PENKO FLEX2100 User manual

FLEX 2100
1
PENKO Engineering B.V.
Your Partner for Fully Engineered Factory Solutions
Manual:
FLEX2100

FLEX 2100
2
IMPORTANT SAFETY INFORMATION
READ THIS PAGE FIRST!
PENKO Engineering B.V. manufactures and
tests its products to meet all applicable
national and international standards. It is vital
that this instrument is correctly installed, used,
and maintained to ensure it continues to
operate to its optimum specification.
The following instructions must be adhered to
and incorporated into your safety program
when installing, using, and maintaining PENKO
products. Failure to follow the recommended
instructions can affect the system’s safety and
may increase the risk of serious personal injury,
property damage, and damage to this
instrument and may invalidate the product’s
warranty.
• Read the instructions fully prior to installing,
operating, or servicing the product. If this
Instruction Manual is not the correct manual
for the PENKO product you are using, call
0031(0)318-525630 for a replacement copy.
Keep this Instruction Manual in a safe place for
future reference.
• If you do not fully understand these
instructions, contact your PENKO
representative for clarification.
• Pay careful attention to all warnings,
cautions, and instructions marked on and
supplied with the product.
• Inform and educate your personnel about
the correct installation, operation, and
maintenance procedures for this product.
• Install your equipment as specified in the
installation instructions of the appropriate
Instruction Manual and as per applicable local
and national codes. Connect all products to
the proper electrical sources.
• To ensure correct performance, use qualified
personnel to install, operate, update, program,
and maintain the product.
• When replacement parts are required,
ensure that qualified technicians use
replacement parts specified by PENKO.
Unauthorized components and procedures can
affect the product's performance and may
affect the continued safe operation of your
processes. The use of non-specified ‘look-alike’
substitution parts may result in the risk of fire,
electrical hazards, or improper operation.
• Ensure that all equipment doors are closed
and protective covers are in place, except
when maintenance is being performed by
qualified persons, to prevent electrical shock
and personal injury.

FLEX 2100
3
WARNING
ELECTRICAL SHOCK HAZARD
Installing cable connections and servicing this instrument require access to shock hazard level voltages
which can cause death or serious injury.
Disconnect separate or external power sources to relay contacts before commencing any maintenance.
The electrical installation must be carried out in accordance with CE directions and/or any other
applicable national or local codes.
Unused cable conduit entries must be securely sealed by non-flammable blanking plates or blind
grommets to ensure complete enclosure integrity in compliance with personal safety and environmental
protection requirements.
To ensure safety and correct performance this instrument must be connected to a properly grounded,
three-wire power source.
Proper relay use and configuration is the responsibility of the user.
Do not operate this instrument without the front cover being secured. Refer any installation, operation
or servicing issues to qualified personnel.
WWW.PENKO.COM
PENKO Engineering B.V.is an ETC Company
Email: info@PENKO.com

FLEX 2100
4
COM
1 2out2out1 C
1 2
COMMON FOR OUTPUTS
-0Vacor 0Vdc
-24Vacor 24Vdc
Common max.35V \0,5A
34Out4Out3 3 4
COM
5 6out6out5 C
5 6
7 8Out8Out7 7 8
Digital inputs 1-8
Digital outputs 1-8
-
+
18-28 VDC
+
-
WIRING CONNECTIONS:
LOADCELL(S), IN/OUTPUTS & POWER SUPPLY
Input 1 can be used as:
or
as
(max.counter input speed 5000Hz)
a normal input
a counter input
- SIGNAL
SHIELD
- EXCITATION
- SENSE
+EXCITATION
+ SENSE
+SIGNAL
1 2 3 4 C 5 6 7 8
Analog output mA (option)
Ground
for output
and supply
+Current
16 BitAnalog output
A
D
+Supply
FLEX 2100Indicator/Controller:
Power supply
for analog output
18-30Vdc
LB
LF1S028
0317M
DC POWER SUPPLY VERSION
This productis intended to be supplied
by a Class2 or Limited PowerSource,
rated 10.8 - 31.2 Vdc,0.65A@24Vdc.
- SIGNAL
SHIELD
- EXCITATION
- SENSE
+EXCITATION
+ SENSE
+SIGNAL
Wiring connections01

FLEX 2100
5
WIRING CONNECTIONS:
COM. PORT RS232/422
com1/4
com1/4
Wiring connections 02
+ - + -
RX. TX
PLC/PC
Note: use twisted pair
data cables PV protocoll
Rs422 PVprotocol Example
example:
com1/2
com3/4
COMMUNICATION RS422.
COMMUNICATION RS232.
CABLE FOR COMPORT
RS232 PRINTER CABLEFOR COMPORT
RS232 PC/PV-PROTOCOL
OR
LB
CE only; 100-240 Vac POWER SUPPLY VERSION

FLEX 2100
6
PROFIBUS PORT CONNECTIONS
RxD/Tx D-P
Profibus
cable.
WIRING CONNECTIONS:
PROFIBUS & ETHERNET
Wiring connections 03
earth
B A
LB
LF1S028
0317M
RJ-45 Ethernetconnector
led functions:
Green=Link
Yellow=Active
1 = td+
2 = td-
3 = rd+
4 = not used
5 = not used
6 = rd-
7 = not used
8 = not used
SHIELD
RxD/Tx D-N
Place jumper
for profibus
termination
CE only;
100-240 Vac POWER SUPPLY VERSION
Main board revision F
or higher has a double
dip switch for Profibus
termination

FLEX 2100
7
DIMENSIONS FLEX 2100 PANEL MOUNT
Side view
Top view
Dimensions 01
5,0 mm
190,5mm
150,0mm
4,0mm
48,00 mm
16,0 mm
170,5mm
260,0 mm
220,0 mm
240,0 mm

FLEX 2100
8
DIMENSIONS FLEX 2100 STAINLESS STEEL
Side view
Top view
Dimensions 02
240,0 mm
276,5 mm
180,0 mm
Use appropriate bracket mounting screws with a total minimum strength of 6,8kg

FLEX 2100
9
Button explanation 01
The Penko Flex hasdifferentfunction keys.
Button explanation:
Menu buttons:
Buttons to entera menu are recognizable by other pictogram with text.
Examples:
Edit buttons:
Buttons to edita parameter can be a -,+ oreditbutton.
With the “-” button the parameter field will scroll down or decrementofthe value.
With the “+”button the parameter field will scroll up .
With the editbutton a keyboard will be opened to edit the selected parameter.
or incrementof the value
Alphanumeric keyboard: Numeric keyboard:
Leave menu buttons:
With the “cancel”button its possible to leave a menu withoutsaving the changed
parameters.
With the “OK” button its possible to leave a menu and save the changed parameters.
With the “Next>>” button its possible to go to the nextscreen with parameters ofthe
selected menu.
With the “<<Prev”button its possible to go to the previousscreen with parameters ofthe
selected menu.
ON/OFF buttons.
Some function can be enabled ordisabled,the buttons are recognizable by the red cross
or green tickmark.
OFF/Disabled ON/Enabled

FLEX 2100
10
Recipe Menu:
From this menu its possible to selectand editrecipes.
To go to this menu,select“Recipe”fromthe Main menu.
Recipe menu 01
Select1 of the 4 tasks
Recipe Number:
Here you can select the numberofthe recipe.
Name:
Here the name ofthe selected recipe will be shown.
Edit:
Here the selected recipe parameterscan be changed.

FLEX 2100
11
System setup:
From this menu its possible to access all settings for the flex.
To go to this menu,select“System setup” from the Main menu.
System setup 01
Differentoptions are:
- Port Setup
- Indicator Setup
- In/Outputs
- Passwords
- Screen Setup
- Set Clock
- Process setup
- Labels and links
- Printer
- System Recall

FLEX 2100
12
Portsetup 01
Protocol:
In this field,several communication protocolscan be selected.
Different protocols are: None, Printer, ASCII, TP Slave, TP Master, NPV Slave, NPV
Master, INDICATOR, HLViewteq, HLPLC,Modbus RTU,Modbus ASCII,Keyboard
Custom.
Address:
To identify the device in a configuration with multiple devices an address has to be
selected. (Notfor all protocols)
Baudrate:
Selecta speed for the protocol(Notforall protocols)
Parity:
Selecta parity for the protocol
(Notfor all protocols)
Port setup:
In the portsetup it’s possible to setup all communication ports and protocols.
To go to the portsetup press the “PortSetup” button fromthe System setup.
RS 232 port:
In this menu all settingsfor the RS 232 comportcan be set.
For settings,see below.
RS 422 port:
In this menu all settingsfor the RS 422 comportcan be set.
For settings,see below.
Stopbits:
Selectthe number ofneeded stopbits for the protocol
(Notfor all protocols)

FLEX 2100
13
Portsetup 02
Protocol:
In this field,several communication protocolscan be selected.
Differentprotocols are:None or Buslink
Buslink Address:
Up to 8 Flexes can communicate with each other,sharing inputs,outputs,markersand
indicators.
In this parameter its possible to setthe Buslink Address.
Baudrate:
Selecta speed for the protocol
CAN 1 port:
In this menu,all settings for the CAN comportcan be set.
USB port:
In this menu all settingsfor the USB comportcan be set.
Protocol:
When the USB portis switched to device mode the Flex acts asan external serial port.
The USB device supports the following protocols:
- None
- Printer
- ASCII
- TP Slave
- USB Host
- Mouse/Keyboard
The firsttime the flex is connected to the PC,windows will ask for a driver.Then selectthe
file Flexusb.infto startthe installation.Thisfile is installed as partof th PIpackage.
USB Host
When the USB portis switched to hostmode,a USB stick formatted with FAT16 orFAT
filesystem can be used to load and store data on the stick.
When no printer portis selected,printcommands will be stored as a textfile on the usb
stick with the name PRINTER.TXT.
Reading and writing registers,indicators and recipes to the USBstickcan be done using
the PLC program commands FILEREAD and FILEWRITE.
Buslink Subaddress:
When using a subaddress,up to 40 flexes can communicate with eachother.
In this parameter its possible to setthe Buslink subaddress.

FLEX 2100
14
Profibus setup:
In this menu all settings for the Profibus comportcan be set.
Portsetup 03
Channel:
To identify the device in the used configuration, a Channel has to be selected.
Format:
The profibus value can be shown as Integer(directvalue withoutdecimal point) oras
Floating point(real value with decimal point).
USB buslink active:
Tells if the USB buslink is active or the status ofthe USB Host.
The USB Portsettings screen can show the following messages:
- USB device portis connected
- USB is disconnected
- USB stick is connected and ready
- USB stick is connected but busy
- too much current draw from USB port
- device connected to the USB hostportis notrecognised.
Currently only FAT or FAT16 formatted USB sticks are supporte d.
- Flex attempted to open a file that is not on the USBstick
- Currently only FAT or FAT16 formatted USB sticks aresupported.
Reformat the stick wit FAT filesystem
- File acces failed
- When the Flex switchesfrom device to host,a connected PC mustbe
disconnected first.
YES
NO
Ready
Busy
USB overcurrent
USB device unknown
File not found
Invalid FAT Format
File error
Disconnect USB
2

FLEX 2100
15
Portsetup 04
Ethernet setup:
In this menu all settingsfor the Ethernetcomportcan be set.
IP Number:
Editthe ethernetIP number.
Subnet Mask:
Editthe ethernetSubnetmask
Gateway:
Editthe ethernetGateway.
Speed:
The speed ofthe ethernetcommunication can be setat:10 Mbps,100Mbpsor automatic
detection.
Name:
In the “name” its possible to give the Flex a unique name within the ethernet
communication.
DCHP:
With the DHCP its possible to letthe networkgenerate an IP address for the Flex.
When its disabled the flexwill work with a fixed IP address.
When its enabled the flexwill request an IP address from the network.
Port:
In the Port” the portnumber for the communication can be set.
Buslink Address:
Up to 8 Flexes can communicate with each other,sharing inputs,outputs,markersand
indicators.
With this parameter its possible to setthe Buslink Address.
Buslink subaddr:
When using a subaddress,up to 40 flexes can communicate with eachother.
With this parameter its possible to setthe Buslink subaddress.

FLEX 2100
16
Portsetup 04
Ethernet setup:
In this menu all settingsfor the Ethernetcomportcan be set.
IP Number:
Editthe ethernetIP number.
Subnet Mask:
Editthe ethernetSubnetmask
Gateway:
Editthe ethernetGateway.
Speed:
The speed ofthe ethernetcommunication can be setat:10 Mbps,100Mbpsor automatic
detection.
Name:
In the “name” its possible to give the Flex a unique name within the ethernet
communication.
DCHP:
With the DHCP its possible to letthe networkgenerate an IP address for the Flex.
When its disabled the flexwill work with a fixed IP address.
When its enabled the flexwill request an IP address from the network.
Port:
In the Port” the portnumber for the communication can be set.
Buslink Address:
Up to 8 Flexes can communicate with each other,sharing inputs,outputs,markersand
indicators.
With this parameter its possible to setthe Buslink Address.
Buslink subaddr:
When using a subaddress,up to 40 flexes can communicate with eachother.
With this parameter its possible to setthe Buslink subaddress.

FLEX 2100
17
Indicator setup 01
Indicator setup
In the indicator setup it’s possible to setall indicator parametersto make sure the indicator
will actproperly.
To reach this Setup see below
The differentoptions are:
- Indicator
- Filter
- Calibration
- Indicators
- Recall
- External Devices
Unit label:
The unit label can have a maximum of 4 characters.
The unit label defines the unitof measurement.
The unit label is the value ofa quantity,chosen byconvention as a reference for
measuring quantities ofthe same kind.
For example:
,- t(ton) kg (kilo gram),g (gram),butcan also be L(liter),lbs (pounds),etc.
Indicator name:
The indicator name can have a maximumof 16 characters.
With an indicator name,the indicator will be unique within the application.
So it's easy to recognize itin the processand/or in the factory.
For example:
Silo 1,Scale,etc.
To change the indicator name,press the “EDIT” button behind the name and change it.
Indicator:
To change the different settings, select “indicator” from the indicator setup
Before its possible to enter this menu,the indicator will askfor the “TAC”code.This“TAC”
code is shown in the upper rightcorner.

FLEX 2100
18
Indicator setup 02
Step size:
Step size can be setat 1,2, 5,10,20,50,100,200.
The step size defines the scaled parts ofthe weight value.
Example:Weigher value is 2003 kg
Step size Display value
1 2003 kg
2 2004 kg
5 2005 kg
10 2000 kg
The display value will be rounded offto the nearestvalue with a valid step size.
Decimal point:
Decimal pointposition can be setfrom NONE to 0,00000.
The Decimal pointdefinesthe pointposition ofthe weightvalue.
Example:value 2006 kg with a decimal pointposition of“2” will be shown as 20.06 kg
Formatting:
Formatting defines the way thatthe weigher value will be shown.
To change the formats ofthe indicator,press the “Formatting” button.
MultiRange/Interval:
In the multirange/intervall the indicator can be setto change its
stepsize when the weigher signal reachesa certain value.
Range:
Step:
Thisisthenumberofdivisionswhentheindicatorhastodisplayusingthenextstepsize.
Auto ranging is disabled when range size is set to 0.
Thebiggestalowedstepsizemustbesetinthestepfield.

FLEX 2100
19
Indicator setup 03
Operation Mode:
This parameter defines the operation mode ofthe unit.
The operation mode can be setat“Industrial” or Certified mode.
In industrial mode its alwayspossible to change the indicator parametersand calibration
settings.
In certified Mode the unitwill be sealed by marks and also the weighing parameters will be
blocked to comply with calibration laws.
If certified mode isselected,the zero band = 4% (+2 and -2%)
Also zero suppressing isdisabled.
A weighing unitmust be certified when its used for
Note:
measuring fortrade aims.
Example:Thenormalstepsizeisper1, Range=100andStep=50.
0-100 1
100-200 2
200-500 5
500-1000 10
1000-2000 20
2000-5000+ 50
Themaximumpresettareonlyworks,andthisisalsothebiggestvalue,tothefirstlevelofthe
autorangewhentheindicatorissettocertified.Inthisexamplethepresettareisvalidto100.
Indicatordisplay Stepsizeper
Mode:
The multi interval function has 2 modes,“Multi range”en “Multi interval”.
With “Multi range”the highestshown stepsize will be resetafter the signal has been lower
or equal to “0”.
With “Multi interval”the highestshown stepsize will be lowered when the signal reaches a
lower range.

FLEX 2100
20
Indicator setup 04
Zero tracking:
Zero tracking isable to tune the zero pointbackto zero when the scale becomes dirty.
The zero tracking can be setwith 3 parameters:
,the time thatthe signal has to be within the range to tune 1 step back to zero.
,the maximum offsetto tune back to zero.
,the step size thatwill be tuned every when the offsetis whithin the
Maximum .
-Time
-Range
-Step time
range
Max load:
To prevent overload by the user,the FLEX will notshow any weightabove this value.
In certified mode the max load is not allowed to be more then the maximum load
+ 9 scale parts.
Stable condition:
The Flex will give a signal when the weigher value is stable within certain values.
The stable function can be setwith 2 parameters:
(milliseconds).
(in the selected weigher unit)
The indicator will give the stable signal when it’s within the for the set
- Time
- Range
range time