Whale INSTANT MATCH SDS236T Assembly instructions

WITH
Quick Connect Guide
SDS236T
Instant Match Transformer

Important Information
Please read the following information before setting up a Bluetooth®wireless technology connection between
the Whale Instant Match®with Bluetooth® wireless technology transformer and Mira®Advance Flex Extra
(J09N) shower:
• The electrical wiring must conform to EU wiring regulations BS7671:2008 Part 7 (17th Edition).
• The Bluetooth®function of the Whale Instant Match®transformer will only work with the Mira Advance Flex
Extra (J09N) shower.
• Previous Whale Instant Match®Wireless transformers canno be connected wirelessly to the Bluetooth®
wireless technology enabled Mira Advance Flex Extra Shower (J09N).
• Bluetooth® wireless technology enabled transformers can be easily identified by the blue test button.
• For optimum signal strength, mount the transformer within 5 metres of the shower.
• Locating the transformer outside of a 5 metre radius may cause a communication breakdown between
the transformer and shower, resulting in intermittent or complete failure to operate.
• Be aware that in very rare situations, dense building material, metallic objects such as steel baths and
foil lined plaster board, or electronic devices may interfere with the Bluetooth® wireless technology signal
and result in intermittent failure. In this situation you should relocate the transformer closer to the shower.
• A hardwired connection should be established if a Bluetooth® wireless technology connection cannot be
made between the shower and transformer.
• If any components or cords are damaged, it must be replaced by a qualified person to avoid a hazard.
Set Up
1. Shower settings
• Before beginning the Bluetooth®registration process,
please ensure that the “Pump LK2” switch inside the Mira®
Advance Flex Extra (J09N) has been set to the “ON” position
as per the diagram shown.
• At this stage please ensure that your transformer is set to be
used with Bluetooth® wireless technology: the flow sensor
setting must be set to 7 for “Bluetooth” and the pipe inlet
diameter must be set to 1 for 15mm.
12345678
BEAB
OFF ON
43 DEG C
45 DEG C
RESERVED
6L/MIN
PUMP LK3
PUMP LK2
PUMP LK1
WARNING
umbing of the Waste Pipe
Bluetooth®wireless technology

• Ensure that the electric supply to the shower is turned OFF.
Then turn the dial on the shower to FULL COLD.
3. Shower set up
2. Transformer set up
• Switch the mains electric supply to the transformer ON.
The light on the transformer will now flash red to indicate
that a Bluetooth® wireless technology connection has not
yet been established.
• Press and H LD the blue test button on the transformer
until the light flashes red and green to indicate that the
transformer is now in pairing mode.
NOTE: You now have 120 seconds to pair the transformer
to the shower.
• Switch the mains electric supply to the shower ON,
Start/ stop button will illuminate.
• Within 10 seconds press and H LD the Start/Stop button on
the shower until the Start/Stop light on the button goes off.
4. Configuring the shower

6. airing the shower to the Whale
Instant Match®transformer
• Press and release the start/stop button on the shower.
The status light on the shower will now flash blue to indicate
that the shower is in pairing mode.
• The status light on the shower will then flash whi e to indicate
that the transformer has successfully been paired to the shower.
• The Whale transformer will flash green only to indicate that it is
paired to the Mira shower.
• Turn the temperature control to full cold and press the
Start/Stop button on the shower. The shower will now
return to normal standby mode.
• You may now follow the “Post Installation Procedure” in
the Mira®Advance Flex Extra (J09N) Instruction Manual
(page 25) if necessary.
7. Completing the pairing
5. Slowly turn the dial on the
shower to position 2.

Some service work that may need to be carried out on the Mira Advance shower e.g. the renewal
of the control PCB board may require the Bluetooth® wireless technology connection between the
shower and Whale Instant Match®transformer to be terminated and paired again once the work
has been completed. To unpair the transformer from the shower, please follow these steps.
1. Switch the mains electric
supply to the shower OFF.
2. Be sure to leave the mains electric
supply to the pump ON.The light on the
transformer will flash blue.
Plumbing of the Waste Pipe
Bluetooth® wireless technology Unpairing
3. ress and HOLD the test button on the transformer
until the light flashes red. The transformer and
shower have now been unpaired.
NOTE: To pair the shower to the transformer again, please
follow the Bluetooth® wireless technology setup procedure.

Transformer
Whale
Transformer
Settings
Blue Jumper - Sensor Position 4
Grey Jumper - ver run 10 Seconds
Red Jumper - Pipe inlet 15mm
Plumbing of the Waste Pipe
Shower Hardwired Connections
Triton®Safeguard + Omnicare Design,
Omnicare Style, T150Z+
Wired Connections to the Whale Instant
Match®Transformer
Redring®Selectronic W (SEL85W or SEL95W )
Wired Connections to the Whale Instant
Match®Transformer
Transformer
Whale
Transformer
Settings
Blue Jumper - Sensor Position 4
Grey Jumper - ver run 10 Seconds
Red Jumper - Pipe inlet 15mm

From Transformer
TERMINAL BLOCK
NL
Brown
CN13
Black
Red
12345678
BEAB
OFF ON
43 DEG C
45 DEG C
RESERVED
6L/MIN
PUMP LK3
PUMP LK2
PUMP LK1
Mira®Advance Flex Extra 1.1785.005 (J09N)
Wired Connections to the WHALE INSTANT MATCH®Transformer
Whale Transformer Settings
Blue Jumper - Sensor Position 6
Grey Jumper - ver run 10 Seconds
Red Jumper - Pipe inlet 15mm
Connection to Mira®Advance Flex Extra J09N Shower
Ensure all LK settings are set to
‘OFF’ for hardwired connection
Flex Extra J09N

lease see below for jumper
and wiring connections.
There are two versions of Gems®flow sensor:
1000 pulses per litre (ppl) and 2200 ppl.
Blue jumper position 3 = 1000ppl
Blue jumper position 4 = 2200ppl (shown below)
umbing of the Waste Pipe
Gems®Sensor connection
Whale®Transformer Settings
Blue Jumper - Sensor Position 2
Grey Jumper - ver run 10 Seconds
Red Jumper - Pipe inlet 15mm
Plumbing of the Waste Pipe
Sika®Sensor Connection
Whale®Transformer Settings
Blue Jumper - Sensor Position 4
Grey Jumper - ver run 10 Seconds
Red Jumper - Pipe inlet 15mm
Sika®Sensor
Gems®Sensor
Please ensure that water flow
through the sensor is in the
direction of the arrow.
Please ensure that water flow
through the sensor is in the
direction of the arrow.

When connecting to the Grundfos®Venturi sensor it is important
to connect an earth wire from the Venturi sensor to the signal
earth connection on Whale®transformer (shown below).
Whale®Transformer Settings
Blue Jumper - Sensor Position 5
Grey Jumper - ver run 10 Seconds
Red Jumper - Pipe inlet 15mm
Plumbing of the Waste Pipe
Grundfos®(Venturi) Connection
Venturi sensor
Please ensure that water flow
through the sensor is in the
direction of the arrow.

Connection to other Electric Showers
Where fitting the Whale Instant Match®to an electric shower without a
digital pump connection a flow sensor is needed in the water supply to the
shower. Please refer to our web page (www.whalepumps.com/psd) and go
to the Resources section for Level Access Adaptations for instructions or
call the Whale Shower Drainage Helpline.
©Copyright Whale 2017 - All rights reserved. Reproduction in whole or in part without permission is prohibited. WHALE®
and WHALE INS AN MA CH® are registered trademarks of Munster Simms Engineering Limited, Bangor, Northern
Ireland trading as Whale. Whale’s policy is one of continuous improvement and we reserve the right to change
specications without prior notice. Illustrations are for guidance purposes only. Neither the accuracy nor completeness of
the information contained in this or any Product literature is guaranteed by the Company and may be subject to change at
its sole discretion. Please note that by contacting Whale Support you will be indicating your consent to receiving product
updates, recall information, help guides and appropriate marketing messages from us via post, email or telephone unless
you indicated an objection to receiving such messages.
he Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks
by Munster Simms Engineering Ltd (trading as Whale) is under licence. Other trademarks and trade names are those of
their respective owners.
MIRA® is a registered trade mark of Kohler Mira Limited.
RI ON® is a registered trade mark of riton Showers a division of Norcros Group (Holdings).
REDRING® is a registered trade mark of Redring Xpelair Group Limited.
SIKA® is a registered trade mark of Dr. Siebert & Kuhn GMbH & Co. KG
GEMS® is a registered trademark of Gems Sensors & Controls.
GRUNDFOS® is a registered trademark owned by Grundfos Management A/S or Grundfos A/S, Denmark.


0845 0694 253
drainagesupport@whalepumps.com
www.whalepumps.com
@Whalecare
Whale, 2 Enterprise Road,
Bangor, Co. Down,
BT19 7TA, N.Ireland
Ref. 182.606_v1_1217
Other manuals for INSTANT MATCH SDS236T
1
Table of contents
Other Whale Transformer manuals