10kVA Panduit UPS and
UVP240 Battery Pack (Front view left. Rear view right.)

UPS STEP-DOWN TRANSFORMER USER MANUAL
5
Four-Post Rack Mounting
The transformer units come with the hardware required for installation in a standard EIA
or JIS seismic rated four-post rack with square or M5 threaded mounting holes. The rail
assemblies adjust to mount in 19” racks with a front-to-rear distance of 460~1000 mm
(18 to 39 inches).
1. Install the URMKIT2 rail kit:
a. Install the front side of the rail kit with 3x Phillips Pan Head M5 screws (see figure
below) on each rail. Do not tighten the screws.
b. Adjust the rail size according to the depth of the rack.
c. Install the rear side of the rail kit with 3x Phillips Pan Head M5 screws (see figure
below) on each rail.
Figure 2 Mounting Rail Kit screw installation (front)
Figure 3 Mounting Rail Kit screw installation (rear)

UPS STEP-DOWN TRANSFORMER USER MANUAL
6
d. Tighten all 12x screws to secure the left and right rails to the rack.
e. Install the 4x M5 cage nuts in the rack front equipment rail, with square holes. One
in each of the first locations below the bottom rail kit screw and one in each of the
first locations above the top rail kit screw (see figure below).
2. Install the mounting brackets (included):
a. Remove the 2x Phillips Flat Head M4x8 screws from the front of each side of the
transformer and retain.
b. Align the mounting brackets with the screw holes on each side of the transformer and
secure with the previously removed Phillips Flat Head M4×8 screws (see figure below)
Figure 4 Mounting Rail Kit cage nut and screw placement.
Figure 5 Mounting brackets attachment.

UPS STEP-DOWN TRANSFORMER USER MANUAL
7
3. Install the transformer into the rack:
a. After installing the mounting brackets onto the transformer, slide the transformer
into the rack on the rail kit (see figure below).
b. Align the mounting brackets with the screw holes on the rack and secure the UPS
with the supplied 4x Phillips Hex Head M5 screws (see figure below).
Figure 6 2 RU UPS or Transformer placement.
Figure 7 Four-post rack mounting ear screw installation.

UPS STEP-DOWN TRANSFORMER USER MANUAL
8
Tower Mounting
•The transformer may be mounted in a tower orientation. It is not recommended to
mount the transformer in the tower orientation without the use of the stabilizing tower
mounting feet.
•Only the stabilizing tower mounting feet containing foam pads (included in the kit) are
to be used.
•Do not mount the transformer in a tower configuration if the unit is positioned at an
incline or decline.
1. Assembling the tower kit:
a. Align to interlock two tower feet at a right angle and rotate to snap together (see
figure below).
Figure 8 Tower Mounting Foot Assembly

UPS STEP-DOWN TRANSFORMER USER MANUAL
9
Section 3 –Transformer Overview and Features
The Panduit UPS Step-Down Transformer unit (UTFMRDU) converts 208 VAC input
from an AC mains source (utility, UPS, or generator) to 120 VAC output. The 2 ft (0.6 m)
input cord is equipped with a NEMA L6-30P 208 VAC 30A plug. The unit is equipped
with 12 NEMA 5-20R 120 VAC outlets that support NEMA 5-15P and 5-20P plugs. The
unit has one NEMA L6-30R outlet for 208 VAC output. The transformer unit supports
rack mounting using the 2 RU four-post rail kit (included). The transformer unit also
supports tower mounting using the tower mounting kit (included).
Key Features
•Step-down isolation transformer that transforms 208 VAC input voltage to 120 VAC
Output voltage.
•Operable at 60 Hz and 50 Hz.
•One NEMA L6-30P input plug.
•One manually resettable 25A input breaker.
•Twelve NEMA 5-20R outlets.
•Four manually resettable 20 A breakers for the 5-20R outlet groups.
•One NEMA L6-30R pass-through outlet (208 VAC).
•Up to 5000W / 5 kVA of rated power handling capacity
•Maximum capacity for each outlet group (1-4) is 1500 W/1.5 KVA
•Included four-post rack mounting rail kit.
•Included tower mounting kit.
Step-Down Transformer Physical Features and Accessories
The following sections provide an overview of physical features on the Step-Down
Transformer unit.
Physical Features
Step-Down Transformer Front Panel
The Step-Down Transformer front panel is a 2 RU form factor designed to conform with
the Panduit 5-10 KVA UPS product line. The front panel contains air flow vents and a
moniker denoting the identity of the unit. The molded faceplate is removeable via push-
in tabs on the sides.

UPS STEP-DOWN TRANSFORMER USER MANUAL
10
Figure 11: Step-Down Transformer Front Panel
Air Flow Vents
The air flow vents are critical to the operation of the Step-Down Transformer unit. These
vents must remain clean and clear of all objects that may restrict the air flow through the
unit.
Step-Down Transformer Rear Panel
The rear panel of the Step-Down Transformer contains the NEMA L6-30P input plug,
120 V NEMA 5-20R outlets, a NEMA L6-30R pass-through outlet, breaker reset
switches for the 120 V outlets, and a toggle 25A / thermal input breaker.
Input Power Cord (INPUT)
The Step-Down transformer input cord is equipped with a NEMA L6-30P 208 VAC 30A
plug with a length of 0.6 meters.
WARNING: Do not power the Transformer unit with 240 VAC.
Input Breaker
The Step-Down transformer input cord is equipped with an input breaker rated at 25A.
The input breaker has a manual reset switch. Outlet groups will be disabled when this
switch is opened. The input breaker is closed (ON) when the indicator on the breaker is
orange and opened (OFF) when the indicator is green. There are additional markings
on the rear panel to denote the ON and OFF positions.
Chassis Ground Connection Point ( )
The Step-Down Transformer rear panel contains a chassis ground connection, labeled
with a ground symbol. For safety and proper grounding procedures, this grounding
connection point must be connected to the rack/cabinet ground.
Output Receptacles (denoted as GROUP1, GROUP2, GROUP3, GROUP4)
The Step-Down Transformer has four groups of 120 VAC NEMA 5-20R power output
connectors, labeled: GROUP 1, GROUP 2, GROUP 3, and GROUP 4. Each of these

UPS STEP-DOWN TRANSFORMER USER MANUAL
11
outlet groups contains three outlets and are protected by a 20A breaker. The breaker is
resettable via a manual push button.
Outlet GROUP 1 and GROUP 2 are paired and may share up to 3000 VA load (1500
VA each). Outlet GROUP 3 and GROUP 4 are paired and may share up to a 3000 VA
load (1500 VA each). The Step-Down Transformer also contains a pass-through 208 V
NEMA L6-30R outlet group, labeled GROUP 5. Total rated capacity of the Transformer
is 5000 VA distributed between these outlet groups.
Cooling Fan
The transformer is equipped with a cooling fan that will run when the unit is powered up.
The fan is critical in preventing the transformer coil from overheating, which may cause
damage to the equipment.
WARNING: Do not use the transformer if the fan is blocked or has malfunctioned.

UPS STEP-DOWN TRANSFORMER USER MANUAL
12
UTFMRDU
Figure 12: UTFMRDU Rear Panel
1. Input Cord
2. Input Breaker
3. L6-30R Output
(Group 5)
4. NEMA 5-20R
Group 1 Output
(120 VAC)
5. NEMA 5-20R
Group 2 Output
(120 VAC)
6. NEMA 5-20R
Group 3 Output
(120 VAC)
7. NEMA 5-20R
Group 4 Output
(120 VAC)
8. Output Breaker
(20 A, push
button reset)
9. System Cooling
Fan
10. Ground
Attachment
Screw

UPS STEP-DOWN TRANSFORMER USER MANUAL
13
Specifications
Model
UTFMRDU
General
Capacity (VA/Watts)
5000VA / 5000W
Cooling
Fan cooled
Rack Height Dimension
2 RU
Installation Type
Rack / Tower
INPUT
Nominal Input Voltage
208 Vac
Input Phase
2W+PE (L1, L2, PE)
Max Input Current
24 A
Input Frequency
50 / 60 Hz
Maximum Input Power
5000VA / 5000W
Input Connection
NEMA L6-30P
Input Cable Length
0.6m
OUTPUT
Nominal Output
Voltage
Group 5
208 VAC (L1,L2,PE)
Groups 1-4
120 VAC (L,N,PE)
Output Frequency
50 / 60 Hz
Maximum Output Power
(Total distributed)
5000VA / 5000W
Maximum Output
Power per Outlet
Group
Group1
1500VA / 1500W
Group2
1500VA / 1500W
Group3
1500VA / 1500W
Group4
1500VA / 1500W
Output Connection(s)
(1) L6-30R, (12) 5-20R
Output Protection
(4) 20A breaker
Efficiency
>93%
PHYSICAL
Dimension WxDxH (mm)
440 x 621.5 x 86.5 (2 RU)
Net Weight (kg)
44.5 kg
Packaging Dimensions WxDxH
(mm)
805 x 555 x 202
Net Weight w/Packaging (kg)
53 kg
ENVIRONMENTAL
Operating temperature
0 ℃~ 40 ℃(no derating)
Storage temperature
-25 ℃~ 55 ℃
Relative humidity
0 ~ 95% (non-condensing)

UPS STEP-DOWN TRANSFORMER USER MANUAL
14
Operating elevation
0 - 1000 meters
>1000 meters requires derating
Noise level
45dB
CONFORMANCE
Safety
cUL: UL 1778 5th Edition, CSA C22.2
NO.107.3-14
FCC
FCC Part 15 Subpart B Class A, ANSI
C63.4-2014
Transportation
ISTA Procedure 2A
Environment
ROHS 2.0

UPS STEP-DOWN TRANSFORMER USER MANUAL
15
Appendix A: Troubleshooting
If the transformer is not properly functioning, it may be related to improper installation,
wiring, or operation. Follow the troubleshooting procedures below as a first pass
analysis of the problem.
No.
Problem
Possible reason
Solution
1
The mains source is
connected but the
transformer will not
power ON. (No voltage
at the output.)
Input power source is not
providing power.
Input voltage and/or
frequency is too low or too
high.
The input breaker of the
transformer is not turned
ON.
Use a multimeter to measure the source
voltage and frequency connected to the
transformer input to ensure it is within
the operational input range.
Check that the transformer input breaker
is turned ON.
2
The source is
connected and powered
but the fan is not
functional.
Input voltage is insufficient.
The fan may have jammed
or malfunctioned.
Verify input voltage is within nominal
range.
Power off unit and clear obstructions if
possible.
If fan has malfunctioned, do not use
transformer and contact customer
support for repair or replacement
options.
3
The output breaker
does not reset once
tripped.
The output breaker may
have malfunctioned.
Disable power to the transformer. Let
the unit cool if hot. Reset the output
breaker. Power the transformer back on
and power is present at the outlets.
If problem persists, contact Panduit
customer support for repair or
replacement options.
4
The input breaker has
tripped.
The transformer may be
overloaded.
The transformer coil has
overheated.
Reduce the load on the transformer
outlets. Verify that the fan is running and
there is nothing obstructing the front and
rear ventilation. Let the unit cool down.
Manually switch the input breaker switch
back on.

UPS STEP-DOWN TRANSFORMER USER MANUAL
17
Appendix B: What’s Included: Step-Down
Transformer (UTFMRDU)
Step-Down Transformer Box
•5 kVA Step-Down Transformer [UTFMRDU] (1 unit)
•2U Step-Down Transformer Front Faceplate (1 piece)
•Tower Mount Kit (4 pieces)
•Rack Mounting Brackets (2 pieces)
•Safety Warning Sheet (1 sheet)
•Rack Rail Mounting Kit [URMKIT2] (1 kit)
oLeft Slide Rail (1 rail mechanism)
oRight Slide Rail (1 rail mechanism)
oPhillips Pan Head M5x12 Screw (12 screws)
oPhillips Hex Head M5x25 Screw (4 screws)
oM5 Cage Nut (4 cage nuts)
oRail Installation Sheet (1 sheet)
Warranty Information
Visit https://www.panduit.com/en/legal-information/panduit-limited-product-warranty.html
Table of contents
Popular Transformer manuals by other brands

Toa
Toa MT-200 operating instructions

LOVATO ELECTRIC
LOVATO ELECTRIC EXS1032 instruction manual

Dewenwils
Dewenwils HOSL08A instruction manual

QSC
QSC Output Isolation Transformer IT-42 installation guide

WAC Lighting
WAC Lighting EN-1260-RB2 Instructions for use

Universal
Universal ECO Series Installation instructions manual