Parr Instrument 4848T Instruction Manual

4848
T
Reactor Controller with Touchscreen
Operating Instruction Manual

2
PREFACE 3
Related Instructions 3
Scope 3
Applications 3
Intended Usage 3
Unpack Carefully 3
Explanation of Symbols 3
Safety Information 3
Provisions for Lifting and Carrying 4
Cleaning & Maintenance 4
General Specifications 4
Environmental Conditions 4
General Instructions 4
User’s Responsibility 5
INSTALLATION 6
Connections 6
COMPONENT SUMMARY 7
Switches and Indicators 7
Protective Fuses and Relays 8
High Limit Reset 8
Motor Speed Control 8
Adjustments To Speed Control Board 9
Solenoid Valve Module 9
Access to the Controller Cabinet 9
BASIC OPERATION 10
Touchscreen Interface 10
INSTRUCTIONS FOR THE
4848
T REACTOR CONTROLLER 11
Main Screen 11
Alarm Settings 12
Program Operation 12
Temperature Control Module 12
Sample Program 13
Tuning 14
Data Collection 14
Charting 15
Adjusting time 16
Reset Defaults 16
COMMUNICATIONS 17
Ethernet Communications 17
Guide to Smart Networking Practices 17
Using the Web Server 18
Using the VNC Server 18
PARTS LIST 20
Fuses 20
Cooling Solenoids 20
Accessories 20

4848T Reactor Controller with Touchscreen
3
PREFACE
Related Instructions
The following publications are also included to
further your understanding of this instrument and
its component parts:
No. Description
201M Limited Warranty
Scope
These instructions cover the installation, opera-
tion and maintenance of Model 4848T Reactor
Controller as used with laboratory reactors and
pressure vessels. The users should study the instruc-
tions carefully before using any of these controllers
so that they will fully understand the capabilities and
limitations of this equipment and the safety precau-
tions to be observed in its operation.
Applications
Each 4848T Reactor Controller consists of a pack-
aged temperature control unit completely wired
and assembled with appropriate power and safety
relays, switches and pilot lights.
These units are designed specifically for use with
reactors and pressure vessels and are to be
used only with equipment.
Intended Usage
This controller has been designed for use with
pressure vessels and reactors. It has been
designed, built, and tested to strict physical and
electrical standards. However, it is the user’s re-
sponsibility to install and operate it in conformance
with local pressure and electrical codes.
If the instrument is used in a manner not specified
by Company, the protection pro-
vided by the equipment may be impaired.
Unpack Carefully
Unpack the equipment carefully and check all the
parts against the packing list. If shipping damage is
discovered, report it immediately to the delivering
carriers. Examine the components closely for any
loose parts or shipping damage and be sure to
check all layers of packing materials thoroughly so
as not to overlook any parts which might otherwise
be discarded.
Explanation of Symbols
II On position, full power heater switch
IOn position, half power heater switch
OOff Position
~Alternating Current (AC)
This CAUTION symbol may be present
on the Product Instrumentation and
literature. If present on the product, the
user must consult the appropriate part
of the accompanying product literature
for more information.
Protective Earth (PE) terminal. Provided
for connection of the protective earth
(green or green/yellow) supply system
conductor.
Safety Information
To avoid electrical shock, always:
1. Use a properly grounded electrical outlet of
correct voltage and current handling capability.
2. Ensure that the equipment is connected to
electrical service according to local and national
electrical codes. Failure to properly connect
may create a fire or shock hazard.
3. For continued protection against possible
hazard, replace fuses with same type and rating
of fuse.
4. Disconnect from the power supply before
maintenance or servicing.
To avoid personal injury:
1. Do not use in the presence of flammable or
combustible materials; fire or explosion may
result.This device contains components which
may ignite such material.
2. Refer servicing to qualified personnel.

4
Provisions for Lifting and Carrying
Before moving the instrument, disconnect all
connections from the rear of the apparatus. Lift the
instrument by grabbing underneath each corner.
Cleaning & Maintenance
Periodic cleaning may be performed on the exterior
surfaces of the controller with a lightly dampened
cloth containing mild soap solution. All power
should be disconnected and the power cord should
be unplugged when cleaning the 4848T Controller.
There are no user serviceable parts inside the
product other than what is specifically called out
and discussed in this manual. Advanced trouble-
shooting instructions beyond the scope of this
manual can be obtained by calling
Company in order to determine which part(s) may
be replaced or serviced.
CAUTION! Ensure that any hot surfaces
have had adequate time to cool before
cleaning or maintaining the reactor and/
or its components.
General Specifications
Electrical Ratings
115VAC, 15.0 Amps, 50/60 Hz
230VAC, 15.0 Amps, 50/60 Hz
Before connecting a controller to an electrical outlet,
the user must be certain that the electrical outlet has
an earth ground connection and that the line, load
and other characteristics of the installation do not
exceed the following limits:
Voltage: Fluctuations in the line voltage should not
exceed 10% of the rated nominal voltage shown on
the data plate.
Frequency: Controllers can be operated from either
a 50 or 60 Hertz power supply without affecting
their operation or calibration.
Current:The total current drawn should not exceed
the rating shown on the data plate on the controller
by more than 10 percent.
Thermocouple: Unless otherwise specified, all 4848T
Controllers operate with aType-J (Iron-Constantan)
thermocouple. The total resistance of the thermo-
couple and the lead wires should not exceed 100
ohms. If the resistance of the thermocouple circuit is
higher, it will not function properly.
Environmental Conditions
This instrument is intended to be used indoors.
CAUTION! Do not use in hazardous
atmospheres.
Operating: 15 ºC to 35 ºC; maximum relative hu-
midity of 80% non-condensing. Installation Cat-
egory II (over voltage) in accordance with IEC 664.
Pollution degree 2 in accordance with IEC 664.
Altitude Limit: 2,000 meters.
Storage:
-25 ºC to 65 ºC; 10% to 85% relative humidity.
General Instructions
Set the controller on a sturdy bench or table where
there is convenient access to an electrical outlet
with the appropriate supply voltage and current rat-
ings in accordance with national and local electrical
code requirements. Leave a space of at least twelve
inches between the controller and the heater of the
reactor so that the controller will not be affected by
radiant heat.
PREFACE (Continued)

4848T Reactor Controller with Touchscreen
5
User’s Responsibility
All Reactors and Pressure Vessels are designed and manufactured with great care to assure
safe operation when used within their prescribed temperature and pressure limits.
But…the basic responsibility for safety when using this equipment rests entirely with the user;
who must:
1. Select a reactor or pressure vessel that has the capability, pressure rating, corrosion
resistance, and design features that are suitable for its intended use. Our engineers will
be glad to discuss available equipment and material options with prospective users, but
the final responsibility for selecting a reactor or pressure vessel that will perform to the
user’s satisfaction in any particular reaction or test must rest with the user
.
In exercising the responsibility for the selection of pressure equipment, the prospective
user is often faced with the choice between over or under-designed equipment. The
hazards introduced by under-designed pressure vessels are readily apparent, but
the penalties that must be paid for over-designed apparatus are often overlooked.
Recognizing these criteria, our reactors and pressure vessels are offered in several
different styles, each designed for convenient use in daily operation within certain
temperature and pressure limits, using gaskets, closures, and other elements carefully
selected for safe operation within the limits specified for that design. But in order to
preserve the validity of these designs, all temperature and pressure limits must be
observed, and no attempt should be made to increase these limits by making alterations
or by substituting components which are not recommended by Company.
2. Install and operate the equipment within a suitable barricade, if required, with appropriate
safety accessories and in full compliance with local safety codes and rules.
All standard pressure vessels are provided with either a suitable relief device or
a means to attach one (typically in the form of a plugged opening). When a pressure
vessel is delivered without a pressure venting device, it is the customer’s responsibility
to provide pressure relief in order to protect the operator and the equipment from
destructive high pressures. If you need more information or need help in selecting a
proper relief device, please contact Company.
3. Establish training procedures to ensure that any person handling the equipment knows
how to use it properly.
4. Maintain the equipment in good condition and establish procedures for periodic testing to
be sure the vessel remains structurally sound.

6
Connections
Labeled connections are provided on the rear panel
of the controller.
4848T Reactor Controller (230V), Back Side
COOLING
ONLY
The cooling output connector is to be used only
with Company cooling solenoid
valve assemblies supplied with the appropriate
cooling power cord.
HEATING
ONLY
The heating output connector is to be used only
with Company heater assemblies
supplied with the appropriate heater power cord.
MOTOR
The motor output connector is to be used only with
Company motor assemblies sup-
plied with the appropriate motor power cord.
Secure the clamp on motor cord to the controller
with the provided screw next to the motor socket
for safety purposes.
Other appropriate connectors are provided on the
rear panel of the controller.
The PRIMARY TEMP INPUT connection is for the
PrimaryTemperature Module sensor input.
The TEMPERATURE INPUT connection is for the
AuxTemp sensor input.
The PRESSURE INPUT connection is for the Pres-
sure Module sensor input.
The RPM INPUT connection is for the RPM Module
sensor input.
The USB and ETHERNET connection is for Commu-
nication output.
INSTALLATION

4848T Reactor Controller with Touchscreen
7
COMPONENT SUMMARY
4848T Reactor Controller, Front Side
Switches and Indicators
The MAIN POWER switch on the back of the con-
troller will cut off power to the controller. Take care
to position the controller such that the main power
switch may be accessed easily when the controller
needs to be disconnected.
The HEATER Switch is a manual, three-position,
illuminated switch which controls the amount of
power sent to the heater. In the HIGH (II) position,
full power is developed by the heater. In the middle
(O) position the heater is off. In the LOW (I) position,
a diode is switched into the system to allow only one-
half of the rated voltage to be supplied to the heater.
This low setting will be most useful when operating
the reactor at temperatures below 175 °C. Power
for the heater is supplied through a solid state relay
controlled by the temperature control module. The
light in the heater switch will glow only when current
is flowing to the heater.
The HIGH LIMIT indicator light will glow if the
controller receives an indication from any of its
sensors that a high temperature or high pressure
limit has been reached and the HIGH LIMIT RESET
has opened. When the light comes on, the user
must find the source of the problem, correct it, and
then manually reset the system using the HIGH
LIMIT RESET button on the front of the controller.
The MOTOR CONTROLS consist of:
1. AUTO/MANUAL switch
2. ON/OFF(I/O) switch
3. SPEED control knob
The SPEED control knob should be turned down
to a minimum setting before turning on the motor
switch to minimize electrical surges within the
speed control unit.
When the auto/manual switch is in manual mode,
the speed control knob will adjust the motor stir-
ring speed. When the auto/manual switch is in
auto mode, the RPM module will adjust the motor
stirring speed.

8
Protective Fuses and Relays
4848T Reactor Controller (230V), Back Side
An instrument fuse is mounted on the back panel.
This is a Fast-acting, 250VAC, 2.0 amp fuse, intend-
ed to protect the temperature control module and
any installed display modules.
The motor reset/motor fuse provides overload
protection for 0-90VDC motors. This is a re-settable
breaker designed to protect the motor if it becomes
overloaded. The breaker will have a rating selected
to match the motor on the apparatus.
A lighted fuse holder provides protection for 0-180
VDC motors. A light will come on if the motor
becomes overloaded and the fuse burns out. The
fuse rating will be selected to match the motor on
the apparatus.
A load fuse is mounted on the back panel on 115V
systems. This fast-acting, 250VAC, 20 amp fuse
is intended to protect the controller and prevent
electric shock hazard from fault from occurring.
Two load fuses are mounted on the back panel on
230V systems. These are fast-acting, 20 Amps, 250VAC
and are intended to protect the controller and to pre-
vent electric shock hazard from fault from occurring.
The 4848T Controller has a number of fuses which
are intended to be field serviceable. See the Parts
List Section on page 23 for more information.
CAUTION! Unplug unit before servicing.
For continued protection against
possible hazard, replace fuses with same
type and rating of fuse.
Thermocouple burnout protection is included in
each of these controllers. If the thermocouple
should burn out, or if there is a break in the ther-
mocouple circuit, the apparent temperature will
rise to the top of the sensor limit, triggering a
sensor break alarm.
High Limit Reset
Each Series 4848T Controller has a high tempera-
ture limit control which will trip the High Limit
Relay and shut off the heater if the temperature
reaches a preset level. If tripped, the lockout relay
will pop out, thereby preventing the system from
heating the reaction when the temperature falls
back below the limit setting. This must be manually
reset before heating can occur again.
On Model 4848T Controllers the high temperature
limit is preset at the factory to 375 °C for most
systems. If the temperature exceeds the limit, the
controller alarm condition will appear.
Motor Speed Control
4848T Controllers are equipped with a solid
state speed control module for use with the variable
speed, DC motors installed on stirred reactors.
The module itself (approximately 4 inches square) is
mounted inside the chassis on the bottom plate. A
motor switch and a speed adjustment potentiometer
are mounted on the front panel. Each module also
requires a resistor matched to the horsepower of
the motor with which it will be used, as listed in the
following table:
Motor
Rating
Motor
Voltage
Resistor
Required
Part
Number
1/17 HP 90 VDC 0.25 ohm 876E6
1/8 HP 90 VDC 0.10 ohm 876E3
1/4 HP 90 VDC 0.05 ohm 876E
1/4 HP 180 VDC 0.10 ohm 876E3
1/2 HP 90 VDC 0.025 ohm 876E2
1/2 HP 180 VDC 0.05 ohm 876E
3/4 HP 180 VDC 0.035 ohm 876E5
4848T Controllers furnished as a part of a complete
stirred reactor system will have the proper
resistor installed at the factory. Any controller sold
separately will require a motor specification so that
the proper resistor may be provided.
COMPONENT SUMMARY (Continued)

4848T Reactor Controller with Touchscreen
9
Always turn the speed control knob fully counter-
clockwise to the off position before turning on the
motor switch, then advance the knob clockwise
slowly to develop the desired speed. Do not over-
load the motor. Any high speed or high viscosity
load which trips the circuit breaker (90 VDC motors)
is too heavy. Reduce the speed to avoid overload-
ing and use the reset button on the rear panel to
restart the motor.
Adjustments To Speed Control Board
There are five trimpots in the speed control module
that can be used to adjust the performance of the
motor. These are set at the factory for optimum
performance and should not be disturbed unless
customized settings are required to match a par-
ticular set of operating conditions. The instructions
below should be followed carefully if these controls
are to be readjusted.
The CL, current limiting/torque adjustment is set at
the factory to 1.5 times the motor rating. It is intend-
ed to protect both the module and the motor against
overloads and heavy surge currents during startup.
It can also serve as a torque limiting device by reduc-
ing the maximum power output of the system.
The IR, compensation adjustment is used to improve
motor control under varying load conditions. If the
loads do not fluctuate, this control can remain at
approximately one-fourth of full setting. But if the
motor speed drops more than 2% under load, this
adjustment should be increased. If it is set too high,
the motor speed will fluctuate in a cyclical manner.
The MAX, maximum speed adjustment controls
the maximum speed of the motor. To increase
the motor speed, turn the control knob on the
front panel to its maximum setting, then use the
MAX trimpot to raise the speed to the desired
level. Note, however, that the motor may become
dangerous if the speed is raised above the motor’s
rated rpm.
The MIN, minimum speed adjustment can be used
to raise the minimum motor speed. To change this
setting, turn the control knob on the front panel to
its minimum setting, then adjust the MIN trimpot
to obtain the desired minimum speed, this adjust-
ment will also affect the maximum setting, making
it necessary to adjust both MAX and MIN trimpots
to obtain the desired spread.
The ACCEL, acceleration adjustment is normally set
to provide controlled acceleration from zero to full
speed in 2 seconds. It can be adjusted to higher or
lower acceleration times anywhere between 0.5 and
4 seconds, but changing this setting will affect the
MAX speed and IR compensation which will have to
be readjusted. If the acceleration time is reduced to
0.5 seconds (6 o’clock trimpot position), increase the
IR trimpot one quarter turn clockwise and decrease
the MAX trimpot one fifth turn counterclockwise. If
the acceleration time is increased to the maximum
time of 4 seconds (full rotation), the IR trimpot must
be decreased and the MAX increased in the same
rotation amounts mentioned above.
Solenoid Valve Module
This module provides a solenoid valve, a metering
valve and all parts needed to assemble an automatic
cooling system for any reactor. It usually is installed
in a cold water line with a flow connection to the
cooling coil and an electrical connection to the
cooling socket on the back of the 4848T Controller.
Coolant will then be admitted to the coil whenever
cooling is called for by the controller, thereby mini-
mizing any temperature overshoot. This system is
particularly advantageous when holding fixed tem-
peratures below 150 °C or for controlling exothermic
reactions. Compressed air can be used as a coolant
if the amount of heat to be removed is not large.
Access to the Controller Cabinet
To open the controller cabinet, unplug the power
cord and remove the five screws on each side of
the enclosure. Then lift the top cover upwards,
providing full access to all internal components.
CAUTION! Inside of controller cabinet
should be accessed by qualified
personnel only.
COMPONENT SUMMARY (Continued)

10
BASIC OPERATION
Touchscreen Interface
The 4848T display is split into two sections; the icon bar and main display area.
Main Screen
The DISPLAY ICON will open the main menu for navigating to the different control and
monitoring screens. Menu items will dynamically appear providing available options
based on the system area the user is in, i.e., security, data logging, setup, etc.
The INFORMATION (HELP) ICON will display text based help associated with the
current screen. Help is available in 10 languages based on the user selection in the
offline setup of section of 4848T.
The HOME ICON will return the user to the main view from anywhere in the 4848T
application.The main view is set by the OEM in the 4848T configuration and can be
the single or dual loop, chart, alarm, alarm history, event or digital IO view.
The ALARM ICON will appear and flash when a new system alarm occurs. Pressing
the alarm icon will take the user directly to the alarm monitor screen in order to view
and /or reset the active alarm condition.
The left and right NAVIGATION ARROWS will appear on screens that provide additional
information that the user can scroll to such as the loop view screens, charts or program
entry screen in order to cycle through each step of a ramp/soak program.
Note: A single press of the left or right arrows will scroll program steps to the next step or screens to the
next available screen option (i.e. chart number). Pressing and holding the arrow keys will continue the item
scrolling until the last step of the program is reached or the button is released.
CAUTION! Do not use any sharp or metal objects on the touchscreen as
they may damage the surface. Also be sure that hands and fingers are free
from oils or chemicals which may mar the surface of the touchscreen.
Icon Bar
Main
Display

4848T Reactor Controller with Touchscreen
11
INSTRUCTIONS FOR THE
4848
T REACTOR CONTROLLER
Main Screen
The Main Screen of the 4848T shows basic infor-
mation for all four modules:
• Temperature Control Module
• Motor Control Module
• Pressure Module
• AuxiliaryTemperature Module (Option 1 or 2)
1) HighTemperature Cut Off Module (HTM)
2) ExternalTemperature Limit Module (ETLM)
The Setpoint (SP) for each module can be adjusted by
touching the screen where it displays the SP value.
The Process Value (PV) for each module (Tempera-
ture, pressure, RPM) is also shown in real time.
The % shows the power percentage output in real time.
Temperature Control Module
The current temperature is shown
under PV. Selecting SP will allow you
to change the intended temperature
setpoint. The heater output is shown
under%.
Motor Control Module
The current RPM is shown under
PV. Selecting SP will allow you to
change the intended RPM setpoint.
The motor output is shown under%.
Pressure Module
The current pressure is shown under
PV.
(See the Alarms section of this
manual for instructions on adjusting
the pressure alarm.)
Auxiliary Temperature Module (HTM)
High Temperature Cut Off Module
The current temperature is shown
under PV.
(See the Alarms section of this
manual for instructions on adjusting
the AuxiliaryTemperature alarm.)
Auxiliary Temperature Module
(ETLM)
External Temperature Limit Module
The external temperature is shown
under PV. SP is the external tem-
perature cut-off set point. %is an
indicator of ETLM state. When it is
at 100% it will allow theTemperature
Control Module to modulate heater
output. When it is at 0% it will disal-
low further heating until the external
temperature falls back below SP.

12
Alarm Settings
To access Alarm Settings from the main screen,
select the following:
1. Select the Display Icon in the icon
bar at the top of the screen
2. Select the Settings Option from
the main display
3. Select the Display Icon in the icon
bar at the top of the screen
4. Select the Alarm Option from the
main display
The Alarm Settings Menu is shown below and can
be adjusted for the PrimaryTemperature, Pressure,
and AuxiliaryTemperature. Use the Navigation
Arrows in the icon bar to scroll between Alarm #1,
#2, and #3.
Program Operation
To access Program Operation, select the Program
Operation button at the bottom of the main display
on the main screen.
Program Operation allows the Temperature Control
Module or the Motor Control Module to be oper-
ated in Automatic Program (ramp and soak) mode.
The module being worked on appears in the drop
box on top of the window.
Temperature Control Module
TheTemperature control module screen is shown
below. The Run, Hold, and Stop functions are only
utilized when an Automatic Program (ramp and
soak) is active. During typical setpoint operation
these functions are not used.
To create a
ramp and soak
program, select
the Edit option.
INSTRUCTIONS FOR THE
4848
T REACTOR CONTROLLER (Continued)

4848T Reactor Controller with Touchscreen
13
The ramp and soak program is shown below. The
program details can be entered here.
Use the navigation arrows in the icon bar to cycle
between each step, and Insert or Remove to adjust
the number of steps.
File and then select Save from the pop up menu to
save the program to the 4848T, and then Home to
return to the main screen. To engage the program,
click on Program Operation.
The ramp and soak program must be selected by
clicking on Select, and then selecting the program
that you wish to execute. When this is complete,
click on Run.
If you wish to hold or stop the program, return to
the Program Operation screen and click on Hold or
Stop.
Sample Program
A program to heat from 25 °C to 200 °C over the
course of 2 hours, hold for 1 hour, and then cool as
quickly as possible.
Step 1: Type = Ramp
Time hh.mm = 0.00
SP = 25
Step 2: Type = Ramp
Time hh.mm = 2.00
SP = 200
Step 3: Type = Soak
Time hh.mm = 1.0 0
Step 4: Type = Ramp
Time hh.mm = 0.00
SP = 25.0
Step 5: Type = End
SP = 25
Cycle Count = 1
INSTRUCTIONS FOR THE
4848
T REACTOR CONTROLLER (Continued)

14
Tuning
The 4848T has a set of default PID values intended
to give reasonable control across a wide range of
conditions, but tighter control can be had by auto-
tuning the system.
To autotune the temperature meter from the main
screen, select the following:
1. Select the Display Icon in the icon
bar at the top of the screen
2. Select the Settings Option from
the main display
3. Select the Display Icon in the icon
bar at the top of the screen
4. Select the Tuning Option from
the main display to enter the
TemperatureTuning screen
The PID settings can be adjusted here manually.
Unless the operator has a background in PID
control, however, autotuning is recommended.
Autotuning is a method to help the controller deter-
mine the best PID settings to control tightly around
the intended setpoint. To do an autotune, fill the
pressure vessel with conditions as equivalent to
the intended process as possible (do a blank run),
and heat it up to the intended setpoint. Once the
temperature has reached setpoint, click on AT to
engage the autotune. During the autotune process,
the temperature will rise by a few degrees, drop
back down to setpoint, and repeat this process
perhaps three times. This can take a good deal of
time, especially in large vessels or in cases at low
temperatures. When the autotune is complete,
the controller will return to regular setpoint mode,
maintain the intended setpoint, and it will have
rewritten the PID values here to better values.
If you need to halt the autotune before completion,
click on the AT button again.
Data Collection
To set the 4848T to collect data, data collection
must first be enabled. Select the Display Icon and
then Data.
1. Select the Display Icon in the icon
bar at the top of the screen
2. Select the Data Option from the
main display
INSTRUCTIONS FOR THE
4848
T REACTOR CONTROLLER (Continued)

4848T Reactor Controller with Touchscreen
15
The Start Button is used to automatically start log-
ging data when the 4848T is powered up. Switch
the Start toggle to the ON position and then press
the Data button to begin recording data. When you
are finished recording, press the Data button again
to stop recording.
Insert a USB stick into the back of the 4848T. Press
the Display Icon, and then the Open button.
A list of files will be shown. Select the file cor-
responding to the most recent time and press the
Open button. The 4848T will display a chart of the
data selected, and select Return to prepare this
data for copy to the USB stick.
Select the Display Icon, and then USB. On the USB
Screen, select the type of data to export to the USB,
and then select the appropriate copy action to write
to the USB.
Charting
To create a chart, click on the Display Icon, and then
Chart. The Set button will allow you to customize
which variables are charted, along with axis properties.
INSTRUCTIONS FOR THE
4848
T REACTOR CONTROLLER (Continued)

16
INSTRUCTIONS FOR THE
4848
T REACTOR CONTROLLER (Continued)
Adjusting time
To adjust the time from the main screen, select the
following:
1. Select the Display Icon in the icon
bar at the top of the screen
2. Select the Settings Option from
the main display
3. Select the Display Icon in the icon
bar at the top of the screen
4. Select the Offline Option from the
main display
5. Select the Display Icon in the icon
bar at the top of the screen
6. Select the Clock Option from the
main display
Reset Defaults
The 4848T can be reset to it’s factory defaults
easily. This is an excellent measure in the event
that the controller is not operating properly.
To reset the 4848T back to the factory default set-
tings, select the following:
1. Select the Display Icon in the icon
bar at the top of the screen
2. Select the Settings Option from
the main display
3. Select the Display Icon in the icon
bar at the top of the screen
4. Select the Offline Option from the
main display to enter Offline Mode
5. Select the Display Icon in the icon
bar at the top of the screen
6. Select the Configuration Option
from the main display to access
the Configuration screen
Press the Reset default configuration button to
return the settings to the factory defaults.

4848T Reactor Controller with Touchscreen
17
COMMUNICATIONS
This section provides instructions on how to
use the 4848T communication interfaces. As a
standard, the 4848T is equipped with an Ethernet
interface for user communications.
Ethernet Communications
The 4848T provides two forms of Ethernet com-
munication interfaces for monitoring and control-
ling the system across a network.The web server
interface provides a monitor only connection, while
the VNC server interface allows a user to manipu-
late and control the 4848T remotely by viewing the
4848T display directly on their PC screen.
NOTE: In order to use Ethernet communications, the
4848T must be properly connected to a network. To
connect the 4848T to a network, connect the touch-
screen’s Ethernet port to your network using a standard
CAT5 cable connection. Note that after connecting the
network cable, it may be necessary to cycle power to
the 4848T in order for it to obtain a valid IP address.
Guide to Smart Networking Practices
The expansion of Ethernet onto the industrial floor
has brought forth a new realm of possibilities from
the gathering of information to the inherent control
of equipment from anywhere around the world.The
flexibility and convenience that this provides makes
it a very desirable feature for new equipment.The
4848T provides this ability, but there are consider-
ations that must be taken by the end user to protect
their equipment and investment.
Just like placing a personal computer on the internet
opens it up to outside attack, placing your 4848T on a
network poses the same risk.The first thing to re-
member is this:The most likely cause of problems is
not a hacker trying to sabotage your equipment, but
more often to be related to the ubiquity of PCs with
Ethernet cards, the ease with which your own co-
workers can “hang stuff on the network”, and careless
or nonexistent internal security measures. Accidental
problems are more common than deliberate ones.
Allowing anyone access to the 4848T by placing it
on the office LAN, also opens the door for accidental
shutdown, damage to equipment, loss of data, lost
time, etc. This is possible even by the most well-
intentioned co-workers. Thus, there are several steps
that should be taken to minimize this risk.
The first is to never mix your office LAN with your
control LAN.The control LAN should be a separate
network that consists of your 4848T controller(s) and
possibly any other equipment that you may have that
is related to the operation of the system. It should be
separated from your office LAN by a firewall, or at
minimum, a bridge or router. A control network and a
business network have two entirely different purpos-
es and their interaction should be closely controlled.
It is also unwise to assume that any Ethernet capable
devices themselves have any security features at all.
The 4848T VNC server only provides minimal single-
password based security access. Separating the con-
trol LAN from the office LAN using a firewall would
increase security and only allow control access that
is based on a combination of IP source address,
destination address, and port number.This is by no
means completely “hacker-proof”, but it should keep
the well-meaning co-workers out.
Another hazard is connecting consumer “plug and
play” devices to your control LAN. A printer for
example, might flood the network with traffic in a
“broadcast storm” as it tries to self-configure or
advertise its presence to all nodes on the network.
Faulty devices, for example defective NIC cards,
can transmit large amounts of bad packets (i.e.,
runts, which are abnormally short Ethernet frames)
into your network. Using switches instead of hubs
will limit the effect of such problems.
The most commonly overlooked source of prob-
lems is cabling. Not all cables are created equal.
Electrical noise generated by factory equipment or
other electrical equipment in the area, could easily
corrupt transmitted data over the network and
cause devices to “lock up” or shut down the VNC
server, both of which then require the 4848T to be
shut down and restarted to clear the problem.
Select the right cable for the environment. Shielded
twisted pair (STP) cable is naturally more noise
immune and is preferable to unshielded twisted pair or
UTP in noisy situations. STP should have at least 40dB
CMRR and less than 0.1pF capacitance unbalance per
foot. Ground STP cable, making sure the ground is
connected only at one end. CAT5 STP patch panels
normally provide a grounding strip or bar. Hubs and
switches don’t provide grounding, use cables.

18
It’s wise to be pessimistic about a cable’s ability to
reject noise from 230 VAC and 460 VAC power lines
and electrically “noisy” equipment in the area.
Capacitance imbalance in cables greater than 70pF
per 100m can introduce harmonic distortion result-
ing in bit errors.The cost of cable is quite small
compared to total equipment cost, so if you’re
looking to save money, this is not a place to do
it. Choose a well designed cable to minimize bit-
error rate after installation, and that will give faster
throughput with fewer glitches.
Using the Web Server
The 4848T web server allows a user to remotely
monitor operations anywhere via a PC’s standard
web browser. When enabled, the web server pro-
vides a detailed status page of the current operat-
ing conditions.The web server can be enabled and
disabled by pressing the web server (Www.) button
on the communications screen (select “Comms”
from the Device\Settings\Set menu).
You must use the assigned IP address to access the
4848T.The IP address is shown on the communica-
tions screen and is also included in the notifications
list. Write down the IP address so you will have it
later to enter into your web browser.
NOTE: Contact your network administrator prior to
enabling the web server of the 4848T. Company policy
may prohibit the use of web servers for security rea-
sons. Future Design Controls is not responsible for the
use of, nor makes any claims as to the security of the
web server interface over your network. The use of
the web server is the responsibility of the end user.
To access and view the 4848T web page, enter
the following link in your PC’s browser address
window: http://”IPaddress”/orion.html. Using the IP
address from the sample screen, the entry would
be: http://192.168.1.2/orion.html.The following
example is typical of the 4848T web page appear-
ance.The web page updates automatically every
30 seconds and provides information on each
individual control loop, ramp/soak program status,
alarm status and system event status.
Using the VNC Server
The 4848T VNC server allows a user to remotely moni-
tor and control 4848T by directly viewing and
manipulating the touchscreen over the network.You
must use the assigned IP address and VNC port number
to access 4848T.The IP address is shown on the commu-
nications screen and is also included in the notifications
list. Write down the IP address and port number so you
will have it to enter into your VNC viewer.
COMMUNICATIONS (Continued)

4848T Reactor Controller with Touchscreen
19
There are many VNC viewers available for both PC
and tablet use. Due to the ever changing market and
availability of such applications, it is not possible to
test them all for compatibility or provide assistance
for their use with the 4848T. It is the responsibil-
ity of the end user to test the chosen VNC client
for compatibility with the 4848T prior to putting
the unit into service. If the VNC client viewer has
compatibility issues with the 4848T, it can cause the
VNC server to stop responding and/or shut down
requiring power to be cycled to the 4848T in order
to reboot the system and restart the server.
Company has tested and recom-
mends the use of RealVNC’s viewer. It has been
tested for compatibility with the 4848T and a free
version can be obtained from RealVNC for PC/MAC
use. RealVNC does offer a version for the iPad that
can be obtained through the App Store for a small
fee.
NOTE: Contact your network administrator prior
to enabling the VNC server of the 4848T. Company
policy may prohibit the use of VNC servers and/
or viewers for security reasons.
Company is not responsible for the use of, nor
makes any claims as to the security of the VNC
server interface over your network. The use of the
VNC server is the responsibility of the end user.
Once the connection is established, the current
4848T display will be shown on your desktop.The
image will be a duplicate of what is on the 4848T.
As you manipulate the screen, the display of the
4848T will also be manipulated so that any local
operator will be able to see what is happening and
vice versa.
Multiple instances of the VNC viewer can be started
on your PC. By running multiple viewers, you can
have access to multiple 4848T controllers right
from your desktop.The heading of each VNC viewer
window will use the “VNC Device Name” entry for
the header. By entering a unique name for each
4848T, you can identify each VNC connection and
know which system you are accessing.
The VNC viewer is meant to be used for short term
control access to the 4848T. It is not meant for long
term monitoring of system operation. If long term
monitoring access is desired, use the built-in web
server of the 4848T or a PC with FDC software to
monitor and control the 4848T over its serial com-
munications port. The web server interface and PC
software is designed for long term monitoring and
status updates.
Due to the nature of VNC operation, and for secu-
rity reasons, the VNC viewer connection should
not be left open on your desktop.The viewer con-
nection should be opened in order to perform the
necessary control and/or status check of system
operation, and then closed once the task is com-
plete. Accidental manipulation of the control or
erroneous network activity could cause connection
problems over the VNC interface and result
in the VNC server shutting down and requiring the
4848T to be restarted in order to regain access.
NOTE: Some viewers may also contain additional
features for file transfer and other high level func-
tions. These functions are NOT compatible with
the 4848T. Any attempt to use them may cause
the 4848T VNC server to malfunction and require
power to be cycled in order to reboot the system.
COMMUNICATIONS (Continued)

20
PARTS LIST
Fuses
Part No. Fuse Rating
139E6 Instrument Fuse Fast acting, 1 Amp, 250VAC
139E10 Cooling Fuse Fast acting, .25 Amp, 250VAC
2074E Line Fuse(s) Fast acting, 20 Amp, 250VAC
959E5 Motor Board
Fuse (A+)
Very Fast acting, 8 Amp,
250VAC
185E2 Motor Board
Fuse (L)
Fast acting, 10 Amp, 250VAC
Motor breaker / fuse
139E8 1/2 hp, 180VDC Slo-blo, 2.5 Amp, 250VAC
139E19 1/4 hp, 180VDC Slo-blo, 1.5 Amp, 250VAC
139E20 3/4 hp, 180VDC Slo-blo, 4.0 Amp, 250VAC
801E 1/12 hp, 90VDC Circuit breaker, 1.0 Amp
801E 1/17 hp, 90VDC Circuit breaker, 1.0 Amp
801E3 1/8 hp, 90VDC Circuit breaker, 1.5 Amp
801E2 1/4 hp, 90VDC Circuit breaker, 2.5 Amp
801E4 1/2 hp, 90VDC Circuit breaker, 5.0 Amp
CAUTION! For continued protection
against possible hazard, replace fuses
with same type and rating of fuse.
Cooling Solenoids
Part No. Description
A160HW3EB Solenoid Valve Pkg 115V
A160HW3EE Solenoid Valve Pkg 230V
A160HW7EB Solenoid Valve Pkg 115V 10FT
A160HW7EE Solenoid Valve Pkg 230V 10FT
A160HW8EB Solenoid Valve Pkg 115V 20FT
A160HW8EE Solenoid Valve Pkg 230V 20FT
A160HW9EB Solenoid Valve Pkg 115V 30FT
A160HW9EE Solenoid Valve Pkg 230V 30FT
Accessories
Temperature (Temperature Control Module)
Aux. Temp. (Auxiliary Temperature Module)
Part No. Description
A470E2 Thermocouple extension wire, 5-ft
A470E4 Thermocouple extension wire, 10-ft
A470E7 Thermocouple extension wire, 15-ft
A470E5 Thermocouple extension wire, 20-ft
A470E8 Thermocouple extension wire, 25-ft
A470E6 Thermocouple extension wire, 30-ft
A470E9 Thermocouple extension wire, 35-ft
A470E10 Thermocouple extension wire, 40-ft
A472E Thermocouple, type-J, 7-1/2" length
A472E2 Thermocouple, type-J, 9-1/2" length
A472E3 Thermocouple, type-J, 11-1/2" length
A472E4 Thermocouple, type-J, 5-1/2" length
A472E5 Thermocouple, type-J, 21-1/2" length
A472E6 Thermocouple, type-J, 15-1/2" length
A490E Dual T/C, type-J, 7-1/2" length
A490E2 Dual T/C, type-J, 9-1/2" length
A490E3 Dual T/C, type-J, 11-1/2" length
A490E4 Dual T/C, type-J, 5-1/2" length
A490E5 Dual T/C, type-J, 21-1/2" length
A490E6 Dual T/C, type-J, 15-1/2" length
A511E2 Heater T/C, type-J, bayonet style
A511E4 Heater T/C, dual, type-J, bayonet style
Table of contents
Other Parr Instrument Controllers manuals