ParTech SludgeWatch 8200w2 User manual

INSTRUCTION MANUAL
SludgeWatch 8200w²
Fixed Sludge Level etector
Issue 01

8200w² Monitor Instruction Manual
** This page is intentionally left blank **
Page 2 of 34 229844IM Issue 01 Issue ate 24/06/2019

8200w² Monitor Instruction Manual
Table of Contents
1 Foreword.......................................................................................................................................................................... 5
2 Introduction...................................................................................................................................................................... 6
2.1 Manual Conventions................................................................................................................................................ 6
2.2 WaterWatch² Trademark......................................................................................................................................... 6
2.3 Scope of Manual...................................................................................................................................................... 6
2.4 Options.................................................................................................................................................................... 6
2.4.1 Compatible Sensors.....................................................................................................................................6
2.5 Quick Overview....................................................................................................................................................... 7
2.5.1 Fault Indication............................................................................................................................................. 7
2.5.2 Alarm Activation............................................................................................................................................ 7
2.5.3 elay Operation............................................................................................................................................ 7
2.5.4 Alarm Relays................................................................................................................................................. 7
2.5.5 Fault Relay.................................................................................................................................................... 7
2.6 Applications............................................................................................................................................................. 7
2.6.1 Sludge Blanket Level etection....................................................................................................................7
3 Safety Precautions........................................................................................................................................................... 8
3.1 General.................................................................................................................................................................... 8
3.2 Electrical Installation................................................................................................................................................ 8
3.3 Operating................................................................................................................................................................. 8
3.4 Service and Maintenance........................................................................................................................................9
3.5 End of Life isposal................................................................................................................................................. 9
4 Installation..................................................................................................................................................................... 10
4.1 Mechanical Installation.......................................................................................................................................... 10
4.2 Installation Considerations....................................................................................................................................10
4.3 Fixings................................................................................................................................................................... 11
4.4 Electrical Installation.............................................................................................................................................. 12
4.4.1 Gland Configuration.................................................................................................................................... 12
4.4.2 C Power Connections.............................................................................................................................. 13
4.4.3 AC Power Connections............................................................................................................................... 13
4.4.4 Sensor Connections...................................................................................................................................14
4.4.5 Extending Sensor Cables........................................................................................................................... 14
4.4.6 Relay Outputs (Alarms)..............................................................................................................................15
5 Basic Operation.............................................................................................................................................................. 16
5.1 Keys and Screen Navigation................................................................................................................................. 16
5.1.1 Menu Button............................................................................................................................................... 16
5.1.2 Navigation Buttons...................................................................................................................................... 16
5.1.3 OK Button................................................................................................................................................... 16
5.2 Measurement Screen............................................................................................................................................ 16
5.3 System Configuration............................................................................................................................................ 16
5.4 efault Configuration............................................................................................................................................. 17
6 Operational Menus......................................................................................................................................................... 18
6.1 Monitor Config Menu............................................................................................................................................. 18
6.1.1 Bleeper........................................................................................................................................................ 18
6.1.2 Backlight..................................................................................................................................................... 18
6.1.3 Contrast...................................................................................................................................................... 18
6.1.4 Language.................................................................................................................................................... 19
6.1.5 Set Time/ ate............................................................................................................................................. 19
6.1.6 Enable Service Mode.................................................................................................................................. 19
6.2 Sensor Config........................................................................................................................................................ 20
6.2.1 Sensor Status............................................................................................................................................. 20
6.2.2 Add Sensor................................................................................................................................................. 20
6.2.3 S:0x Info...................................................................................................................................................... 21
6.2.4 S:0x Averaging........................................................................................................................................... 21
229844IM Issue 01 Issue ate 24/06/2019 ` Page 3 of 34

8200w² Monitor Instruction Manual
6.2.5 Sensor Removal......................................................................................................................................... 22
6.2.6 S0x Faults................................................................................................................................................... 22
6.3 Alarm Config (Relay outputs)................................................................................................................................22
6.3.1 Alarm status................................................................................................................................................ 22
6.3.2 Alarm x Config............................................................................................................................................ 23
6.4 Alarm 3 (Fault Alarm)............................................................................................................................................24
6.5 Information............................................................................................................................................................. 24
6.5.1 Monitor Information.....................................................................................................................................24
6.5.2 Contact Information....................................................................................................................................24
6.6 Lock Config............................................................................................................................................................ 25
6.6.1 Lock Monitor............................................................................................................................................... 25
6.6.2 Change Password......................................................................................................................................25
6.6.3 Set Auto Lock..............................................................................................................................................25
7 Sludge Blanket Level etection..................................................................................................................................... 26
7.1 escription............................................................................................................................................................. 26
7.2 Sensor Installation.................................................................................................................................................26
7.3 Monitor Configuration............................................................................................................................................ 26
7.3.1 Blanket not detected...................................................................................................................................27
7.3.2 Blanket continually detected....................................................................................................................... 27
8 Menu Tree...................................................................................................................................................................... 28
9 Maintenance.................................................................................................................................................................. 29
9.1 On-Board Battery Backup Replacement............................................................................................................... 29
10 Technical Support........................................................................................................................................................ 30
10.1 Returning Equipment for Repair.......................................................................................................................... 30
11 Technical Specification................................................................................................................................................ 31
11.1 Physical............................................................................................................................................................... 31
11.2 User Interface...................................................................................................................................................... 31
11.3 Electrical.............................................................................................................................................................. 31
11.4 Sensors and Optional Interfaces.........................................................................................................................31
Page 4 of 34 229844IM Issue 01 Issue ate 24/06/2019

8200w² Monitor Instruction Manual
1 Foreword
8200w² Monitor is another “Operator Interface” to the WaterWatch² family of measuring instruments and
sensors, and has been developed to be the successor to the very popular 8100 & 8200 Monitors. Using the
latest embedded processor technology, the 8200w² Monitor has been designed to encompass an easy to
use and intuitive interface while providing advanced features and communication protocols to satisfy the
most demanding of applications and environments.
The 8200w² Monitor is designed to interface with all members of the SoliTechw² IR Sensor family. The
standard 8200w² Monitor provides connectivity for 1 or 2 sensors. It provides two alarm relay outputs (one for
each channel) and a single fault relay output. The fault relay is used to indicate a fault on either input
channel. The 8200w² Monitor has two pairs of set point and delay controls. The alarm set point and delay for
each channel can be independently set and the status of each channel is indicated separately.
229844IM Issue 01 Issue ate 24/06/2019 ` Page 5 of 34

8200w² Monitor Instruction Manual
2 Introduction
2.1 Manual Conventions
All dimensions stated in this manual are in millimetres unless otherwise indicated.
The manual has been written assuming the user has a basic knowledge of instrumentation and an
understanding of the type of measurements being made. Training in the use of the 8200w² Monitor and
sensors can be provided, please contact Partech for further information.
Icons have been used throughout this manual to draw your attention to precautions and useful notes.
They are categorised in the following way:
NOTES: Specifications and general notes of interest to the user.
GENERAL CAUTION: Used where caution is required to prevent injury, damage, corruption of
data, loss of calibration or invalidation of warranty etc.
INSTALLATION NOTES: General installation notes of interest to the installer.
ELECTRICAL CAUTION: Used where there is a danger of electric shock to the installer or end
user, or where caution is required to prevent damage to the instrument.
MAINTENANCE NOTES: Used to highlight recommended maintenance procedures and help with
fault finding.
ENVIRONMENTAL NOTES: General notes on environmental issues, waste and disposal.
2.2 WaterWatch² Trademark
WaterWatchw² is the family name for the w² range of monitors and sensors. Sensors and instruments
designed for specific use with the 7300w² & 8200w² Monitors will be suffixed with the w² trademark.
2.3 cope of Manual
This manual describes the installation, configuration, testing and operation of the 8200w² Monitor. While
basic configuration of sensors is included in this manual, please refer to the specific user manual for each
sensor for a comprehensive configuration set-up.
2.4 Options
Part No. Description
229623 SludgeWatch 8200w² Fixed Sludge Level etector (85 to 264VAC, 3 x Relay Outputs)
229624 SludgeWatch 8200w² Fixed Sludge Level etector (9 to 36V C, 3 x Relay Outputs)
2.4.1 Compatible ensors
The 8200w² monitor can be used with the following Partech sensors:
Part No. Description
223893 SoliTechw² IR Sensor (Range: 0-200 mg/l, Cable Length: 10 metres)
223895 SoliTechw² IR Sensor (Range: 0-1,500 mg/l, Cable Length: 10 metres)
223897 SoliTechw² IR Sensor (Range: 0-10,000 mg/l, Cable Length: 10 metres)
223899 SoliTechw² IR Sensor (Range: 0-30,000 mg/l, Cable Length: 10 metres)
All the above sensors are available with 20 metre options. Contact Partech for details.
Page 6 of 34 229844IM Issue 01 Issue ate 24/06/2019

8200w² Monitor Instruction Manual
2.5 Quick Overview
2.5.1 Fault Indication
Fault indication is via the main display clearly visible on the front panel of the monitor. When there is a
fault present ‘FAULT’ is displayed and fault relay will enter into the alarm condition.
2.5.2 Alarm Activation
With the sensor(s) clear and not in a fault condition ‘OK’ is displayed next to associated sensor. If
however, the sensor is obscured or blocked then the specific sensor relay will enter into the alarm
condition and ‘ALARM’ will be displayed next to associated sensor.
2.5.3 Delay Operation
A delay can be introduced between conditions for an alarm turning on being met and the relay
changing state. At any time during the selected delay, if the conditions for turning the alarm on are
removed, then the delay will end and the alarm relay will not change state. Similarly a second delay
can be introduced between conditions when an alarm turning off and the relay changing state.
These delays can be set between 1 & 90 seconds. The delay functions are in place to try to avoid the
occurrence of false alarms that may be caused by suspended debris or conversely the clearing of
alarms prematurely.
2.5.4 Alarm Relays
The alarm relays are internally configured for fail safe operation. When power is applied and the
sensors are clear the relays will be energised, on alarm the relays are de-energised. Each alarm has
normally closed and normally open contacts for external signalling, the normal condition is when the
unit is powered and the alarm is off. There are two alarm relays each assigned to a sensor.
2.5.5 Fault Relay
The fault relay is activated in two instances: when there is a problem with a sensor or due to a failure
in the power supply to the system. In the latter case, this will cause the relay to be de-energised,
resulting in a fault state. The fault relay is common to both channels on the 8200w² and will be
activated if one of the sensors fails or is removed. A sensor fault could be as simple as the sensor
connector is unplugged or wire broken and the monitor can no longer communicate with the sensor.
The relay can be wired as normally closed or normally open on the output side depending on customer
preference.
2.6 Applications
The 8200w² Monitor, when combined with a compatible sensor, is designed for use as a sludge
blanket level detector, a sludge density switch, or as a suspended solids/turbidity switch. The 8200w²
Monitor is therefore suitable for interfacing with automatic de-sludging control of primary and
secondary settlement tanks, thickener control through high and low blanket level alarm, or as a simple
alarm in a water/ waste water flow.
2.6.1 ludge Blanket Level Detection
When used for this operation the monitor uses an SoliTechw² IR series sensor, which is suspended by
its cable to the desired monitoring depth in the tank. When the settled sludge reaches the sensor then
the alarm output is activated. This can then be used as an input to a process system to directly control
pumps, bell mouths or simply to alert the operator. The same principle can be used to monitor when
the sludge reaches a minimum point when it is being removed from the holding tank.
229844IM Issue 01 Issue ate 24/06/2019 ` Page 7 of 34

8200w² Monitor Instruction Manual
3 afety Precautions
3.1 General
Read the safety precautions carefully.
Check the delivery of your 8200w² Monitor for damage. Any damage should be reported to your supplier as
soon as possible.
Use care when unpacking the monitor. NEVER use sharp instruments to open the packaging, as this can
cause damage to the membrane keyboard or display.
Only use sensors and accessories specifically manufactured by Partech for use with this monitor.
Read the operating instructions carefully before installing and operating this monitor.
Keep sharp instruments away from the keypad or display.
Keep the monitor dry and free from dust contamination during installation.
Keep the monitor out of direct sunlight and away from other heat sources.
Keep the monitor away from any other equipment that may radiate electromagnetic influences.
Keep the monitor and cabling away from high voltage cables.
3.2 Electrical Installation
Only suitably qualified personnel may install, operate or repair this equipment. The installer must ensure all
electrical installations comply with local wiring regulations and standards (refer to BS7671 for UK
installations).
Please check the correct voltage is applied to the monitor before making live. Incorrect supply voltage can
cause damage to the 8200w² Monitor.
Only connect sensors from the w² range to this monitor, other Partech products without the w² reference are
not compatible and may cause damage if connected. IF IN OUBT, PLEASE ASK.
Never work on a live monitor. High Voltages may be present on the circuit boards.
Beware, even when the monitor is electrically isolated from the supply, there is still the possibility of live
voltage on the telemetry terminals from the end user (relay outputs). Please ensure the end user has isolated
any telemetry voltages before undertaking any work or testing.
3.3 Operating
The users must acquire the appropriate knowledge to use the equipment in their specific application, as this
monitor can be used for a wide range of applications.
Partech are always available to provide advice and assistance with your application. Please contact Partech
for further information.
Sensors attached to this monitor must be correctly calibrated. Please follow the procedures for installation
and calibration as provided in the instruction manual for your Partech sensor.
Page 8 of 34 229844IM Issue 01 Issue ate 24/06/2019

8200w² Monitor Instruction Manual
3.4 ervice and Maintenance
Before maintenance, this equipment must be isolated or disconnected from HAZAR OUS LIVE voltages
before access.
Maintenance for the 8200w² Monitor should be carried out as specified in this instruction manual. Failure to
carry out regular maintenance could invalidate the Warranty.
Services and repairs must be carried out by a Partech engineer. Partech can provide a service contract for
your system. Please ask for details.
3.5 End of Life Disposal
This equipment should be recycled according to local regulations.
Partech can provide recycling and disposal of your old Partech equipment, and may also provide the same
service for other manufacturers equipment when replaced with Partech equipment.
Partech may provide a trade-in option for old Partech equipment when upgrading your system. Please
contact us for further information.
229844IM Issue 01 Issue ate 24/06/2019 ` Page 9 of 34

8200w² Monitor Instruction Manual
4 Installation
Whilst all attempts have been made to ensure that these instructions are correct, common sense and good
engineering practice should always be used, as every installation can present a new set of challenges and
difficulties. If you are in any doubt please contact Partech or your local distributor for further information.
4.1 Mechanical Installation
Monitor external dimensions.
4.2 Installation Considerations
Below are a number of points to be considered when deciding on a final location to install or mount the
8200w² Monitor.
•If the monitor requires regular inspection or local reading of measurements, ensure the monitor is
mounted in a position that allows for easy reading. Consider operators of all heights.
•If the sensor is to be calibrated by a single person, consideration should be paid to the proximity of
the monitor to the sensor. Some sensors require constant monitoring or staged inputs during the
calibration process. This could be difficult if the sensor is remote from the monitor.
•Keep the monitor out of direct sunlight. This can make the display difficult to read, and in extreme
conditions could cause the monitor to overheat and fail.
•Keep the monitor away from other heat sources or electronics that may transmit or radiate
electromagnetic influences.
•Keep the monitor away from mains power cables, variable speed drives and motor controllers.
•The monitor is suitable for the most demanding of environments. Where there is a likelihood of
physical damage, salt-water spray or cleaning by high pressure hoses, we advise the monitor is
installed inside an enclosure for added protection.
Page 10 of 34 229844IM Issue 01 Issue ate 24/06/2019

8200w² Monitor Instruction Manual
4.3 Fixings
The 8200w² Monitor has 3 fixing points for mounting. Follow these instructions for easy installation and
mounting.
•Offer the monitor up to the final mounting position. Mark the wall behind with a dot halfway along the
top of the enclosure.
•Measure down from the dot 27mm and fit an M4 screw. Ensure the screw has 3.5mm of thread
exposed for a snug fit.
•Hang the enclosure on the screw using the hanging bracket moulded into the back of the monitor
(Loosen the screw if too tight to hang).
•Remove the lower terminal strip cover to reveal the two lower fixing slots (shown as A on the
illustration below).
•Level the Monitor with a spirit level and mark the two lower slots.
•Remove the enclosure and fix drill/tap the above marks.
•Rehang the enclosure (Tighten the top screw if the enclosure feels loose) and fit the two lower
screws. The enclosure has a 14mm shoulder so fixing screws must be at least 16mm long to
penetrate beyond the back of the enclosure.
•Refit the lower terminal cover.
229844IM Issue 01 Issue ate 24/06/2019 ` Page 11 of 34
AA

8200w² Monitor Instruction Manual
4.4 Electrical Installation
Unscrew the two cover screws on the lower panel of the 8200w² Monitor to reveal the Terminals. Each
terminal strip is labelled as illustrated below. (This equipment must be isolated or disconnected from
HAZAR OUS LIVE voltages before access).
The maximum size wire that can be terminated is 2.5mm² CSA. All the connections are via removable
Plug/Socket terminals. To disengage the terminals, simply pull down to release.
Two power options are available for the 8200w² Monitor, AC and C. Apart from the supply voltage, all other
connections are identical.
4.4.1 Gland Configuration
The 8200w² Monitor is supplied with IP68 Skintop Nylon glands with lock nuts in the following configuration:
•Left: 1 x USB connection
•Centre 4 x M16 glands (4.5-10mm Ø cable)
•Right: 1 x M20 gland (5-10mm Ø cable)
Gland holes are clearance, not tapped. Always blank unused glands to retain the IP rating of the enclosure
Cabling
When selecting and calculating the mains power cable, please note, an ambient temperature of 60ºC may
see a rise to 80ºC within the terminal compartment. This should be considered when making your
calculations, therefore we recommend a power cable with a maximum rating no less than 80ºC.
Recommended cables include H07RN-F, Steel Wire Armoured or YY, CY or SY types (always check
cable data sheets for maximum temperature ratings, as this can vary between manufactures).
Page 12 of 34 229844IM Issue 01 Issue ate 24/06/2019

8200w² Monitor Instruction Manual
(Refer to BS7671, section 522 “Selection and erection of wiring systems in relation to external
influences” for guidance).
Shrouded Bootlace Ferrules should always be used when terminating conductors.
4.4.2 DC Power Connections
The C power connection is a 3 way terminal strip, located furthest right of the termination
bank. The left terminal is the Positive (+) supply, the Right terminal is the Negative (-) or Zero
voltage supply and the centre terminal is the Ground.
The power supply is galvanically isolated from all other terminals on the 8200w² Monitor. It is not
necessary to connect a ground to the monitor,.This terminal has been provided for convenience.
The C powered 8200w² Monitor is powered typically from a 12V to 24V C supply.
Min/Max Voltages are 9V to 36V. We do not advise operating the monitors in the field at
voltages approaching the Min or Max values as surges, dips or ripples in supply can fall outside
the Max/Min limits and can cause damage or interruptions to the performance of the 8200w² Monitor.
It is recommended that a circuit protective device (5A Trip) or fuse (5A anti-surge fuse) is fitted to the supply
voltage in close proximity to the monitor and located in a position where it is not difficult to operate, replace
or reset the device. The monitor has an on-board 3.5A fuse for internal protection and is fitted with a reverse
polarity diode.
In addition to the protective device, we advise a local isolator or disconnection switch is fitted in close
proximity to the monitor to allow easy disconnection or isolation of the monitor. This switch should be in easy
reach of the operator and clearly marked as the disconnection device for this equipment. This allows for easy
power-down of the monitor during servicing or periods where the monitor is not being used.
NOTE: If the equipment is used in a manner not specified by this manual, the protection provided by the
equipment may be impaired.
4.4.3 AC Power Connections
The AC power terminal strip is a 3 way connector, located furthest right of the termination bank.
The left terminal is the Earth (E), the Right terminal is the Live supply (L), and the centre
terminal is the Neutral Supply (N).
The AC powered 8200w² Monitor is powered typically from a 100VAC to 240VAC 50/60Hz
supply.
Min/Max voltages are 85VAC to 264VAC, 47Hz-63Hz. We do not advise operating the monitors
in the field at voltages approaching the Min or Max values as surges, dips or ripples in supply
can fall outside the Max/Min limits and can cause damage or interruptions to the performance
of the 8200w² Monitor.
The supply voltage should be fitted with a 3A Type C MCB (the monitor is prone to inrush currents during
initial power up, therefore a “Motor Rated” Type C MCB should be used to prevent nuisance tripping).
It is recommended that a circuit protective device or MCB is situated in close proximity to the monitor, and
located in a position where it is not difficult to operate or reset the device.
In addition to the protective device, we advise a local isolator or disconnection switch is fitted in close
proximity to the monitor to allow easy disconnection or isolation of the monitor. This switch should be in easy
reach of the operator and clearly marked as the disconnection device for this equipment. This allows for easy
power-down of the monitor during servicing or periods where the monitor is not being used.
The monitor should be adequately earthed. Circuit Protective Conductor (Earth conductor) Cross Sectional
Area (CSA) should not be less than the CSA of the calculated phase conductors.
(Refer to BS7671, section 543 “Protecti e Conductors” for guidance).
NOTE: If the equipment is used in a manner not specified by this manual, the protection provided by the
equipment may be impaired.
All external wiring should comply with local wiring regulations and standards.
The monitor has an insulation resistance of 3KV, however, care should be taken when conducting insulation
resistance tests. We advise the AC terminal strip is disengaged from the circuit board before such tests are
carried out.
229844IM Issue 01 Issue ate 24/06/2019 ` Page 13 of 34

8200w² Monitor Instruction Manual
4.4.4 ensor Connections
When routing the sensor cables, please ensure all cables are separated from any mains cables.
Although the WaterWatch² sensors have a high resistance to interference, separation of mains and
data cables is always good practice and should be followed where practical.
All WaterWatch² sensors and Expansion Boxes communicate with the monitor using the ModTechw²
Protocol. This is a modified Modbus Protocol and has been specifically developed to take advantage
of the advanced features and diagnostics designed into the w² range of sensors.
Note: These sensors can NOT be used with other monitors that are not included in the w² family.
All sensors within the w² family of instruments are connected to the 8200w² Monitor using the same 4 wire
configuration, however some slight variations may occur with specific sensors. Always check the manual
supplied with the sensor to ensure the correct termination is applied.
•RE and BLACK wires provide the 12V C supply to
the sensor and the communication ground.
•WHITE and GREEN provide data communication.
A maximum of two sensors can be directly connected to the
standard 8200w² Monitor, however additional sensors can be
added using optional Expansion Boxes available separately.
Remove the 4-way connector from the 8200w² Monitor by
pulling downwards to disconnect for easy access to the
connections. Connect the sensor cores as follows:
(Terminals from left to right on the 4 way connector)
Term 1 (Left) - RE (+12V)
Term 2 - Black (0V) and rain
Term 3 - White ( ata A)
Term 4 (Right) - Green ( ata B)
Always connect the screen drain wire with the Black (Term 2). Illustration right shows
drain wire and Black wire connected together, and covered in Black Heat shrink.
Always use Bootlace ferrules when terminating the sensors to ensure a good
connection to the terminals.
4.4.5 Extending ensor Cables
Sensors are usually supplied with 10m cables (longer cables can be provided on request). These cables can
be extended to a maximum length of 100m. To ensure optimum performance, we advise the use of Partech
ModTechw² cable for extensions. Partech can supply Junction Boxes to allow for easy termination of cable
extensions. These should be used on all installations where the cable length from the sensor to the monitor
exceeds 20M (Partech Junction Boxes include on-board filtering for long cable lengths). Junction Boxes are
also useful for local connection of sensors close to the sample point. This permits easier replacement of
sensors without the need to pull back cables to the monitor. The Junction Box has an on-board terminator
switch that can be activated to terminate the network if the sensor is to be removed for long periods.
When joining cables, ensure the connection is fully waterproof. Any moisture ingress can effect the
performance of the sensor and monitor. Always ensure the earth screen is continued when making joints.
ModTechw² Cable specification:
•2 Twisted Pair: Red/Black (Power) and Green/White ( ata) with Screen and rain wire
•Cores 24AWG (0,22mm²) 7 x 0,20mm
•Outer Insulation: PUR Polyurethane Blue (RAL5003), iameter – 5mmØ
Page 14 of 34 229844IM Issue 01 Issue ate 24/06/2019

8200w² Monitor Instruction Manual
4.4.6 Relay Outputs (Alarms)
The relay outputs are 3 way terminal strips, located in the middle of the termination bank. The 8200w²
Monitor offers 3 SPCO relay contacts that are user configurable.
Please refer to the “Alarm Configuration” section of this manual for details of how to configure the relays for
alarms or process control outputs.
The relays can switch non-inductive loads up to a maximum of 5A, and withstand voltages up to 240VAC.
Please note, for “Alarm” applications the relays are fail safe. Once configured, the relays will remain
energised in a non-alarmed state (Healthy), therefore N/C will be “Open Circuit”, and N/O will be “Closed
Circuit”. uring an Alarm condition, system fault or power failure the relay will de-energise, returning back to
the state illustrated on the label. If the alarm has not been configured, the relay will remain de-energised.
229844IM Issue 01 Issue ate 24/06/2019 ` Page 15 of 34

8200w² Monitor Instruction Manual
5 Basic Operation
5.1 Keys and creen Navigation
All menus and parameter settings are accessed using the 8200w² Monitor membrane keypad.
5.1.1 Menu Button
From the measurement display screen press to show the Main Menu. While in sub menus, acts as a
return to the previous menu.
5.1.2 Navigation Buttons
Use the navigation buttons to move the cursor up, down or across menus. For example, when setting the
“Time” press or to move the cursor over the number to be changed, and press or to change
the number. These buttons can also be used to change the display screen for multi measurement displays.
5.1.3 OK Button
Press to accept a value or to select a sub menu.
5.2 Measurement creen
creenshot 1 creenshot 2 creenshot 3
The screen shots above show the 8200w² monitor main display in various conditions.
creenshot 1 illustrates two sensors installed and no alarms asserted.
creenshot 2 illustrates sensor 1 has detected the sludge blanket and alarmed. The associated alarm 1
relay will also activate in this example.
creenshot 3 illustrates sensor 1 with a fault. The associated alarm 1 relay will activate as normal, but in
addition the alarm 3 fault relay will activate
5.3 ystem Configuration.
From the Measurement isplay press to enter the “MAIN MENU”. From this menu, all
configurations and parameters are defined.
Setting up the monitor is a simple and intuitive process. The menu structure has been designed to lead
the operator through the configuration process. Simply start with the menu at the top and work down
through the menus.
Menu options are:
Monitor Config.
ensor Config.
Alarm Config.
Information
Lock Config.
Page 16 of 34 229844IM Issue 01 Issue ate 24/06/2019

8200w² Monitor Instruction Manual
Press or to highlight the menu required, and press to select.
Press at any time to return back to the previous menu.
Note: If no key is pressed for 2 minutes, the monitor will default back to the measurement display
screen.
5.4 Default Configuration
When the Monitor is powered up for the first time, the display will show ‘NO SENSORS’. This indicates
no sensors have been configured. Each sensor must be configured before a value is displayed.
229844IM Issue 01 Issue ate 24/06/2019 ` Page 17 of 34

8200w² Monitor Instruction Manual
6 Operational Menus
6.1 Monitor Config Menu
The MONITOR CONFIG menu is used to set up the core monitor
functions, including backlight, bleeper function, time and date. This menu
option also provides access to some advanced configuration and reset
functions.
From the MAIN MENU, ensure MONITOR CONFIG is highlighted (if not,
press or to highlight the option) then press . The six options of
Bleeper, Backlight, Contrast, Language, ate & Time, and Service Mode
are now available.
6.1.1 Bleeper
From the MONITOR CONFIG menu
press or to highlight BLEEPER,
and press to select.
The bleeper (button pressed
acknowledgement bleep) can be turned
on or off as desired. Under normal
circumstances it is preferable to leave the
bleeper turned on as it provides an
audible feedback of key presses and a triple bleep is confirmation that a function has been
successfully changed or selected.
Press or to highlight the option required, and press to select. A tick will appear next to your
selection.
Press to exit this option.
6.1.2 Backlight
From the MONITOR CONFIG menu press or to highlight BACKLIGHT, and press to select.
The backlight can be set to always ON,
always OFF or ON after key press
(backlight will switch off again after a
period of inactivity). There is a marginal
power saving by having the backlight
switched off, otherwise this setting is
down to user preference.
Press or to highlight the option
required, and press to select. A tick
will appear next to your selection.
Press to exit this option.
6.1.3 Contrast
From the MONITOR CONFIG menu
press or to highlight CONTRAST,
and press to select.
The factory setting of 50% should be
sufficient for most ambient light
conditions. For different conditions the
contrast can be altered.
Press or to increase or decrease
the Contrast by 5% (the screen contrast will react with each press of the buttons).
Page 18 of 34 229844IM Issue 01 Issue ate 24/06/2019

8200w² Monitor Instruction Manual
Press to exit this option.
6.1.4 Language
From the MONITOR CONFIG menu
press or to highlight LANGUAGE,
and press to select.
The factory default setting is English.
Press or to highlight the option
required, and press to select. A tick
will appear next to your selection.
Press to exit this option.
6.1.5 et Time/Date
From the MONITOR CONFIG menu
press or to highlight SET
TIME/ ATE, and press to select.
Press or to move the cursor
below the digit to be changed.
Press or to increase or decrease
the digit.
Press to accept.
Daylight avings: The monitor does not automatically update the time to take into account “ aylight
Savings”.
Press to exit this option.
6.1.6 Enable ervice Mode
Service mode allows the user access to
diagnostic information and detailed set-
up parameters. This will normally be
used under the guidance of a Partech
engineer, see section 7.
229844IM Issue 01 Issue ate 24/06/2019 ` Page 19 of 34

8200w² Monitor Instruction Manual
6.2 ensor Config
The monitor leaves the factory with no sensors pre-installed. Before attempting to configure a
measurement, the sensor must be installed. At this stage it is worth reviewing the contents of the
sensor manual(s) to ensure each sensor has been mechanically and electrically installed correctly.
NOTE: Once the Sensors have been wired, unplug each 4-way connector from the 8200w² Monitor or
Expansion Box before powering up the unit. The system must recognise each sensor in turn through
the ModTechw² Protocol in the “Add Sensor Config Menu”.
For further information on the configuration and operation of our sensors
please refer to their relevant manuals supplied with the sensor, please
read both manuals to ensure correct set up and operation. To access the
ensor Config Menu:
From the MAIN MENU screen, select SENSOR CONFIG by pressing
or to highlight, and press to select.
The SENSOR CONFIG menu should be
displayed. The screen shot on the right,
shows that no sensors have been
installed. The screen shot on the far
right shows both sensors installed.
6.2.1 ensor tatus
From the SENSOR CONFIG menu
press or to highlight, and press
to select. This menu will display a
which of the sensors are installed and
will include the serial number for
reference. Up to 2 sensors can be
configured to a single monitor. If only
one sensor is installed, the remaining
sensor allocation will display ‘NOT
INSTALLE ’. The first screen shot on
the right shows the SENSOR STATUS
menu with no sensors installed. The far right with both installed.
6.2.2 Add ensor
After power up, plug in the sensor(s).
From the MAIN MENU screen, select
SENSOR CONFIG by pressing or
to highlight, and press .
The SENSOR CONFIG menu should be
displayed. Press to highlight the
appropriate NO SENSOR INSTALLE
channel and press .
The :0x Add option will now be
highlighted. Press and the ‘Are you
sure’ page will be displayed. Press
again and the monitor will now search
for the plugged in sensor.
Once the search is complete, the Monitor will display the sensor found.
Repeat the addition process to install a second sensor. Sensor addition is now complete.
Press to exit this option.
Page 20 of 34 229844IM Issue 01 Issue ate 24/06/2019
Table of contents
Other ParTech Security Sensor manuals
Popular Security Sensor manuals by other brands

RIDGID
RIDGID NaviTrack Scout operating instructions

Scott
Scott Alpride System quick start guide

AMP Lighting
AMP Lighting VAC-MOTION1-4-BBZ Installation & maintenance guide

Franke
Franke FAID0003 Installation and operating instructions

SICK
SICK Prime KTX-WP92141242ZZZZ manual

Industrial Scientific
Industrial Scientific MX6 iBrid Operation guide