Pentair Pool Products 48ES Series User manual

48ES and 51ES NXT Stager Controller
Service Manual
43037 Rev B FE11
TABLE OF CONTENTS
NXT STAGER DIMENSIONS .................................................2
SYSTEM SPECIFICATIONS 48ES AND 51ES SERIES........2
SYSTEM DEFINITIONS.........................................................3
SYSTEM OPERATION IN SERVICE
(SYSTEM 14-DEMAND).........................................................4
TIMER DISPLAY FEATURES.................................................5
NETWORK/COMMUNICATION CABLES &
CONNECTIONS.....................................................................5
TIMER OPERATION ..............................................................6
MASTER PROGRAMMING MODE FLOW CHART...............7
USER PROGRAMMING MODE FLOW CHART....................9
DIAGNOSTIC PROGRAMMING MODE FLOW CHART........9
PLUMBING DIAGRAMS.........................................................12
SOLENOID USE.....................................................................13
STAGER CONTROLLER, 48ES, NEMA 4
24V/50-60Hz ASSEMBLY.......................................................14
STAGER CONTROLLER, 51ES, NEMA 4
24V/50-60Hz ASSEMBLY.......................................................15
WIRING DIAGRAM 48/51ES STAGER CONTROLLER ........16
TROUBLESHOOTING ...........................................................17
SERVICE ASSEMBLIES ........................................................18
IMPORTANT PLEASE READ:
• Theinformation,specicationsandillustrationsinthis
manualarebasedonthelatestinformationavailable
atthetimeofprinting.Themanufacturerreservesthe
righttomakechangesatanytimewithoutnotice.
• Thismanualisintendedasaguideforserviceofthe
controlleronly.Systeminstallationrequiresinformation
fromanumberofsuppliersnotknownatthetimeof
controlmanufacture.Thisproductshouldbeinstalled
byaplumbingprofessional.
• Thisproductmustbeinstalledincompliancewithall
stateandmunicipalplumbingandelectricalcodes.
Permitsmayberequiredatthetimeofinstallation.
• Ifdaytimeoperatingpressureexceeds80psi,
nighttimepressuresmayexceedpressurelimits.A
pressurereducingvalvemustbeinstalledifpressure
exceeds125psi.
• Donotinstalltheunitwheretemperaturesmaydrop
below32°F(0°C)orabove110°F(43°C).
• Donotplacetheunitindirectsunlight.Blackunitswill
absorbradiantheatincreasinginternaltemperatures.
• Donotstrikethecontrolleroranyofthecomponents.
• Warrantyofthisproductextendstomanufacturing
defects.Misapplicationofthisproductmayresult
infailuretoproperlyconditionwater,ordamageto
product.
• Apreltershouldbeusedoninstallationsinwhichfree
solidsarepresent.
• Correctandconstantvoltagemustbesuppliedtothe
controllertomaintainproperfunction.

SYSTEM SPECIFICATIONS 48ES AND
51ES SERIES
Generic Meter Guidelines
• Opencollectoroutput
• Pulserategeneratedmustnotexceed100pulsesper
second(100Hz),or6,000pulsesperminute
• Supportformeteroutputsintherangeof1-255gallons
(25.5 m3)forevery1-255pulses
Example:35gallons/100pulses
(=3.5gallons/10pulses,=0.35gallons/1pulse)
• Metermustoperateat5VDC
Electrical Rating
• 24 VAC Transformers
115VAC±20%input,24VACoutputw/40VA(maintain
inputvoltageinthisrange)
230VAC±20%input,24VACoutputw/108VA(maintain
inputvoltageinthisrange)
Humidity
• 95%RH,non-condensing
Temperature
• Maximumcontroluidtemperature140°F(60°C)
• Operatewhereambienttemperaturesareabove32°F
andbelow110°F
Pressure
• Maximumcontroluidpressure125psi(8.5bar)
• Controluidcanbeeitherwaterorairandmustbeequal
toorgreaterthansystempressure.
NXT STAGER DIMENSIONS
(6X) 1/8" NPT PORT 60 APART
48ES STAGER
(4X) HOLE "A"
48ES
HOLE "B"
48ES
51ES STAGER
(8X) 1/8" NPT - 45 APART
(4X) HOLE "A"
51ES
HOLE "B"
51ES
11.13 [282.7]
10.50 [266.6]
5.25 [133.4]
1.41 [35.8]
2.45 [62.2]
2.06 [52.3]
2.75 [69.9] 2.75 [69.9]
4.00 [101.6]
2.00 [50.8]
2.72 [69]
3.50 [88.9]
6.42 [163.1] 1.25 [31.7] 6.00 [152.4]
(4X) R.16 [4] (4X) .19 [4.8]
.32 [8.1]
11.13 [282.7]
1.75 [44.4]
Optional
Solenoid
8.91 [226.3]
1/8" NPT Drain
1/8" NPT Filtered Inlet
1/8" NPT Drain
1/8" NPT Filtered Inlet
1/8" NPT Drain
Figure1
2•NXTStagerControllerFE11

SYSTEM DEFINITIONS
System
Number
System
Description
# of
Tanks/
Controls
Connect meter and/or remote
regeneration input to...
Type Operation Discussion
4SingleUnit 1TimeClock:NoMeter
Immediate:OneMeter
Delayed:OneMeter
RemoteSignalStart:NoMeter
Stager
(nosolenoidrequired)
Singletankconguration.During
Regenerationnowateravailabletoservice
unlessoptionalbypassvalve#2Ainstalled.
5Interlocked 2, 3, or 4 Immediate:AllMeters
RemoteSignalStart:NoMeter
Stager
(nosolenoidrequired)
Alltanksinparallelsupplyingtreatedwater.
Eachunitinthesystemwillhaveitsown
owmeter/sensorinput.Thecontrolwill
delaythestartofRegenerationifanother
unitisalreadyinRegeneration.Oncethat
unithascompletedaRegenerationcycle,
andhasreturnedtoService,theunitwith
longestregenerationqueuetimewillbegin
Regeneration.Nomorethanoneunitwillbe
in Regeneration at a time.
6 Series
Regeneration
2, 3, or 4 Immediate:OneMeter
Delayed:OneMeter
RemoteSignalStart:NoMeter
Stager
(nosolenoidrequired)
Alltanksinparallelsupplyingtreatedwater.
Only#1controlwillmonitorowmeter/
sensorinput.Whenaregenerationis
requiredforthesystem,itwillregenerate
valveaddress#1rst,immediatelyfollowed
by#2,then#3,then#4ifinstalled.Nomore
thanoneunitwillbeinRegenerationata
time.
7 Twin
Alternating
2Immediate:OneMeter
RemoteSignalStart:NoMeter
Solenoid
(plugstagerport2)
Onetankonlinesupplyingtreatedwater,
onetankinStandby.Only#1control
willmonitoritsowmeter/sensorinput.
Regenerationofaunitwillbeginafterthe
othercontrolhasleftStandbyandreturned
toService.WhentheRegenerationcycle
iscomplete,theregeneratedunitwillenter
Standby.Standbyoneachtankiscontrolled
byasolenoidconnectedtotheservice
outletvalveofthattank.
9MultipleTank
Alternating
2, 3, or 4 Immediate:AllMeters
RemoteSignalStart:NoMeter
Solenoid
(plugstagerport2)
One,two,orthreetanksonlinesupplying
treatedwater,onetankinStandby.Meter/
sensorinputisrequiredoneachtank.
Regenerationofaunitwillbeginafterthe
othercontrolhasleftStandbyandreturned
toService.WhentheRegenerationcycle
iscomplete,theregeneratedunitwillenter
Standby.Standbyoneachtankiscontrolled
byasolenoidconnectedtotheservice
outletvalveofthattank.
14 Demand
Recall
2, 3, or 4 Immediate:AllMeters Solenoid
(plugstagerport2)
Meterinputisrequiredoneachtank.Unit
#1willbeginInServicewith#2,#3,and
#4(ifinstalled)willbegininStandby.At
leastoneunitisInServiceatalltimes.
WhenowratetothePrimaryServiceUnit
increasestoauserspeciedrate,thenext
unitinsequencewillmovefromStandbyto
Service.Astheowratefallsbelowtheuser
speciedratesubsequenttankswillreturn
toStandby.WhenthePrimaryServiceUnit
regenerates,thenextunitinsequence
willbecomethenewPrimaryServiceUnit.
Aseachunitscapacityisreachedthe
controllerwillinitiateaRegenerationofthat
unit.Dependingonthenumberofunits
inthesystem,andowratedemandthe
regeneratedunitwillthenbeplacedeither
intoStandbyorService.Onlyoneunitwill
beinRegenerationatatime.
NXTStagerControllerFE11•3

SYSTEM OPERATION IN SERVICE
(SYSTEM 14-DEMAND)
Thesystemoperatesaspartofamulti-tankregeneration
system.Thisexampleappliestoeithera2,3or4tanksystem.
Eachtankinthesystemwillhaveanactiveowmeterinput,
eveninStandby.
ThenumberoftanksInServicedependsontheowrate.
Examples of a Four-Unit System:
1. OneTankisInServiceatalltimes(the"primarytank").
In Service
(Primary Tank) Standby
12 3 4
2. Thetotalowratetotheprimarytankincreasedpastthe
rsttrippointprogrammedrate.Theowstayedpast
thetrippointdelayedtime.Thenexttank(leastvolume
remaining)changesfromStandbytoInService.Thisthen
splitsthetotalowbetweentwometers.
In Service
1 2 3 4
Standby
First Trip Point
(Primary Valve)
Total Flow Split
Between Two Meters
3. Theowratedemanddecreasedbelowthersttrippoint.
ThetankreturnstoStandby.
Standby
Flow Rate Demand
Below First Trip Point
(Primary Valve)
1 2 3 4
4. Totalowratedemandincreasedpastasecondtrippoint
programmedrate.Thesecondandthirdtank(leastvolume
remaining)changesfromStandbytoInService.Thetotal
owissplitbetweenthethreemeters.
Standby
Flow Split Between
Three Meters
1 2 3 4
5. ThethirdtankreturnstoStandbyasdemanddecreases
pastthesecondtrippoint.
Standby
Flow Split Between
Two Meters
1 2 3 4
6. TanksreturntoStandbyduetodecreasedtotalowrate
andtrippointsprogrammed.Thetankwiththemost
remainingvolumewillbethersttogointoStandby.
Full Capacity
4th in Standby
(Primary Valve)
3/4 Capacity
3rd in Standby
1 2 3 4
1/2 Capacity
2nd in Standby
1/4 Capacity
1st in Standby
7. Theprimarytankregenerates.Thenexttankwiththeleast
remainingvolumebecomesthenewprimarytank.Thetank
withthenextleastvolumeremainingwillbethersttrip
pointprogrammedrate.Tankscontinueoperatinginthis
order.
Full Capacity
4th in Standby
3/4 Capacity
3rd in Standby
1 2 3 4
1/2 Capacity
First Trip Point
Programmed Rate
1/4 Capacity
New Primary Tank
System Operation in Regeneration:
IftwotanksareInServiceandbothreach
VolumeRemaining=0,theothertwotankswillshiftfrom
StandbytoInService.Theleadtankwith
VolumeRemaining=0willstartRegeneration.Thesecond
tankwithVolumeRemaining=0willenterStandby.Ifow
increasespastthetrippointathirdtankneedstoenterIn
Service.ThetankinStandbywithVolumeRemaining=0will
shiftintoInServicetomaintainasteadyow.Operatingfor
extendedperiodsinthismodemaydegradethewaterquality.
4•NXTStagerControllerFE11

TIMER DISPLAY FEATURES
System
Number
Valve
Address
Valve State
(SBY, SRV, INI, LCK)
Flow
Indicator
Time
of Day
Shift Button
Adjusts Values to the Left
Up Button
Adjusts Values Up
Down Button
Adjusts Values Down
Volume Remaining
Status LED
Display Screen
Time of Day alternates
with Error Screen
Example: Valve #, Volume
Remaining, Errors
Diagnostic Button
View Flow Rate, Peak Flow
Rate, Totalizer, Hours
Between Last Two
Regenerations, Hours Since
Last Regeneration, Adjustable
Volume Remaining, Valve
Position, Send & Receive
Errors, Software Version
Extra Cycle Button
Cycle Valve in
Regeneration/Cycle
Programming Steps
Figure1
Valve State
INI (Initializing) - INIwilldisplayonthescreenfor30to
45secondswheninitializingafterapowerfailureresetor
programming.
RGQ (Regeneration Queued) -RGQindicatesthatthereserve
hasbeenenteredinadelayedsystemandregenerationhas
beenqueued.Wheninthemainscreen,presstheExtraCycle
buttontotoggleservice(SRV)withRGQ.
Service (SRV) - SRVwilldisplaywhentheunitisInService.
LCK (Lock) - Lockwillbedisplayedwhencontactclosureis
appliedacrosstheinterlockterminalsonthecircuitboard.See
the“Network/CommunicationCables&Connections”sectionof
thismanual.
LED Status Lights
Blue LED - IlluminateswhiletheunitisInServiceandno
errorsexist.TheunitwillalwaysbeInServiceunlessa
regenerationtriggerhasoccurred(greenLEDlightwillbe
displayed).AblinkingbluelightindicatesthetimerisInService,
andqueuedforregeneration.
Green LED - IlluminateswhentheunitisinRegeneration
mode.AblinkinggreenlightindicatesthetimerisinStandby,
andnotinRegeneration.
Red LED- Illuminateswhenthereisanerror.
Flow Indicator
Arotatingline(appearingasarotatingstarshape)willdisplay
onthescreenwhenowisgoingthroughthemeter.
NETWORK/COMMUNICATION CABLES
& CONNECTIONS
UseaCAT5Network/Communicationcable.
Connectthenetwork/communicationcabletoeitherportbefore
programming.
Themaximumcablelengthbetweentimersis100feet.
Connectunitstogetherfromonecommunicationporttothe
nextcommunicationport.Theorderisnotimportant.
CommunicationPorts
Ground
Lock Regen
Figure2CurrentNXTCircuitBoard
NXTStagerControllerFE11•5

TIMER OPERATION
Set Time of Day
HoldtheUporDownbuttontochangetime.Whileintime
changemodepressShifttoadjustnextdigitover.Onmultiple
tanksystemschangetimeon#1controlonly.Allothercontrols
insystemwillmirrorthetimeoncontrol#1.
Manually Initiating a Regeneration
1. WhentimerisInServiceorStandBy,presstheExtraCycle
buttononthemainscreenforve(5)secondstoforcea
manualregenerationifanotherunitisnotinRegeneration.
2. ThetimerreachesRegenerationcycleStep#1.
3. PresstheExtraCyclebuttononcetoadvancevalvetothe
nextRegenerationcycle.
Timer Operation During Regeneration
IntheRegenerationcyclestepdisplay,thetimershows
thecurrentRegenerationcyclenumberthevalveisin,or
hasreached,andthetimeremaininginthatstep.Onceall
regenerationstepsarecompletethetimerreturnstoInService
andresumesnormaloperation.
Example:12minutesremaininginCycle1
PresstheExtraCyclebuttonduringa
RegenerationCycletoimmediatelyadvancethe
valvetothenextcycleandresumenormaltiming.
Flow Meter Equipped Timer
DuringnormaloperationtheTimeofDayscreenalternateswith
the Error screen (if errors are present).
Astreatedwaterisused,theVolumeRemainingdisplaycounts
downfromthecalculatedsystemcapacitytozero.Whenzero
isreachedaRegenerationcyclebeginsifnootherunitsarein
regeneration.
Timer Operation During Programming
ThetimerenterstheProgramModeinStandbyorService
Modeaslongasitisnotinregeneration.WhileintheProgram
Modethetimercontinuestooperatenormallymonitoringwater
usage.Timerprogrammingisstoredinmemorypermanently.
Timer Operation During A Power Failure
Duringapowerfailurealltimerdisplaysandprogrammingare
storedforuseuponpowerre-application.Thetimerretains
allvalues,withoutloss.Thetimerisfullyinoperativeandany
callsforregenerationaredelayed.Thetimer,uponpower
re-application,resumesnormaloperationfromthepointthatit
wasinterrupted.
NOTE: A ashing Time of Day display indicates a power
outage. Hold the Up or Down button to reset time.
Remote Lockout
Thetimerdoesnotallowtheunit/systemtogointo
Regenerationuntiltheregenerationlockoutinputsignaltothe
unitiscleared.Thisrequiresacontactclosuretoactivatethe
lockout.Therecommendedgaugewireis20withamaximum
lengthof500feet.
Regeneration Day Override Feature
IftheDayOverrideoptionisturnedonandtheactualnumber
ofdayssincelastregenerationexceedsthesetregeneration
dayoverridevalue,theRegenerationcyclestarts.Ifotherunits
areinregeneration,itisaddedtoaregenerationqueue.This
occursregardlessoftheremainingvolumeavailable.
WARNING:
This unit is not designed to drive/power
external devices. Transformer must be
grounded. Ground wire must be terminated
to the back plate where grounding label is
located.
Auxiliary Relay Output
TheAuxiliaryRelayOutputonthecircuitboardcanbe
programmedtobeclosedduringawindowoftimewithinthe
regenerationsequence.TheAuxRelayOutputStarttimesets
theturn-ontimereferencedtothestartofregeneration.The
AuxRelayOutputEndtimesetstheturn-offtimereferencedto
thestartofregeneration.TheAuxiliaryRelayOutputsharesthe
samerelayastheChemicalPumpOutput.Seewiringdiagram
for connection information.
Chemical Pump Output
WhentheChemicalPumpOutputfeatureisenabled,the
controlwillcalculatevolumeofwaterusedandclosethe
relaywhenthesetCPOAuxRelayVolumeisreached.Once
activated,therelaywillstayclosedfortheamountoftimeset
inCPOAuxRelayTime.TheChemicalPumpOutputonly
functionswhileinservice,andtheCPOvolumeisresettozero
eachregeneration.TheChemicalPumpOutputsharesthe
samerelayastheAuxiliaryRelayOutput.Seewiringdiagram
for connection information.
6•NXTStagerControllerFE11

VALVE ADDRESS:
#2
Options: Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve) (Default)
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
SYSTEM TYPE: 4
SINGLE UNIT
Options: System 4 (single unit)
System 5 (2-4 units) - Parallel Interlock
System 6 (2-4 units) - Parallel Series Regeneration
System 7 (2 units) - Alternating
System 9 (2-4 units) - Alternating
System 14 (2-4 units) - Demand Recall
Example:
System Type 4, Single Unit
Example:
Valve Address #2 (Second Control Valve) (Default)
SYSTEM SIZE:
2 VALVES
Options: 2 Valves in the System (Default)
3 Valves in the System
4 Valves in the System
Example:
2 Valves in the System (Default)
REGEN TYPE:
TIME CLK DELAYED
Options: Time Clock Delayed (System 4 Only) (Default)
Meter Immediate (All System Types)
Meter Delayed Fixed Reserve (Systems 4 & 6 Only)
Example:
Time Clock Delayed (Default)
VALVE TYPE:
STAGER-NOTCH CAM
Options: 2750
2850
2900
3150
3900
Stager - Notch Cam (Default)
Example:
Stager - Notch Cam (Default)
REMOTE SIGNAL
START:OFF
Options: 00:06:00 (Hours:Munutes:Seconds)
Range: 1 second to 99 minutes (1 hour, 39 minutes)
Example:
Off (Default)
DISPLAY FORMAT:
US-GALLONS
Options: U.S. - Gallons (Default)
EU-Metric - Liters (Metric)
Example:
U.S. Gallons (Default)
UNIT CAPACITY:
0300000 GRAINS
Options: Grains (in U.S. Format) (Default)
Grams (in Metric Format)
Example:
0300000 Grains (Default)
CAPACITY SAFETY
FACTOR: 00%
Range: 0 to 50%
Example:
00% (Default)
FEED WATER
HARDNESS: 15 GPG
Range: 1 to 199 Grains/Gallon (U.S. Format)
2 to 199 miligrams CaCOs/L (Metric Format)
Example:
15 GPG (U.S. Format) (Default)
SELECT LANGUAGE:
ENGLISH
Options: English
Espanol
Portugues
Deutsch
Francais
Example:
English
TRIP POINT 1:
000 gpm
Range: 2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
NOTE: This screen will not display for System Type 4.
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
NOTE: Use the Shift button to move to the left.
Range: 1 to 9,900,000 Grain Capacity in U.S. Format
1.0 to 190,000 grams CaCO3Capacity in Metric Format
NOTE: Use the Shift button to move to the left.
NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. Use the Shift button to change each
decimal position.
NOTE: This screen will only display for System 14.
REGENERATION DAY
OVERRIDE:OFF
Example:
Off (Default for Meter)
On (Default for Time Clock)
REGENERATION DAY
OVERRIDE:01 DAYS
Options: Off (Default for Meter) or On (Default for Time Clock)
Example:
1 Day
Range: 1 to 99 Days
REGENERATION
TIME: 02:00AM
Example:
2:00 A.M. (Default)
Options: A.M. (U.S. Format)
HR (Metric Format)
NOTE: Regeneration time will not appear unless Regeneration Day Override
is on.
CYCLE 1 00:10:00 Example: Backwash
00:10:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
AUXILIARY RELAY:
DISABLED
Example:
Auxiliary Relay is Disabled
Options: Enabled
Disabled (Default)
AUX RELAY OUTPUT
START 1 00:00:00
Example:
Auxiliary Relay Output Start 1 at
0 hours, 0 minutes, & 0 seconds
Range: 00:00:00 to 18:00:00
NOTE: Only displayed if Auxiliary Relay is enabled in previous screen.
Auxiliary Relay will only display if Chemical Pump is OFF for System
Types 6 & 7.
AUX RELAY OUTPUT
END 1 00:00:00
Example:
Auxiliary Relay Output End 1 at
0 hours, 0 minutes, & 0 seconds
Range: 00:00:00 to 18:00:00
CHEMICAL PUMP:
DISABLED
Example:
Chemical Pump is Disabled
Options: Enabled
Disabled (Default)
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
CPO AUX RELAY
TIME: 00:00:00
Example:
Each time chemical pump relay is on, run for
30 seconds (00:00:30)
Range: 00:00:00 to 02:00:00
FLOW METER:
1.0 PADDLE
Example:
1.0 Paddle Flow Meter
Options: 1.0 Paddle (Fleck)
1.0 Turbine (Fleck)
1.5 Paddle (Fleck)
1.5 Turbine (Fleck)
2.0 Paddle (Fleck)
3.0 Paddle (Fleck)
Generic
NOTE: Default flow meter type is based on the valve type. This screen will
only display on the lead unit for System Types 6 & 7. All other system types
it will display for all units.
MAXIMUM FLOW
RATE: 0000 gpm
Example:
Maximum Flow Rate of 0 gpm
Range: 20 - 2000 gpm (U.S. Format)
20 - 2000 Lpm (Metric Format)
NOTE: Only displayed if “Generic” is chosen for the flow meter.
Range: 1 - 99 Gallons (U.S. Format)
0.1 - 09.9 L (Metric Format)
Pulses: 1 - 99
Options: Gallons (U.S. Format)
Liters (Metric Format)
ADD 01 GALLONS
EVERY 001 PULSES
Example:
Add 1 Gallon for Each Pulse in U.S. Format
NOTE: Only displayed if “Generic” is chosen for the flow meter.
PROGRAMMING UNIT
PLEASE WAIT...
Example:
Master Programming Mode is Exiting
CPO AUX RELAY
VOLUME: 000 9
Example:
Energize Chemical Pump relay every 50 gals (50)
Energize Chemical Pump relay every 200 L (200)
Range: 1 to 999 gallons in U.S. Format
1 to 9999 L in Metric Format
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 3 or 4 to appear. Use
the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 2:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 3 or 4 to appear. Use
the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 2:
gpm
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 3:
gpm
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 3:
30 SECONDS
NOTE: This display will not be viewed in System 14.
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. Use the Shift button to move one space
to the left.
TRIP DELAY 1:
30 SECONDS
NOTE: This screen will only display for System 14.
CYCLE 2 01:00:00 Example: Brine
01:00:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
Options: 01:00:00 for Conditioner for the 48-00 Stager & 51-09 Stager
(Default)
00:00:00 for Filter for the 48-00 Stager
CYCLE 3 00:10:00 Example: Fast Rinse
00:10:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 4 OFF Example:
Off (Default 48-00 Stager)
CYCLE 4 00:12:00 Example: Refill
00:12:00 (Default 51-09 Stager)
(Hours:Minutes:Seconds)
NOTE: This screen will only display when cycle 4 is not OFF.
CYCLE 5 OFF Example:
Off (Default 51-09 Stager)
1 to 997 gpm
1 to 3997 Lpm
2 to 998 gpm
1 to 3997 Lpm
3 to 999 gpm
1 to 3997 Lpm
VALVE ADDRESS:
#2
Options: Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve) (Default)
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
SYSTEM TYPE: 4
SINGLE UNIT
Options: System 4 (single unit)
System 5 (2-4 units) - Parallel Interlock
System 6 (2-4 units) - Parallel Series Regeneration
System 7 (2 units) - Alternating
System 9 (2-4 units) - Alternating
System 14 (2-4 units) - Demand Recall
Example:
System Type 4, Single Unit
Example:
Valve Address #2 (Second Control Valve) (Default)
SYSTEM SIZE:
2 VALVES
Options: 2 Valves in the System (Default)
3 Valves in the System
4 Valves in the System
Example:
2 Valves in the System (Default)
REGEN TYPE:
TIME CLK DELAYED
Options: Time Clock Delayed (System 4 Only) (Default)
Meter Immediate (All System Types)
Meter Delayed Fixed Reserve (Systems 4 & 6 Only)
Example:
Time Clock Delayed (Default)
VALVE TYPE:
STAGER-NOTCH CAM
Options: 2750
2850
2900
3150
3900
Stager - Notch Cam (Default)
Example:
Stager - Notch Cam (Default)
REMOTE SIGNAL
START:OFF
Options: 00:06:00 (Hours:Munutes:Seconds)
Range: 1 second to 99 minutes (1 hour, 39 minutes)
Example:
Off (Default)
DISPLAY FORMAT:
US-GALLONS
Options: U.S. - Gallons (Default)
EU-Metric - Liters (Metric)
Example:
U.S. Gallons (Default)
UNIT CAPACITY:
0300000 GRAINS
Options: Grains (in U.S. Format) (Default)
Grams (in Metric Format)
Example:
0300000 Grains (Default)
CAPACITY SAFETY
FACTOR: 00%
Range: 0 to 50%
Example:
00% (Default)
FEED WATER
HARDNESS: 15 GPG
Range: 1 to 199 Grains/Gallon (U.S. Format)
2 to 199 miligrams CaCOs/L (Metric Format)
Example:
15 GPG (U.S. Format) (Default)
SELECT LANGUAGE:
ENGLISH
Options: English
Espanol
Portugues
Deutsch
Francais
Example:
English
TRIP POINT 1:
000 gpm
Range: 2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
NOTE: This screen will not display for System Type 4.
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
NOTE: Use the Shift button to move to the left.
Range: 1 to 9,900,000 Grain Capacity in U.S. Format
1.0 to 190,000 grams CaCO3Capacity in Metric Format
NOTE: Use the Shift button to move to the left.
NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. Use the Shift button to change each
decimal position.
NOTE: This screen will only display for System 14.
REGENERATION DAY
OVERRIDE:OFF
Example:
Off (Default for Meter)
On (Default for Time Clock)
REGENERATION DAY
OVERRIDE:01 DAYS
Options: Off (Default for Meter) or On (Default for Time Clock)
Example:
1 Day
Range: 1 to 99 Days
REGENERATION
TIME: 02:00AM
Example:
2:00 A.M. (Default)
Options: A.M. (U.S. Format)
HR (Metric Format)
NOTE: Regeneration time will not appear unless Regeneration Day Override
is on.
CYCLE 1 00:10:00 Example: Backwash
00:10:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
AUXILIARY RELAY:
DISABLED
Example:
Auxiliary Relay is Disabled
Options: Enabled
Disabled (Default)
AUX RELAY OUTPUT
START 1 00:00:00
Example:
Auxiliary Relay Output Start 1 at
0 hours, 0 minutes, & 0 seconds
Range: 00:00:00 to 18:00:00
NOTE: Only displayed if Auxiliary Relay is enabled in previous screen.
Auxiliary Relay will only display if Chemical Pump is OFF for System
Types 6 & 7.
AUX RELAY OUTPUT
END 1 00:00:00
Example:
Auxiliary Relay Output End 1 at
0 hours, 0 minutes, & 0 seconds
Range: 00:00:00 to 18:00:00
CHEMICAL PUMP:
DISABLED
Example:
Chemical Pump is Disabled
Options: Enabled
Disabled (Default)
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
CPO AUX RELAY
TIME: 00:00:00
Example:
Each time chemical pump relay is on, run for
30 seconds (00:00:30)
Range: 00:00:00 to 02:00:00
FLOW METER:
1.0 PADDLE
Example:
1.0 Paddle Flow Meter
Options: 1.0 Paddle (Fleck)
1.0 Turbine (Fleck)
1.5 Paddle (Fleck)
1.5 Turbine (Fleck)
2.0 Paddle (Fleck)
3.0 Paddle (Fleck)
Generic
NOTE: Default flow meter type is based on the valve type. This screen will
only display on the lead unit for System Types 6 & 7. All other system types
it will display for all units.
MAXIMUM FLOW
RATE: 0000 gpm
Example:
Maximum Flow Rate of 0 gpm
Range: 20 - 2000 gpm (U.S. Format)
20 - 2000 Lpm (Metric Format)
NOTE: Only displayed if “Generic” is chosen for the flow meter.
Range: 1 - 99 Gallons (U.S. Format)
0.1 - 09.9 L (Metric Format)
Pulses: 1 - 99
Options: Gallons (U.S. Format)
Liters (Metric Format)
ADD 01 GALLONS
EVERY 001 PULSES
Example:
Add 1 Gallon for Each Pulse in U.S. Format
NOTE: Only displayed if “Generic” is chosen for the flow meter.
PROGRAMMING UNIT
PLEASE WAIT...
Example:
Master Programming Mode is Exiting
CPO AUX RELAY
VOLUME: 000 9
Example:
Energize Chemical Pump relay every 50 gals (50)
Energize Chemical Pump relay every 200 L (200)
Range: 1 to 999 gallons in U.S. Format
1 to 9999 L in Metric Format
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 3 or 4 to appear. Use
the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 2:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 3 or 4 to appear. Use
the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 2:
gpm
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 3:
gpm
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 3:
30 SECONDS
NOTE: This display will not be viewed in System 14.
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. Use the Shift button to move one space
to the left.
TRIP DELAY 1:
30 SECONDS
NOTE: This screen will only display for System 14.
CYCLE 2 01:00:00 Example: Brine
01:00:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
Options: 01:00:00 for Conditioner for the 48-00 Stager & 51-09 Stager
(Default)
00:00:00 for Filter for the 48-00 Stager
CYCLE 3 00:10:00 Example: Fast Rinse
00:10:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 4 OFF Example:
Off (Default 48-00 Stager)
CYCLE 4 00:12:00 Example: Refill
00:12:00 (Default 51-09 Stager)
(Hours:Minutes:Seconds)
NOTE: This screen will only display when cycle 4 is not OFF.
CYCLE 5 OFF Example:
Off (Default 51-09 Stager)
1 to 997 gpm
1 to 3997 Lpm
2 to 998 gpm
1 to 3997 Lpm
3 to 999 gpm
1 to 3997 Lpm
MASTER PROGRAMMING MODE FLOW
CHART
CAUTION
Before entering Master Programming, please
contact your local professional water dealer.
WhentheMasterProgrammingModeisentered,parameters
canbesettomakethetimer(s)functionasneeded.
NOTE: Depending on current option settings, some
displays cannot be viewed or set.
Entering Master Programming Mode
1. PressandholdtheShiftandUpbuttonsfor5seconds.
OR
2. Setthetimeofdaydisplayto12:01PMor12:01HR.Press
andholdUporDownbuttonstosetthetime.Thenpress
theUpandDownbuttonsatthesametimefor5seconds.
Exiting Master Programming Mode
1. PresstheExtraCyclebuttononceperdisplayuntilall
areviewed.MasterProgrammingModeisexitedandthe
normaldisplayscreenappears.
2. ToexittheMasterProgrammingModewithoutsaving
changes,presstheDiagnosticbutton.
NOTE: If no keypad activity is made for 5 minutes while
in the Master Programming Mode, or if there is a
power failure, no changes will be saved, and the
unit will go back to the main display screen.
Resets
Soft Reset: PressandholdtheUpandDownbuttonsfor25
secondsuntil12:00PM(or12:00HR)appears.Thisresetsall
parametersexceptfortheowmetertotalizervolume.
Master Reset: HoldtheExtraCyclebuttonwhilepoweringup
theunit.Thisresetsalloftheparametersintheunit.Check
andverifythechoicesselectedinMasterProgrammingMode.
NXTStagerControllerFE11•7

MASTER PROGRAMMING MODE FLOW
CHART continued
VALVE ADDRESS:
#2
Options: Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve) (Default)
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
SYSTEM TYPE: 4
SINGLE UNIT
Options: System 4 (single unit)
System 5 (2-4 units) - Parallel Interlock
System 6 (2-4 units) - Parallel Series Regeneration
System 7 (2 units) - Alternating
System 9 (2-4 units) - Alternating
System 14 (2-4 units) - Demand Recall
Example:
System Type 4, Single Unit
Example:
Valve Address #2 (Second Control Valve) (Default)
SYSTEM SIZE:
2 VALVES
Options: 2 Valves in the System (Default)
3 Valves in the System
4 Valves in the System
Example:
2 Valves in the System (Default)
REGEN TYPE:
TIME CLK DELAYED
Options: Time Clock Delayed (System 4 Only) (Default)
Meter Immediate (All System Types)
Meter Delayed Fixed Reserve (Systems 4 & 6 Only)
Example:
Time Clock Delayed (Default)
VALVE TYPE:
STAGER-NOTCH CAM
Options: 2750
2850
2900
3150
3900
Stager - Notch Cam (Default)
Example:
Stager - Notch Cam (Default)
REMOTE SIGNAL
START:OFF
Options: 00:06:00 (Hours:Munutes:Seconds)
Range: 1 second to 99 minutes (1 hour, 39 minutes)
Example:
Off (Default)
DISPLAY FORMAT:
US-GALLONS
Options: U.S. - Gallons (Default)
EU-Metric - Liters (Metric)
Example:
U.S. Gallons (Default)
UNIT CAPACITY:
0300000 GRAINS
Options: Grains (in U.S. Format) (Default)
Grams (in Metric Format)
Example:
0300000 Grains (Default)
CAPACITY SAFETY
FACTOR: 00%
Range: 0 to 50%
Example:
00% (Default)
FEED WATER
HARDNESS: 15 GPG
Range: 1 to 199 Grains/Gallon (U.S. Format)
2 to 199 miligrams CaCOs/L (Metric Format)
Example:
15 GPG (U.S. Format) (Default)
SELECT LANGUAGE:
ENGLISH
Options: English
Espanol
Portugues
Deutsch
Francais
Example:
English
TRIP POINT 1:
000 gpm
Range: 2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
NOTE: This screen will not display for System Type 4.
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
NOTE: Use the Shift button to move to the left.
Range: 1 to 9,900,000 Grain Capacity in U.S. Format
1.0 to 190,000 grams CaCO3Capacity in Metric Format
NOTE: Use the Shift button to move to the left.
NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. Use the Shift button to change each
decimal position.
NOTE: This screen will only display for System 14.
REGENERATION DAY
OVERRIDE:OFF
Example:
Off (Default for Meter)
On (Default for Time Clock)
REGENERATION DAY
OVERRIDE:01 DAYS
Options: Off (Default for Meter) or On (Default for Time Clock)
Example:
1 Day
Range: 1 to 99 Days
REGENERATION
TIME: 02:00AM
Example:
2:00 A.M. (Default)
Options: A.M. (U.S. Format)
HR (Metric Format)
NOTE: Regeneration time will not appear unless Regeneration Day Override
is on.
CYCLE 1 00:10:00 Example: Backwash
00:10:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
AUXILIARY RELAY:
DISABLED
Example:
Auxiliary Relay is Disabled
Options: Enabled
Disabled (Default)
AUX RELAY OUTPUT
START 1 00:00:00
Example:
Auxiliary Relay Output Start 1 at
0 hours, 0 minutes, & 0 seconds
Range: 00:00:00 to 18:00:00
NOTE: Only displayed if Auxiliary Relay is enabled in previous screen.
Auxiliary Relay will only display if Chemical Pump is OFF for System
Types 6 & 7.
AUX RELAY OUTPUT
END 1 00:00:00
Example:
Auxiliary Relay Output End 1 at
0 hours, 0 minutes, & 0 seconds
Range: 00:00:00 to 18:00:00
CHEMICAL PUMP:
DISABLED
Example:
Chemical Pump is Disabled
Options: Enabled
Disabled (Default)
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
CPO AUX RELAY
TIME: 00:00:00
Example:
Each time chemical pump relay is on, run for
30 seconds (00:00:30)
Range: 00:00:00 to 02:00:00
FLOW METER:
1.0 PADDLE
Example:
1.0 Paddle Flow Meter
Options: 1.0 Paddle (Fleck)
1.0 Turbine (Fleck)
1.5 Paddle (Fleck)
1.5 Turbine (Fleck)
2.0 Paddle (Fleck)
3.0 Paddle (Fleck)
Generic
NOTE: Default flow meter type is based on the valve type. This screen will
only display on the lead unit for System Types 6 & 7. All other system types
it will display for all units.
MAXIMUM FLOW
RATE: 0000 gpm
Example:
Maximum Flow Rate of 0 gpm
Range: 20 - 2000 gpm (U.S. Format)
20 - 2000 Lpm (Metric Format)
NOTE: Only displayed if “Generic” is chosen for the flow meter.
Range: 1 - 99 Gallons (U.S. Format)
0.1 - 09.9 L (Metric Format)
Pulses: 1 - 99
Options: Gallons (U.S. Format)
Liters (Metric Format)
ADD 01 GALLONS
EVERY 001 PULSES
Example:
Add 1 Gallon for Each Pulse in U.S. Format
NOTE: Only displayed if “Generic” is chosen for the flow meter.
PROGRAMMING UNIT
PLEASE WAIT...
Example:
Master Programming Mode is Exiting
CPO AUX RELAY
VOLUME: 000 9
Example:
Energize Chemical Pump relay every 50 gals (50)
Energize Chemical Pump relay every 200 L (200)
Range: 1 to 999 gallons in U.S. Format
1 to 9999 L in Metric Format
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 3 or 4 to appear. Use
the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 2:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 3 or 4 to appear. Use
the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 2:
gpm
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 3:
gpm
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 3:
30 SECONDS
NOTE: This display will not be viewed in System 14.
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. Use the Shift button to move one space
to the left.
TRIP DELAY 1:
30 SECONDS
NOTE: This screen will only display for System 14.
CYCLE 2 01:00:00 Example: Brine
01:00:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
Options: 01:00:00 for Conditioner for the 48-00 Stager & 51-09 Stager
(Default)
00:00:00 for Filter for the 48-00 Stager
CYCLE 3 00:10:00 Example: Fast Rinse
00:10:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 4 OFF Example:
Off (Default 48-00 Stager)
CYCLE 4 00:12:00 Example: Refill
00:12:00 (Default 51-09 Stager)
(Hours:Minutes:Seconds)
NOTE: This screen will only display when cycle 4 is not OFF.
CYCLE 5 OFF Example:
Off (Default 51-09 Stager)
1 to 997 gpm
1 to 3997 Lpm
2 to 998 gpm
1 to 3997 Lpm
3 to 999 gpm
1 to 3997 Lpm
VALVE ADDRESS:
#2
Options: Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve) (Default)
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
SYSTEM TYPE: 4
SINGLE UNIT
Options: System 4 (single unit)
System 5 (2-4 units) - Parallel Interlock
System 6 (2-4 units) - Parallel Series Regeneration
System 7 (2 units) - Alternating
System 9 (2-4 units) - Alternating
System 14 (2-4 units) - Demand Recall
Example:
System Type 4, Single Unit
Example:
Valve Address #2 (Second Control Valve) (Default)
SYSTEM SIZE:
2 VALVES
Options: 2 Valves in the System (Default)
3 Valves in the System
4 Valves in the System
Example:
2 Valves in the System (Default)
REGEN TYPE:
TIME CLK DELAYED
Options: Time Clock Delayed (System 4 Only) (Default)
Meter Immediate (All System Types)
Meter Delayed Fixed Reserve (Systems 4 & 6 Only)
Example:
Time Clock Delayed (Default)
VALVE TYPE:
STAGER-NOTCH CAM
Options: 2750
2850
2900
3150
3900
Stager - Notch Cam (Default)
Example:
Stager - Notch Cam (Default)
REMOTE SIGNAL
START:OFF
Options: 00:06:00 (Hours:Munutes:Seconds)
Range: 1 second to 99 minutes (1 hour, 39 minutes)
Example:
Off (Default)
DISPLAY FORMAT:
US-GALLONS
Options: U.S. - Gallons (Default)
EU-Metric - Liters (Metric)
Example:
U.S. Gallons (Default)
UNIT CAPACITY:
0300000 GRAINS
Options: Grains (in U.S. Format) (Default)
Grams (in Metric Format)
Example:
0300000 Grains (Default)
CAPACITY SAFETY
FACTOR: 00%
Range: 0 to 50%
Example:
00% (Default)
FEED WATER
HARDNESS: 15 GPG
Range: 1 to 199 Grains/Gallon (U.S. Format)
2 to 199 miligrams CaCOs/L (Metric Format)
Example:
15 GPG (U.S. Format) (Default)
SELECT LANGUAGE:
ENGLISH
Options: English
Espanol
Portugues
Deutsch
Francais
Example:
English
TRIP POINT 1:
000 gpm
Range: 2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
NOTE: This screen will not display for System Type 4.
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
NOTE: Use the Shift button to move to the left.
Range: 1 to 9,900,000 Grain Capacity in U.S. Format
1.0 to 190,000 grams CaCO3Capacity in Metric Format
NOTE: Use the Shift button to move to the left.
NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. Use the Shift button to change each
decimal position.
NOTE: This screen will only display for System 14.
REGENERATION DAY
OVERRIDE:OFF
Example:
Off (Default for Meter)
On (Default for Time Clock)
REGENERATION DAY
OVERRIDE:01 DAYS
Options: Off (Default for Meter) or On (Default for Time Clock)
Example:
1 Day
Range: 1 to 99 Days
REGENERATION
TIME: 02:00AM
Example:
2:00 A.M. (Default)
Options: A.M. (U.S. Format)
HR (Metric Format)
NOTE: Regeneration time will not appear unless Regeneration Day Override
is on.
CYCLE 1 00:10:00 Example: Backwash
00:10:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
AUXILIARY RELAY:
DISABLED
Example:
Auxiliary Relay is Disabled
Options: Enabled
Disabled (Default)
AUX RELAY OUTPUT
START 1 00:00:00
Example:
Auxiliary Relay Output Start 1 at
0 hours, 0 minutes, & 0 seconds
Range: 00:00:00 to 18:00:00
NOTE: Only displayed if Auxiliary Relay is enabled in previous screen.
Auxiliary Relay will only display if Chemical Pump is OFF for System
Types 6 & 7.
AUX RELAY OUTPUT
END 1 00:00:00
Example:
Auxiliary Relay Output End 1 at
0 hours, 0 minutes, & 0 seconds
Range: 00:00:00 to 18:00:00
CHEMICAL PUMP:
DISABLED
Example:
Chemical Pump is Disabled
Options: Enabled
Disabled (Default)
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
CPO AUX RELAY
TIME: 00:00:00
Example:
Each time chemical pump relay is on, run for
30 seconds (00:00:30)
Range: 00:00:00 to 02:00:00
FLOW METER:
1.0 PADDLE
Example:
1.0 Paddle Flow Meter
Options: 1.0 Paddle (Fleck)
1.0 Turbine (Fleck)
1.5 Paddle (Fleck)
1.5 Turbine (Fleck)
2.0 Paddle (Fleck)
3.0 Paddle (Fleck)
Generic
NOTE: Default flow meter type is based on the valve type. This screen will
only display on the lead unit for System Types 6 & 7. All other system types
it will display for all units.
MAXIMUM FLOW
RATE: 0000 gpm
Example:
Maximum Flow Rate of 0 gpm
Range: 20 - 2000 gpm (U.S. Format)
20 - 2000 Lpm (Metric Format)
NOTE: Only displayed if “Generic” is chosen for the flow meter.
Range: 1 - 99 Gallons (U.S. Format)
0.1 - 09.9 L (Metric Format)
Pulses: 1 - 99
Options: Gallons (U.S. Format)
Liters (Metric Format)
ADD 01 GALLONS
EVERY 001 PULSES
Example:
Add 1 Gallon for Each Pulse in U.S. Format
NOTE: Only displayed if “Generic” is chosen for the flow meter.
PROGRAMMING UNIT
PLEASE WAIT...
Example:
Master Programming Mode is Exiting
CPO AUX RELAY
VOLUME: 000 9
Example:
Energize Chemical Pump relay every 50 gals (50)
Energize Chemical Pump relay every 200 L (200)
Range: 1 to 999 gallons in U.S. Format
1 to 9999 L in Metric Format
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 3 or 4 to appear. Use
the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 2:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 3 or 4 to appear. Use
the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 2:
gpm
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 3:
gpm
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 3:
30 SECONDS
NOTE: This display will not be viewed in System 14.
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. Use the Shift button to move one space
to the left.
TRIP DELAY 1:
30 SECONDS
NOTE: This screen will only display for System 14.
CYCLE 2 01:00:00 Example: Brine
01:00:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
Options: 01:00:00 for Conditioner for the 48-00 Stager & 51-09 Stager
(Default)
00:00:00 for Filter for the 48-00 Stager
CYCLE 3 00:10:00 Example: Fast Rinse
00:10:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 4 OFF Example:
Off (Default 48-00 Stager)
CYCLE 4 00:12:00 Example: Refill
00:12:00 (Default 51-09 Stager)
(Hours:Minutes:Seconds)
NOTE: This screen will only display when cycle 4 is not OFF.
CYCLE 5 OFF Example:
Off (Default 51-09 Stager)
1 to 997 gpm
1 to 3997 Lpm
2 to 998 gpm
1 to 3997 Lpm
3 to 999 gpm
1 to 3997 Lpm
8•NXTStagerControllerFE11

USER PROGRAMMING MODE FLOW
CHART
Entering User Programming Mode
HoldtheUpandDownbuttonsfor5seconds.
FEED WATER
HARDNESS: gpg
REGENERATION DAY
OVERRIDE: OFF
REGENERATION DAY
OVERRIDE:99 DAYS
REGENERATION
TIME: 02:00AM
Options: U.S. Format [OFF] = default
Metric Format [OFF] = default
Options: U.S. Format [gpg]
Metric Format [mgL]
Options: U.S. Format [02:00AM] = default
Metric Format [02:00] = default
DIAGNOSTIC PROGRAMMING MODE
FLOW CHART
Entering Diagnostic Programming Mode
1. Pushandreleasethe"D"button.
2. PresstheExtraCyclebuttononceperdisplayuntilall
displaysareviewedandNormalDisplayisresumed.
3. Pushandreleasethe"D"buttonatanytimeduring
diagnosticmodeandthetimerwillexitthemode.
4. Dependingonthecurrentcontrollerprogramming,certain
displaysmaynotbeabletobeviewedorset.
CURRENT FLOW
RATE: 0 gpm
PEAK FLOW RATE:
0 gpm
TOTALIZER:
130 g
LAST TWO REGENS:
0 HOURS
LAST REGEN
0 HOURS
VOLUME REMAIN:
1000 g
VALVE ADDRESS
#2
VERSION:
X.XX
Explaination: Flow rate at this time.
Explaination: Peak flow since last regeneration.
Explaination: Gallons at the outlet since installation.
Explaination: Hours between the last regeneration and the one before it.
Explaination: Hours since last regeneration.
Explaination: Volume remaining; can be adjusted.
Explaination: Controller unit number.
Explaination: Installed software level of the controller in use.
NXTStagerControllerFE11•9

NXT Multi Language
Programming Parameters and Ranges
Gallons Liters
Valve Address 12341234 1 2 12341234
Select Language x x x xxxxxxxx x x xxxxxxxx
System Size x x x x x
Regen Type x x x xxxxxxxx x x xxxxxxxx
Valve Type x x x xxxxxxxx x x xxxxxxxx
Regenerant Flow x x x xxxxxxxx x x xxxxxxxx
Remote Signal Start x x x xxxxx x xxxx
Display Format x x x xxxxxxxx x x xxxxxxxx US - Gallons EU - Metric-Liters
Unit Capacity x x xxxxx x x xxxxxxxx 1 - 9900000 Grains 1 - 198000 gCaCO3
Capacity Safety Factor x x xxxxx x x xxxxxxxx
Feed Water Hardness x x xxxxx x x xxxxxxxx 1 - 199 Grains/Gallons 1 - 1999 mgL
Trip Point 1 x0 - 997gpm 0 - 3997 Lpm
Trip Delay 1 x30 - 99 Seconds 30 - 99 Seconds
Trip Point 2 xTrip Point 1 + 1 - 998 gpm Trip Point 1 + 1 - 3998 Lpm
Trip Delay 2 x30 - 99 Seconds 30 - 99 Seconds
Trip Point 3 xTrip Point 2 + 1 - 999 gpm Trip Point 2 + 1 - 3999 Lpm
Trip Delay 3 x30 - 99 Seconds 30 - 99 Seconds
Regeneration Day Override x x x xxxxx x xxxxxxxx
Regeneration Time
xo o ooooo o o oooooooo 12:00 a.m. - 11:59 p.m. 00:00 - 23:59 Hour
Cycle 1 x x x xxxxxxxx x x xxxxxxxx
Cycle 2 x x x xxxxxxxx x x xxxxxxxx
Cycle 3 x x x xxxxxxxx x x xxxxxxxx
Cycle 4 x x x xxxxxxxx x x xxxxxxxx
Cycle 5 x x x xxxxxxxx x x xxxxxxxx
Auxiliary Relay x x x x x x x uxxx ux xxxxxxxx
Aux Relay Output Start
c c c cccccccc c c cccccccc
Aux Relay Output End
c c c cccccccc c c cccccccc
Chemical Pump x x x x x x u u xxxxxxxx
CPO Aux Relay Volume
c c ccccc c cccccccc 1 - 999 gallons 0001 - 9999 Liters
CPO Aux Relay Time
c c ccccc c cccccccc 00:00:01 - 02:00:00 00:00:01 - 02:00:00
Flow Meter x x xxxxx x xxxxxxxx
Generic
x x xxxxx x xxxxxxxx
Maximum Flow Rate
a a aaaaa a aaaaaaaa 20 - 2000 GPM 20 - 2000 LPM
Add _ _ _ Gallons or Liters
a a aaaaa a aaaaaaaa 1 - 255 Gallons 001 - 255 Liters
Every _ _ _ Pulses
a a aaaaa a aaaaaaaa 1 - 255 1 - 255
Notes o -
u -
c -
a -
System Type
If Generic Flow Meter is chosen, then programming parameters will be viewed.
Regeneration Time will only be viewed if Regeneration Day Override is used.
If Auxiliary Relay is Enabled then Chemical Pump Relay will not be viewed or if Chemical Pump Relay is Enabled then Auxiliary Relay will not be viewed.
All Relay Output parameters programming will be viewed if Enabled.
00:00:01 to Total Regeneration Time - 1
Start Time + 1 to Total Regeneration Time
Enabled, Disabled
Off, 1 - 99
00:00:00 - 04:00:00
Off, 00:00:00 - 04:00:00
1" 1.5" Paddle or Turbine, 2" Paddle, 3" Paddle, Generic
Off, 00:00:00 - 04:00:00
Off, 00:00:00 - 04:00:00
Off, 00:00:00 - 04:00:00
Enabled, Disabled
2750, 2850, 2900, 3150, 3900, Stager
Downflow, Upflow, Upflow Fill First
Off, 00:00:01 - 01:39:00
0- 50%
6
Series
7
Alternating
9
Alternating
Time Clock, Metered Delayed, Metered Immediate
Programming Parameter Ranges
4
Time
Clock
4
Metered
Immediate
4
Metered
Delayed
5
Interlock
14
Demand
Recall
1 thru 4
English, Espanol, Portugues, Deutsch, Francais
1 thru 4
10•NXTStagerControllerFE11

Stager Operation
Stagersaremotordriven,rotarymulti-portvalvesusedto
controlasetofvalvesinapredenedsequence.Theyfunction
byinternallyconnectinginletpressuretoadenedsetof
controlportsandallowingothercontrolportsbeventedthrough
adrain.Controlportsareusedtoopenandclosevalvesina
presetsequence.Asthestageradvancestovariouspositions,
differentvalvesareopenandclosedinasystem.Thecontrol
portpressureandventsequenceispresetatthefactoryand
cannotbeeldaltered.
Stager Installation
1. Connectaconstantpressurewaterorairsourcetothe1/8"
NPTstagerinlet.Controluidpressuremustbeequaltoor
greaterthansystempressure.Toensurelongtroublefree
operation,a100micronlterinthecontrolpressurelineis
recommended.
2. Stagerdrainportshouldbeleftopenordischargedto
unrestrictedoropendrain.DONOTplugorrestrictdrain
port.
3. Connectthe1/8"NPTcontrolportstoappropriatevalves.
RefertotubingschematicprovidedinthePlumbing
Diagramssectionofthismanual.Tubinginsidediameter
shouldbe1/8"orlarger.
NXTStagerControllerFE11•11

Optional Hard
Water Bypass Valve
Note: All valves normally open except optional valve 2A.
4 Position Filter (48-00 Stager)
Optional Hard
Water Bypass Valve
Note: All valves normally open except optional valve 2A.
Installer to plug for
filter operation
Note: Program Cycle 2 time to 00:00:00 for filter operation.
4 POSITION FILTER
PLUMBING DIAGRAMS
4 Position Softener (48-00 Stager)
12•NXTStagerControllerFE11

PLUMBING DIAGRAMS continued
5 Position Softener w/Timed Brine Rell
(51-09 Stager)
Note: All valves normally open except optional valve 2A.
Plugs installed
at factory
Optional Hard
Water Bypass Valve
SOLENOID USE
Solenoids only required for Systems 7, 9 and 14
Installer to
Plug Port 2
Series 48-00/51-09 Stager
1 2
3
Drain
Solenoid
Valve
Inlet Pressure
1
3
2
Flow
Solenoid Energized
1
3
2
Flow
Solenoid De-energized
Energized To Close
TheNXTStagercontrolcanoperateanoptional24VAC
solenoidtocontrolwhenatankisoffline.Thissolenoidis
electricallyconnectedtothe"lowerdrive"connectiononthe
circuitboard,andcontrolpressureisrunthroughthesolenoid
totheserviceoutletdiaphragmvalve.
Thesolenoidinstalledatthefactoryisauniversaltype.Itis
plumbedinanenergizetocloseconguration.
WhenatankentersRegenerationorStandbythesolenoidis
energized.Pressurefromsolenoidport1passestoport2.The
diaphragmvalve#2willclose.
WhenatankentersInServicethesolenoidisde-energized.
Theinletpressuretosolenoidport2isstopped.The
diaphragmvalveisventedthroughsolenoidport2toport3
(drain).Thevalve#2opens.
NXTStagerControllerFE11•13

Item No. QTY Part No. Description
1.................. 1......... 43001 ................... Motor, 24V, 50/60Hz, 5/8 RPM
2 .................. 1......... 1070436 ............... Plate,MotorMTG,Stagers
3 .................. 6......... 1075746 ............... Screw,6-32x1/4",Phil
4 .................. 4......... 1072371 ............... Screw,6-32x.375,RD.HD,SS
5.................. 1......... 1075737 ............... Gasket, Stager MTG, 48
6 .................. 1......... 1071667 ............... O-ring,2-010,Nitrile
7.................. 1......... 1075454*.............. ThumbWheel,Molded
8.................. 1......... 1074074 ............... Washer, 302, SS
9.................. 1......... 1070448 ............... Shaft, Stem Assy, 48 Series
10 ................ 1......... 1074784 ............... Backplate,48-00,Brass
11 ................ 1......... 1074793............... Bonnet, 48, Brass
12 ................ 1......... 1074825 ............... InletStrainer,Assy
13 ................ 3......... 1075759 ............... Screw,PanHead,6-32x.88"
14................ 1......... 1076234 ............... Spring, Wave, 17-7 SS, 48 STGR
15 ................ 1......... 1074845 ............... Stemplate,48,-00
16................ 1......... 1076245*.............. Cam,Cycle,Machined
17 ................ 1......... 1070437 ............... Plate,BottomMTG,Stager
18 ................ 2......... 1075499 ............... Switch, Micro
19 ................ 1......... 1075455 ............... SwitchSpacer,Insulator
20 ................ 1......... 1084171 ............... Gasket,Backplate,48Nitrile
21 ................ 2......... 1073593 ............... Washer,Lock,Internal,#4,SS
22 ................ 2......... 1075757 ............... MachineScrew,4-40x1.00,SSif2
switches
.................... 2......... 1072389 ............... Screw,4-40x1-3/8"if3switches
23................ 1......... 1075453*.............. Cam,Auxiliary,Blank
24 ................ 2......... 3014200 ............... Screw,SlottedHXHD,10-32
25 ................ 2......... 1078992 ............... Washer,Lock,Internal,#10,SS
26................ 1......... 14202-01.............. Screw,HexWasher#8-32x5/16
27................ 1......... 43077-00.............. Label,Dial,STGR,23/8x7/8
28................ 2......... 17967-01.............. Nut,LiquidTight,HeyCo3169
29................ 2......... 17967-02.............. Fitting,LiquidTight,Black
30 ................ 1......... 1075538 ............... TerminalBlock,10
31 ................ 2......... 1072369 ............... Screw,PanHD,4-40x5/8,SS
32 ................ 1......... 1076219 ............... Label,Ground,.75Dia.
STAGER CONTROLLER, 48ES, NEMA 4
24V/50-60Hz ASSEMBLY
33 ................ 1......... 1073732 ............... Label,TerminalStrip,1-10
34................ 1......... 43094-01.............. Enclosure,48ES,NEMA4
35 ................ 1......... 43093 ................... Panel,A10P,8"x6"Modied
36................ 1......... 43046*.................. KeypadLabelAssy,XT,NEMA4
37 ................ 1......... 1070649 ............... Solenoid,N1,24/60
38................ 4......... 42827-04.............. Stand-off,Plastic,.625"
39 ................ 1......... 42753U* ............... CircuitBoard,XT,ML
40 ................ 4......... 43092 ................... Screw,FLTHD,#6-20,TYP-B
41................ 1......... 40941 ................... Harness, Upper Drive
42 ................ 1......... 43090 ................... Washer,Sealing,Conduit,1/2"
43 ................ 1......... 43140 ................... Fitting,NPT1/2,Conduit
44................ 1......... 43141 ................... Washer, Lock, 7/8, INT Tooth
45 ................ 1......... 61764 ................... CableAssy,COM,CAT5E,NEMA4
46................. 1..........19121-09 ............... MeterCableAssy,NT,99.5"
47................. 4..........1081780 ................ Mount,CableTie,4-Way
48................. 1..........1072379 ................ Screw,10-32x5/8",RNDHD,SS
49................. 1..........1071660 ................ Nut,Hex,10-32,KEPS
50................. 2..........43138 ....................Plug,.75,HeyCo
51................. 1..........43177 ....................Washer,Lock,#8,INT,18-8SS
52................. 1..........1071648 ................ Nut
Not Shown
.................... 1......... 61500-48/51LNE.. Line Drawing
.................... 9......... 1073701 ............... Tie,Cable,HeyCoVNT#4-18
.................... 2......... 1073702 ............... Wire Tie
.................... 3......... 1073955 ............... Terminal,Ring,#10,16-14GA
.................... 1......... 1073875 ............... Wire,Black,18AWG
.................... 1......... 1073880 ............... Wire, White, 18 AWG
.................... 1......... 1073874 ............... Wire, Green, 14 AWG
.................... 1......... 43163 ................... Literature,3214NXTStager,S/M
.................... 1......... 43012 ................... Wiring Diagram, 48/51ES
.................... 1......... 61784 ................... Service Kit, 48/51, Timer
.................... 1......... 61783 ................... ServiceKit,48/51,Solenoid
*OnlysoldasServiceAssembly
Item No. QTY Part No. Description
36
37
42
40
ISO FRONT VIEW
SCALE 1:4
HOFFMAN PARTS BAG
SCALE 1:4
41
25
24
11
68
14
9
15
20
10
12
13
5
17
19
21
22
4
23
7
3
1
2
3
26
27
18
46
29
28
30 33
32
50
52
48
47
44
31 34
38
39
16
43
35
51
47
3
AUX 1 (RED)
CYCLE (WHITE)
TO METER
NOT CONNECTED
KIT BR61764
SCALE 1:4
45
BOTTOM DETAIL VIEW
SCALE 1:2
12
49
61803 Rev D
14•NXTStagerControllerFE11

BOTTOM DETAIL VIEW
SCALE 1:2
42
42
7
30
15
14
43
40 48
45
41
44
46
49
6
50
10
11
12
4
13
5
3
1
2
3
17
9
35
19
18
20 23
22
51
38
37
32
21 39
29
27
8
47
33
24
16
34
36
36
KIT BR61764
SCALE 1:4
AUX 1 (Red)
CYCLE (White)
52
25
31
26
28
ISO FRONT VIEW
SCALE 1:4
HOFFMAN PARTS BAG
SCALE 1:4
53
STAGER CONTROLLER, 51ES, NEMA 4
24V/50-60Hz ASSEMBLY
Item No. QTY Part No. Description
1.................. 1......... 43001 ................... Motor, 24V, 50/60Hz, 5/8 RPM
2 .................. 1......... 1070436 ............... Plate,MotorMTG,Stagers
3 .................. 6......... 1075746 ............... Screw,6-32x1/4",Phil
4 .................. 2......... 1072371 ............... Screw,6-32x.375,RD.HD,SS
5.................. 1......... 1075454*.............. ThumbWheel,Molded
6.................. 1......... 1075674 ............... Gasket, Stager MTG, 51, 96
7 .................. 1......... 1074825 ............... InletStrainer,Assy
8.................. 1......... 1076243*.............. Cam,Cycle,Machined
9 .................. 2......... 1075499 ............... Switch, Micro
10 ................ 1......... 1075455 ............... SwitchSpacer,Insulator
11 ................ 2......... 1073593 ............... Washer,Lock,Internal,#4,SS
12 ................ 2......... 1075757 ............... MachineScrew,4-40x1.00,SS
13................ 1......... 1075453*.............. Cam,Auxiliary,Blank
14 ................ 2......... 3014200 ............... Screw,SlottedHXHD,10-32
15 ................ 2......... 1078992 ............... Washer,Lock,Internal,#10,SS
16................ 1......... 14202-01.............. Screw,HexWasher#8-32x5/16
17................ 1......... 43078-09.............. Label,Dial,STGR,23/8x7/8
18................ 2......... 17967-01.............. Nut,LiquidTight,HeyCo3169
19................ 2......... 17967-02.............. Fitting,LiquidTight,Black
20 ................ 1......... 1075538 ............... TerminalBlock,10
21 ................ 2......... 1072369 ............... Screw,PanHD,4-40x5/8,SSif2
switches
.................... 2......... 1072389 ............... Screw,4-40x1-3/8"if3switches
22 ................ 1......... 1076219 ............... Label,Ground,.75Dia.
23 ................ 1......... 1073732 ............... Label,TerminalStrip,1-10
24 ................ 1......... 43093 ................... Panel,A10P,8"x6"Modied
25................ 1......... 43046*.................. KeypadLabelAssy,ST,NEMA4
26 ................ 1......... 1070649 ............... Solenoid,N1,24/60
27 ................ 1......... 42753U* ............... CircuitBoard,XT,ML
28 ................ 4......... 43092 ................... Screw,FLTHD,#6-20,TYP-B
29................ 4......... 42827-04.............. Stand-off,Plastic,.625"
30................ 1......... 40941 ................... Harness, Upper Drive
31 ................ 1......... 43090 ................... Washer,Sealing,Conduit,1/2"
32................ 1......... 43141 ................... Washer, Lock, 7/8, INT Tooth
33 ................ 1......... 43140 ................... Fitting,NPT1/2,Conduit
34 ................ 1......... 61764 ................... CableAssy,COM,CAT5E,NEMA4
35 ................ 1..........19121-09 ............... MeterCableASSY,NT,99.5"
36................ 4..........1081780 ................Mount,CableTie,4-Way
37................ 1..........1072379 ................Screw,10-32x5/8",RNDHD,SS
38................ 1..........1071660 ................Nut,Hex,10-32,KEPS
39................ 1......... 43094-02.............. Enclosure,51ES,NEMA4
40................ 1......... 1075241 ............... Washer, 302, SS
41................ 1......... 1070438 ............... Shaft, Stem Assy, 51 Series
42 ................ 2......... 1071903 ............... MalePipePlugs
43................ 1......... 1074883 ............... Bonnet, 51, Brass
44................ 1......... 1075647*.............. Stemplate,96,Alpha
45 ................ 1......... 1075242 ............... Spring, Compression
46................. 1..........1084172 ................ Gasket,Backplate,51&96STGRS
47................. 1..........1074866*............... Backplate,D.V.Nest
48................. 1..........1071716 ................O-ring, EP, ORE-011
49................. 4..........1075760 ................ Screw,Machine,#6-32x11/8
50................. 1..........1077824 ................ MTGPlate,BTM,STGR,51ES
51................. 2..........43138 ....................Plug,.75,HeyCo
52................. 1..........43177 ....................Washer,Lock,#8,INT,18-8SS
53................. 1..........1071648 ................ Nut
Not Shown
.................... 1......... 61500-48/51LNE.. Line Drawing
.................... 9......... 1073701 ............... Tie,Cable,HeyCoVNT#4-18
.................... 2......... 1073702 ............... Wire Tie
.................... 3......... 1073955 ............... Terminal,Ring,#10,16-14GA
.................... 1......... 1073875 ............... Wire,Black,18AWG
.................... 1......... 1073880 ............... Wire, White, 18 AWG
.................... 1......... 1073874 ............... Wire, Green, 14 AWG
.................... 1......... 43163 ................... Literature,3214NXTStager,S/M
.................... 1......... 43012 ................... Wiring Diagram, 48/51ES
.................... 1......... 61784 ................... Service Kit, 48/51, Timer
.................... 1......... 61783 ................... ServiceKit,48/51,Solenoid
*OnlysoldasServiceAssembly
Item No. QTY Part No. Description
61804 Rev D
NXTStagerControllerFE11•15

WIRING DIAGRAM 48/51ES STAGER
CONTROLLER
M 1
C
N.O.
N.C .
S W 2
FM
C
N.O.
N.C .
S W 1
S W 3
N.C .
N.O .
C
1
2
3
4
5
6
7
8
9
10
BLACK
ORANGE
BLACK
PURPLE
PURPLE
ORANGE
BLACK
YELLOW
WT/BLK
BLACK
WHITE
BLACK
GREEN
RED
SWITCHED HOT
NEUTRAL
OPTIONAL SOLENOID VALVE ENERGIZED
DURING REGENERATION OR STANDBY
(P6 OUTPUT - 24VAC 50/60Hz, 1.0 A,
MAX.)
OPTIONAL INTERLOCK
SWITCH (N.O.)
UNSWITCHED HOT
24VAC/3A MAX. RESISTIVE
30VDC/3A MAX. RESISTIVE
NEUTRAL
SWITCHED HOT
OPTIONAL MOTOR/PUMP ON DURING REGENERATION
OR CPO DEVICE ON DURING SERVICE (N.O. OUTPUT)
OPTIONAL REMOTE
SIGNAL START
SWITCH (N.O.)
BLUE
BLUE
BR43001
24V/50/60, 4 WATT OPTIONAL
AUX CAM
#2
AUX CAM
#1 PROGRAM CAM
(HOMING CAM)
(SWITCH HOUSING
IS RED)
(CYCLE CAM)
NOTES:
SWITCHES SHOWN IN SERVICE.1.
NEMA 4 ENCLOSURE WIRING IS SHOWN.2.
BLACK
BROWN
BLUE
GREEN/YELLOW
BLACK
BLACK
GREEN/YELLOW
GROUND
SCREW
GROUND
LUG
STAGER
MOUNTING
SCREW
GREEN/YELLOW
GREEN/YELLOW
GREEN/YELLOW
BLACK
WHITE
GREEN/YELLOW
WHITE
BLACK
BLACK
WHITE
BLACK
S1
-CLOSED CONTACT PREVENTS REGENERATION
-INPUT SIDE PULLED UP TO 32 VDC
-CLOSED CONTACT INITIATES REGENERATION IF OPTION ENABLED
-INPUT SIDE PULLED UP TO 32 VDC
CAN1 CAN2
METER
24V AC
UPPER DRIVE
LOWPERDRIVE
LOC K OUT
REMOTE START
GND
AUX
F1
OPTIONAL FLOW METER
-NOT REQUIRED FOR TIME CLOCK OR REMOTE SINGAL
START REGENERATION APPLICATIONS.
MODEL 48 & 51
STAGER
43012 Rev E
16•NXTStagerControllerFE11

TROUBLESHOOTING
Detected Errors
Ifacommunicationerrorisdetected,anErrorScreenwill
alternatewiththemain(timeofday)screeneveryfewseconds.
• AllunitsInServiceremainintheInServiceposition.
• AllunitsinStandbygotoInService.
• AnyunitinRegenerationwhentheerroroccurs
completesRegenerationandgoestoInService.
• NounitsareallowedtostartaRegenerationCyclewhile
theerrorconditionexists,unlesstheyaremanuallyforced
into Regeneration.
• Whenanerroriscorrectedandtheerrornolonger
displays(itmaytakeseveralsecondsforalloftheunits
inasystemtostopdisplayingtheerrormessage),the
systemreturnstonormaloperation.
NOTE: During the error condition the control continues
to monitor the ow meter and update the volume
remaining. Once the error condition is corrected
all units return to the operating status they
were in prior to the error. Regeneration queue is
rebuilt according to the normal system operation.
Or, if more than one unit has been queued for
regeneration, then the queue is rebuilt according to
which one communicates rst.
Message Displayed Cause For Error Correction
Flashingtime Poweroutage. ProgramtimebyholdingUPonUnit#1.
DetectedError=MatchingAddress Twoormoreunitsprogrammedwiththesamevalve
addressnumber.
Programeachunitwithuniquevalve
addressnumberinMasterProgramming.
DetectedError=ProgramMismatch Masterprogramparametersdonotmatchbetweentwoor
morecontrols. ConrmMasterProgrammingforeachunit.
DetectedError=NoMessage#1 NopowertoControl#1. PowerControl#1.
CommunicationCabletoValveAddress#1badormissing. ConnectorreplaceCommunicationCable.
DetectedError=NoMessage#2 NopowertoControl#2. PowerControl#2.
CommunicationCabletoValveAddress#2badormissing. ConnectorreplaceCommunicationCable.
DetectedError=NoMessage#3 NopowertoControl#3. PowerControl#3.
CommunicationCabletoValveAddress#3badormissing. ConnectorreplaceCommunicationCable.
DetectedError=NoMessage#4 NopowertoControl#4. PowerControl#4.
CommunicationCabletoValveAddress#4badormissing. ConnectorreplaceCommunicationCable.
DetectedError=E2ResetUnit This message appears after a software reset. ReprogramcontrolusingMaster
Programming section.
TestMode CircuitBoardwasnotprogrammedatfactory. ReplaceCircuitBoard.
BlackSquaresonscreen BadCircuitBoard. ReplaceCircuitBoard.
INI on screen for more than 2
minutes Circuitboardnotgettingfeedbackfromcycleswitch.
InspectMotor-shouldberotating.
Connectwireharnesstocycleswitch.
CheckCycleMicroSwitch.
CHG on screen for more than 2
minutes Controlprogrammedincorrectlyas2900or3900valvetype. ReprogramunitasStagerValvetype.
NXTStagerControllerFE11•17

SERVICE ASSEMBLIES
48-00 ES Stager Assembly
61808-01 ....................Stager Assy, 48-00, NXT 24VAC, HMG
No2ndAuxSwitch
61808-02 ....................Stager Assy, 48-00, NXT 24VAC, SA,
2ndAuxNotchedinService
61808-03 ....................Stager Assy, 48-00, NXT 24VAC, SC,
2ndAuxNotchedInBackwash
1074817......................Kit,InternalParts,48-00Stager
61817-01 ....................CamAssy,48-00NXT,HMG,no2nd
AuxCam
61817-02 ....................CamAssy,48-00NXT,SA,2ndAux
NotchedinService
61817-03 ....................CamAssy,48-00NXT,SC,2ndAux
NotchedinBackwash
51-09 ES Stager Assembly
61809-01 ....................Stager Assy, 51-09, NXT 24VAC, HMG,
No2ndAuxSwitch
61809-02 ....................Stager Assy, 51-09, NXT 24VAC, SA,
2ndAuxNotchedinService
61809-03 ....................Stager Assy, 51-09, NXT 24VAC, SD,
2ndAuxNotchedinBackwash
61809-04 ....................Stager Assy, 51-09, NXT 24VAC, SH,
2ndAuxNotchedinRell
1074888......................Kit,InternalParts,51-09Stager
61818-01 ....................CamAssy,51-09NXT,HMG,No2nd
AuxSwitch
61818-02 ....................CamAssy,51-09NXT,SA,2ndAux
NotchedinService
61818-03 ....................CamAssy,51-09NXT,SD,2ndAux
NotchedinBackwash
61818-04 ....................CamAssy,51-09NXT,SH,2ndAux
NotchedinRell
Meter Assembly, In Line
60613..........................MeterAssy,1",Elec.,BrassBody,PDL
60614..........................MeterAssy,1-1/2",Elec.,BrassBody,
PDL
60616..........................MeterAssy,2",Elec.,BrassBody,PDL
60617..........................MeterAssy,3",Elec.,BrassBody,PDL
60625..........................MeterAssy,2",Elec.,Plastic,PDL
61560-01 ....................MeterAssy,1",Elec.,Plastic,Turbine
61560-07 ....................MeterAssy,1",Elec.,BrassTHDS,
Turbine(Fleck)
61560-09 ....................MeterAssy,1-1/2",Elec.,BrassTHDS,
Turbine(Fleck)
61560-13 ....................MeterAssy,1-1/2",Elec.,Plastic,
Turbine(Fleck)
Service Parts Common To Both 48ES & 51 ES Stager Control
61783..........................Kit,48/51ESNEMA4,Solenoid
61784..........................Kit48/51ES,3214NXT,CKTBoard&
Keypad
61764..........................CableAssy,Communication,CAT5,
5 Meters Long
42469..........................Transformer, 120V/24V, 40VA
41049..........................Transformer, 220/24V/EUR/108VA
41050..........................Transformer, 220/24V/AUST/108VA
19121-09 ....................MeterCable,99.5",PaddleWheel
19121-10 ....................MeterCable,303.5",PaddleWheel
19791-04 ....................MeterCable,100",Turbine(Fleck)
19791-05 ....................MeterCable,304",Turbine(Fleck)
1075499......................Switch, Micro
40941..........................Wire Harness, Upper Drive
1075502......................WireHarness,2ndAuxSwitch
43001..........................Motor
18•NXTStagerControllerFE11

NXTStagerControllerFE11•19

20•NXTStagerControllerFE11
This manual suits for next models
3
Table of contents
Other Pentair Pool Products Controllers manuals