PCI MTSE User manual

Multi-Trans Smart Ecosystem
Paragon Controls Incorporated 1 Revision Level 000
OVERVIEW
The Multi-Trans Smart Ecosystem (MTSE) is factory configured so it will
be ready to read airflow and pressure measurements after following this
quick start guide. This guide is intended for field startup of the MTSE only.
The full MTSE Installation, Operation, and Maintenance Manual (IO&M)
can be downloaded from PCI’s website at www.paragoncontrols.com.
INSTALLATION CONSIDERATIONS
Power Requirements 20 - 28VAC/VDC
Power Consumption 8.5Watts, 15.3VA Max
Analog Outputs (4) 16-bit Analog Outputs
Field Selectable 0-10V & 4-20mA
Analog Inputs (4) 12-bit Analog Inputs
Field Selectable 0-5V, 0-10V, & 4-20mA
Supported Protocols Modbus RTU Slave, BACnet MS/TP
Max communication length 4000 ft. (EIA-485)
Operating Temperature -20°F to 158°F (-29°C to 70°C)
Do not exceed ratings. Only qualified personnel should perform
installation. Connection code is located on inside cover.
The MTSE can be custom configured to match most applications to measure, sum, and report up to 5 sensing
points in 3 systems (i.e., Supply Air, Return Air, and Outside Air) and 4 additional ΔP points of measurement
(i.e., pre-filter, final filter, coils, etc.) for a total of up to 9 sensing points. Depending on how your MTSE was
ordered, the system quantity and ΔP quantity will change the appearance of the Main Screen. Shown in the
above image is a three-system configuration with no ΔP points of measurement.
INSTALLATION
Before any electrical connections are made, ensure the POWER SWITCH is in the OFF position. The MTSE
is rated for either indoor or outdoor installation. When installed outdoors, do not install the MTSE where the
screen is in direct sunlight. Avoid locations that are subject to high vibration.
Step 1. Open the cover by unlatching the stainless-steel clasps.
Step 2. Ensure the Power Switch is in the OFF position.
Step 3. Install the interface wiring for the electrical connectors as described below. The electrical
connectors have removable terminal blocks for ease of installing the interface wiring. Shielded
24 AWG (min.) twisted-wire cable is recommended for all connections between the MTSE,
temperature transmitter, and network communication. The electrical connection code and
example of electrical connections are shown below.
- For network communication, connect Pins 31 and 32 (J4) to the positive and negative
connectors on the communication device. Ensure that only one side of the shielding wire is
connected to EARTH ground at the building network communication device.
- If a loop powered 4-20mA temperature transmitter (TT) is to be installed for OA, determine
which system is OA from the inside label. For System 1 - connect Pins 71 and 81 (J7 and
J8) on the MTSE to the positive and negative connectors on the TT, respectively; for System
2 – connect Pins 71 and 83; or for System 3 – connect Pins 71 and 85. The TT must be
connected to the correct pins for temperature compensation of corresponding system.
QUICK START GUIDE
PLEASE READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY
WITH THESE INSTRUCTIONS COULD CAUSE DAMAGE TO THE DEVICE!

Multi-Trans Smart Ecosystem Quick Start Guide
Paragon Controls Incorporated 2 Revision Level 000
- Connect Pins 91 and 92 (J9) for System 1 analog process output to the positive and negative
connectors on an analog receiving device; connect Pins 93 and 94 for System 2; and connect
Pins 95 and 96 for System 3 (if available).
- Connect Pins 1 and 2 (J1) to a 24 VAC or 24 VDC power supply. Ensure that Pin 3 is used
to connect the MTSE to EARTH ground.
Step 4. Connect the total (high) pressure and static (low) pressure ports of the MTSE to the high- and
low-pressure ports of the Airflow Measuring Station (or fans if multiple systems) using plenum-
rated tubing (by others). Transducers in the MTSE are numbered sequentially; therefore, all
connections for System 1 must be made in order starting at sensor 1, and then System 2 will
start immediately after the last sensor in System 1, and so on. See label inside cover of MTSE
for sensor numbering relative to system tagging. An example of this label is shown below.
Step 5. Turn the Power Switch (S1) to the ON position.
Step 6. Close the cover.
Electrical Connection Code Example Inside Label
Electrical Connections
(LEFT
SIDE)
W.O. No.:
SERIAL No.:
12345
6789
(RIGHT
SIDE)
LO
-
HI
POWER: 20-28 VAC/DC
HI
-
LO
●
1
●
SYSTEM #1 AHU-1 SA
●
6
●
Sensor(s) 1 to 2
●
2
●
SYSTEM #2 AHU-1 RA
●
7
●
Sensor(s) 3 to 4
●
3
●
SYSTEM #3 AHU-1 OA
●
8
●
Sensor(s) 5
●
4
●
ΔP1 Sensor 6
●
9
●
ΔP2
Sensor 7
●
5
●
ΔP3
Sensor 8
ΔP4
Sensor 9

Multi-Trans Smart Ecosystem Quick Start Guide
Paragon Controls Incorporated 3 Revision Level 000
STARTUP
Upon power up, the Main Screen will show how the
MTSE was configured for the application. If one
system was ordered, only System 1 will be visible on
the Main Screen, and if two systems were ordered
then System 1 and System 2 will show on the screen,
etc. If ΔP points of measurement were ordered, they
will appear at the bottom half of the screen as shown
to the right in a fully loaded MTSE with 3 systems and
4 ΔP points of measurement.
MENU CHANGES
If any values need to be changed, the user can
navigate through the Setup Menu to the appropriate
screen to make changes by pressing the Setup button
on the bottom of the Main Screen. On occasion, system effects will require the MTSE airflow measurement to
be corrected with a K-factor to match a balancer or reference airflow rate. See the flow chart of the Setup
Menus on page 4 for easy navigation through the Setup Menu or the MTSE Installation, Operation &
Maintenance Manual for more information.
PROPER INSTALLATION CHECK PROCEDURE
Upon power up, a form of the Main Screen as discussed in the Startup Section above will appear. A check for
proper installation can be made by navigating to the Sensor Data page from the Main Screen by pressing
DIAGNOSTICS » SENSOR DATA to confirm individual sensor flow and pressure and then checking the
following:
1) A negative pressure reading indicates reversed tubing to a sensor (other than a very small negative
pressure value from possible zero drift); swap the low and high signal tubing for that sensor number.
2) S_Err in the Pressure column indicates a “sensor acknowledge error” from an unresponsive sensor.
Cycle power and contact the Factory if this is not resolved.
3) If flow and pressure are being displayed on Sensor Data page but there is no system flow displayed on
Main Screen, the MTSE is in lockdown for that system; reduce the lockdown percent (SETUP MENU »
7.ALARMS).
4) If a single fan in a system array is reading near zero or very different from other fans in the same system,
this could indicate either fan failure,
closed fan backdraft damper, or a problem with the pneumatics (e.g.,
kinked or blocked signal tubing, etc.), please check for these issues.
The MTSE is user friendly with many help screens
available in the menus. The “?” button available at the
bottom right corner on most pages will provide an
explanation of the parameter configurations and
available options for each menu selection. The “?”
button on the Main Screen shows Factory contact
information and firmware revision levels; pressing the
right arrow will bring up a series of troubleshooting
steps the user should perform before contacting the
Factory. Continue pressing the right arrow for
additional troubleshooting steps, such as, no flow or
incorrect flow readings, analog output, and
communication issues. Consult Factory for additional
information, technical questions, or repair. Do not
disassemble or repair unit unless directed by Factory.
8
9
0.097
1.214
0.392
0.242
Pre Filter
Final Filter
Cool Coil
Heat Coil

Multi-Trans Smart Ecosystem Quick Start Guide
Paragon Controls Incorporated 4 Revision Level 000
SETUP MENUS