Pepperl+Fuchs VisuNet FLX RM-320P Series User manual

VisuNet FLX Panel
RM-320P-*
PC-320P-*
DM-320P-*
Manual

With regard to the supply of products, the current issue of the following document is applicable:
The General Terms of Delivery for Products and Services of the Electrical ndustry, published
by the Central Association of the Electrical ndustry (Zentralverband Elektrotechnik und Elek-
troindustrie (ZVE ) e.V.) in its most recent version as well as the supplementary clause:
"Expanded reservation of proprietorship"
Worldwide
Pepperl+Fuchs Group
Lilienthalstr. 200
68307 Mannheim
Germany
Phone: +49 621 776 - 0
E-mail: [email protected]
North A erican Headquarters
Pepperl+Fuchs nc.
1600 Enterprise Parkway
Twinsburg, Ohio 44087
USA
Phone: +1 330 425-3555
E-mail: [email protected]
Asia Headquarters
Pepperl+Fuchs Pte. Ltd.
P+F Building
18 Ayer Rajah Crescent
Singapore 139942
Phone: +65 6779-9091
E-mail: [email protected]rl-fuchs.com
https://www.pepperl-fuchs.com

VisuNet FLX Panel
Contents
2021-04
3
1 History of the Manual ................................................................................................ 4
2 Introduction................................................................................................................ 5
2.1 Content of this Docu ent............................................................................. 5
2.2 Manufacturer .................................................................................................. 5
2.3 Target Group, Personnel ............................................................................... 5
2.4 Sy bols Used ................................................................................................ 6
2.5 Tolerances for Linear Di ensions ............................................................... 7
3 Product Description .................................................................................................. 8
3.1 Overview......................................................................................................... 8
3.2 Reference Docu ents................................................................................. 10
3.3 Technical Data.............................................................................................. 11
3.4 Di ensions and Na eplates...................................................................... 19
4 Mechanical Installation ........................................................................................... 22
4.1 Unpacking .................................................................................................... 22
4.2 Panel Installation ......................................................................................... 23
4.3 General Installation Infor ation ................................................................ 24
4.4 Mounting the Panel in the enclosure ......................................................... 25
5 Electrical Installation............................................................................................... 31
5.1 Equipotential Bonding of the VisuNet FLX Panel ..................................... 32
5.2 Power Connection........................................................................................ 33
6 Interfaces.................................................................................................................. 35
6.1 Co puting Unit - Interface Connectors..................................................... 35
6.1.1 Power Limitations.............................................................................................................. 35
7 Maintenance............................................................................................................. 36
7.1 Exchanging the BPC3200-* or DMU3200-* ................................................ 37
7.2 Dis ounting the Display Unit..................................................................... 41
7.3 Gloves Tested for Touch Sensitivity ........................................................... 42
7.4 Cleaning........................................................................................................ 43
8 Accessories.............................................................................................................. 44

2021-04
4
VisuNet FLX Panel
History of the Manual
1 History of the Manual
The following editions of the manual have been released:
Version Co ents
04/2021 First edition

VisuNet FLX Panel
ntroduction
2021-04
5
2 Introduction
2.1 Content of this Docu ent
This document contains information that you need in order to use your product throughout the
applicable stages of the product life cycle. These can include the following:
•Product identification
•Delivery, transport, and storage
•Mounting and installation
•Commissioning and operation
•Maintenance and repair
•Troubleshooting
•Dismounting
•Disposal
The documentation consists of the following parts:
•Present document
•nstruction manual
•Datasheet
Additionally, the following parts may belong to the documentation, if applicable:
•EU-type examination certificate
•EU declaration of conformity
•Attestation of conformity
•Certificates
•Control drawings
•Additional documents
2.2 Manufacturer
2.3 Target Group, Personnel
Responsibility for planning, assembly, commissioning, operation, maintenance, and dismount-
ing lies with the plant operator.
Only appropriately trained and qualified personnel may carry out mounting, installation, com-
missioning, operation, maintenance, and dismounting of the product. The personnel must have
read and understood the instruction manual and the further documentation.
Prior to using the product make yourself familiar with it. Read the document carefully.
Note
This document does not substitute the instruction manual.
Note
For full information on the product, refer to the instruction manual and further documentation on
the nternet at www.pepperl-fuchs.com.
Pepperl+Fuchs Group
Lilienthalstraße 200, 68307 Mannheim, Germany
nternet: www.pepperl-fuchs.com

2021-04
6
VisuNet FLX Panel
ntroduction
2.4 Sy bols Used
This document contains symbols for the identification of warning messages and of informative
messages.
Warning Messages
You will find warning messages, whenever dangers may arise from your actions. t is mandatory
that you observe these warning messages for your personal safety and in order to avoid prop-
erty damage.
Depending on the risk level, the warning messages are displayed in descending order as fol-
lows:
Infor ative Sy bols
Action
This symbol indicates a paragraph with instructions. You are prompted to perform an action or
a sequence of actions.
Danger!
This symbol indicates an imminent danger.
Non-observance will result in personal injury or death.
Warning!
This symbol indicates a possible fault or danger.
Non-observance may cause personal injury or serious property damage.
Caution!
This symbol indicates a possible fault.
Non-observance could interrupt the device and any connected systems and plants, or result in
their complete failure.
Note
This symbol brings important information to your attention.

VisuNet FLX Panel
ntroduction
2021-04
7
2.5 Tolerances for Linear Di ensions
For all dimension drawings (e.g. dimension drawings, etc.) the European dimension standards
are valid.
All dimensions are in mm.
Unless otherwise specified, the following general tolerances are valid.
No inal di ension ranges
No inal di ension range
General tolerance according to
DIN ISO 2768 ediu
up to 6 mm ± 0.1 mm
over 6 mm to 30 mm ± 0.2 mm
over 30 mm to 120 mm ± 0.3 mm
over 120 mm to 400 mm ± 0.5 mm
over 400 mm to 1000 mm ± 0.8 mm

2021-04
8
VisuNet FLX Panel
Product Description
3 Product Description
3.1 Overview
VisuNet FLX Panels consist of a display unit with touch screen in combination with a computing
unit. Various display sizes and configurable computing units like BPC3200-* and DMU3200-*
are available.
The VisuNet FLX panels are designed for use in hazardous locations ATEX/ ECEx Zone 2/22
and Class , , Div 2 and non-hazardous area applications. The different display sizes and
configuring options lead to the highest application flexibility. Due to a fully modular design, the
new platform, which is geared to the needs of the (petro-) chemical and pharmaceutical indus-
tries, the HM s can be configured to fit exactly and enable simple and fast customer adjust-
ments in the field.
Phar a suitable concept: The VisuNet FLX fulfills with its seal concept strict hygiene require-
ments. The gap free surface which is available with a typical surface roughness of 0.8 µm and
rounded edges of the bezel prevent accumulation of liquids or bacteria. Display and seals are
chemically resistant to typical cleaning agents.
n addition, individual solutions can also be created and manufactured at Pepperl+Fuchs' Solu-
tion Engineering Centers (SEC), which are located around the world.

VisuNet FLX Panel
Product Description
2021-04
9
VisuNet FLX Panel Co ponents
Figure 3.1
An extra system housing is available in which the VisuNet FLX panel can be easily installed in.
Refer to the VisuNet FLX system manual (RM-320S-*, PC-320S-* and DM-320S-*) for further
information.
No. Description
(1) Display Unit:
21.5" display, touch screen, hardened front glass, available with optical
bonding or non- optical bonding.
19" display, touch screen, hardened front glass with optical bonding
15" display, touch screen, hardened front glass with optical bonding
(2) RAM / Storage:
RAM available as 4 GB, 8 GB ans 16 GB DDR4-2133
Storage available as 32 GB, 256 GB and 512 GB, expandable with quali-
fied Pepperl+Fuchs components.
(3) Co puting Unit:
(TCU, PCU or DMU): processor, SSD and memory, Ex circuits, interface
modules
Note
For a description of the product model nomenclature, see the VisuNet FLX RM (RM-320P-*),
VisuNet FLX PC (PC-320P-*) or VisuNet FLX DM (DM-320P-*) product datasheets at
www.pepperl-fuchs.com.

2021-04
10
VisuNet FLX Panel
Product Description
3.2 Reference Docu ents
I portant Instructions and Manuals for Operating the Device
Docu entation Contents
You are here:
VisuNet FLX
Panel anual
•Panel installation
•nformation regarding 21.5", 19" and 15.6" DPU
•Connecting the BPC3200-* to the DPU3200-*
•Panel dimensions
•Cut out dimensions
VisuNet FLX
System manual
•System installation (mechanical, electrical)
•Power connection (DC and AC)
•nstalling peripherals
•Maintenance
BPC32000-*
manual
•Technical data and expanded technical data
•Electrical installation
•/O connection
•D P Switch positions when exchanging a computing unit
•B OS settings
DMU3200-*
manual
•Product Versions
•Technical data
• /O Connection
•Opening the device

VisuNet FLX Panel
Product Description
2021-04
11
3.3 Technical Data
PC-320P-* (Personal Co puter)
General specifications
Type Personal Computer
Hardware
Processor ntel® Core™ i5-7300U
ntel® Celeron™ 3965U
RAM 2x SO-D MM slots, supports up to 32 GB DDR4-2133 (one SO-D MM slot)
Configurable RAM options:
ndustrial temperature grade (temperature option A):
A: 1x 4 GB DDR4-2133 [Celeron]
B: 1x 8 GB DDR4-2133
C: 1x 16 GB DDR4-2133
Wide temperature grade (temperature option B):
K: 1x 4 GB DDR4-2133 [Celeron]
L: 1x 8 GB DDR4-2133
M: 1x 16 GB DDR4-2133
Mass storage Storage interface:
1x M.2 2242/2280 M Key, PC e + SATA 3
1x M.2 2242/2280 M Key, 2242/2280, SATA 3, supports Raid 0/1 [i5]
Configurable storage options:
ndustrial temperature grade (temperature option A):
A: 32-GB M.2 SATA 3 [Celeron]
D: 256-GB M.2 NVMe 1.3 (PC e 4x)
E: 512-GB M.2 NVMe 1.3 (PC e 4x)
Wide temperature grade (temperature option B):
K: 32-GB M.2 SATA 3 [Celeron]
P: 256-GB M.2 NVMe 1.3 (PC e 4x)
Q: 512-GB M.2 NVMe 1.3 (PC e 4x)
Software
Operating system Microsoft® Windows® 10 oT Enterprise 2019 LTSC (x64)

2021-04
12
VisuNet FLX Panel
Product Description
RM-320P-* (Re ote Monitor)
General specifications
Type RM-320P-*: Remote Monitor
Hardware
Processor ntel® Celeron™ 3965U
RAM Configurable RAM options:
A: 1x 4 GB DDR4-2133, industrial temperature grade [temperature class
A]
K: 1x 4 GB DDR4-2133, wide temperature grade
Mass storage Storage interface:
1x M.2 2242/2280 M Key, PC e + SATA 3
Configurable storage options:
A: 32-GB M.2 SATA 3, industrial temperature grade [temperature class A]
K: 32-GB M.2 SATA 3, wide temperature grade
Software
Operating system Pepperl+Fuchs VisuNet RM Shell 5 (based on Microsoft® Windows® 10
oT Enterprise 2019 LTSC (x64))

VisuNet FLX Panel
Product Description
2021-04
13
PC-320P-* (Personal Co puter) and RM-320P-* (Re ote Monitor)
Supply
nput current max. 3 A, max. 60 W
Refer to chapter 6.1.1 Power Li itations for further information.
Power consu ption
DC 24 V d. c. (20 ... 28 V d. c.) (SELV/PELV or class 2)
For connections designation refer to the VisuNet FLX manual.
Indicators/operating eans
Display
Type Liquid Crystal Display (LCD) with LED backlight
Screen diagonal Configurable display options:
22GT: 54.61 cm (21.5") [temperature class A]
22FC: 54.61 cm (21.5'')
(Display might react sluggishly below 0°C)
19SC: 48.26 cm (19")
15FC: 39.62 cm (15.6")
Resolution 22GT, 22FC, 15FC: 1920 x 1080 pixels (Full HD) Aspect Ratio (16:9)
19SC: 1280 x 1024 pixels (SXGA) Aspect Ratio (5:4)
Color depth 24 bit (16.7 M) color
Contrast Typically
22GT: 1000:1
22FC: 5000:1
19SC: 1000:1
15FC: 800:1
Brightness Configurable display options:
22GT: 250 cd/m2
22FC: 300 cd/m2
19SC: 450 cd/m2
15FC: 450 cd/m2
Reading angle 22GT: 178° in all directions
22FC, 19SC: horizontal: 170°, vertical: 160°
15FC: 170° in all directions
Life span 22GT: back lamp life: 30.000-hrs typical half life, at 25°C (77°F)
22FC, 19SC, 15FC: back lamp life: 50.000-hrs typical half life, at 25°C
(77°F)
Input devices
Touch screen Configurable Display Options: 10-finger multi-touch, glove-friendly
22GT: Capacitive touch, no optical bonding
22FC, 19SC, 15FC: Capacitive touch, optical bonding
Interface
nterface type 1 x DisplayPort 1.2 (DP++)
1 x mini DisplayPort 1.2 (DP++ w/ mono locking screw)
1 x Audio Line-out
2 x USB Ex i ports prepared for Pepperl+Fuchs intrinsically safe keyboard
2 x USB 3.1 Gen1 (5 Gbps) ports
1 x USB 2.0 port
2 x LAN ports (RJ45, 10/100/1000 Mbps)
2 x RS232/422/485 (B OS configurable) with 5V/12V to power peripherals
(1 x DB9 male + 1 x RJ45)

2021-04
14
VisuNet FLX Panel
Product Description
Directive confor ity
Electro agnetic co patibility
Directive
2014/30/EU
D N EN 55035:2018-04
Explosion protection
Directive
2014/34/EU
EN EC 60079-0:2018
EN EC 60079-7:2015/A1:2018
EN 60079-11:2012
EN 60079-31:2014
RoHS
Directive
2011/65/EU
(RoHS)
EN EC 63000:2018
A bient conditions
Operating tem-
perature
Temperature classes:
A: 0 … 45 °C (32 … 113 °F)
B: -20 … 55 °C (-4 … 131 °F) [with wide temperature grade RAM/storage
and optically bonded display unit]
Storage tempera-
ture
-20 ... 65 °C (-4 ... 149 °F)
Relative humidity max. relative humidity 93% at 40°C (non-condensing) according to
EN60068-2-78
Climatic condi-
tions
Passive cooling, no rotating parts
Altitude Operating altitude max. 2000 m
Shock resistance 18 shocks 15 g, 11 ms all axis, EC 60068-2-27
Vibration resis-
tance
10 ... 150 Hz, +/- 0.075 mm, 1 g, 10 cycles per axis according to EN60068-
2-6
Mechanical specifications
Degree of protec-
tion
Front side: P66
Back side: P20
Type 4X indoor
Material Front bezel: Stainless steel A S 304 (glass, silicone gasket)
Backside: Painted aluminum sheet metal
nstallation Panel mount (additional Mounting Kits available) installed in boundary wall,
in cabinet wall or special enclosure
Mass 22GT, 22FC and 19SC: approx. 8 kg
15FC: 5.4 kg
Dimensions 22 inches: 567 mm x 358 mm x 68 mm
19 inches: 485.7 mm x 410.5 mm x 68 mm
15 inches: 434 mm x 283.4 mm x 67 mm
For cut out dimensions refer to chapter 4.4 Mounting the Panel Into the
Enclosure.

VisuNet FLX Panel
Product Description
2021-04
15
DM-320P-* (Direct Monitor)
Data for application in connection with hazardous areas (pending)
EU-type exa ination certificate
Marking Certificate in preparation.
3 G Ex ec [ic] C T4 Gc
3 D Ex tc [ic] C T85°C Dc
International approvals (pending)
UL approval
Approved for Certificate in preparation.
Ordinary location
acc. UL 61010-1 and UL 61010-2-201
Hazardous location
Class , D V 2, GPS A-D
Class , D V 2, GPS F-G
Class
Class , ZN 2, C T4
Class , ZN 2, C T85°C
Class
IECEx approval
ECEx certificate Certificate in preparation.
ECEx marking Ex ec [ic] C T4 Gc
Ex tc [ic] C T85°C Dc
Standards EC 60079-0:2017
EC 60079-11:2011
EC 60079-31:2013
EC 60079-7:2015/A1:2017
General specifications
Type Direct Monitor
Supply
nput current max. 1.5 A, max. 30 W
Power consu ption
DC 24 V d. c. (20 ... 28 V d. c.) (SELV/PELV or class 2)
For connections designation refer to the VisuNet FLX manual.
Indicators/operating eans
Display
Type Liquid Crystal Display (LCD) with LED backlight
Screen diagonal Configurable display options:
22GT: 54.61 cm (21.5") [temperature class A]
22FC: 54.61 cm (21.5'')
(Display might react sluggishly below 0°C)
19SC: 48.26 cm (19")
15FC: 39.62 cm (15.6")

2021-04
16
VisuNet FLX Panel
Product Description
Resolution 22GT, 22FC, 15FC: 1920 x 1080 pixels (Full HD) Aspect Ratio (16:9)
19SC: 1280 x 1024 pixels (SXGA) Aspect Ratio (5:4)
Color depth 24 bit (16.7 M) color
Contrast Typically
22GT: 1000:1
22FC: 5000:1
19SC: 1000:1
15FC: 800:1
Brightness Configurable display options:
22GT: 250 cd/m2
22FC: 300 cd/m2
19SC: 450 cd/m2
15FC: 450 cd/m2
Reading angle 22GT: 178° in all directions
22FC, 19SC: horizontal: 170°, vertical: 160°
15FC: 170° in all directions
Life span 22FC, 19SC, 15FC: back lamp life: 50.000-hrs typical half life, at 25°C
(77°F)
22GT: back lamp life: 30.000-hrs typical half life, at 25°C (77°F)
Interface
nterface type 1x Power input w/ 3-pin terminal block
1x HDM
1x DV -
1x VGA
1x USB
1x 3.5-mm audio jack (Line-out)
1x OSD Menu w/ power button
Directive confor ity
Electro agnetic co patibility
Directive
2014/30/EU
D N EN 55035:2018-04
Explosion protection
Directive
2014/34/EU
EN EC 60079-0:2018
EN EC 60079-7:2015/A1:2018
EN 60079-11:2012
EN 60079-31:2014
RoHS
Directive
2011/65/EU
(RoHS)
EN EC 63000:2018
A bient conditions
Operating tem-
perature
Temperature classes:
A: 0 … 45 °C (32 … 113 °F)
B: -20 … 55 °C (-4 … 131 °F) [with wide temperature grade RAM/storage
and optically bonded display unit]
Storage tempera-
ture
-20 ... 65 °C (-4 ... 149 °F)
Indicators/operating eans

VisuNet FLX Panel
Product Description
2021-04
17
Relative humidity max. relative humidity 93% at 40°C (non-condensing) according to
EN60068-2-78
Climatic condi-
tions
Passive cooling, no rotating parts
Altitude Operating altitude max. 2000 m
Shock resistance 18 shocks 15 g, 11 ms all axis, EC 60068-2-27
Vibration resis-
tance
10 ... 150 Hz, +/- 0.075 mm, 1 g, 10 cycles per axis according to EN60068-
2-6
Mechanical specifications
Degree of protec-
tion
Front side: P66
Back side: P20
Type 4X indoor
Material Front bezel: Stainless steel A S 304 (glass, silicone gasket)
Backside: Painted aluminum sheet metal
nstallation Panel mount (additional Mounting Kits available) installed in boundary wall,
in cabinet wall or special enclosure
Mass 22GT, 22FC and 19SC: 6.5 kg
15FC: 4.4 kg
Dimensions 22 inches: 567 mm x 358 mm x 68 mm
19 inches: 485.7 mm x 410.5 mm x 68 mm
15 inches: 434 mm x 283.4 mm x 67 mm
For cut out dimensions refer to the panel mount manual.
Data for application in connection with hazardous areas (pending)
EU-type exa ination certificate
Marking Certificate in preparation.
3 G Ex ec [ic] C T4 Gc
3 D Ex tc [ic] C T85°C Dc
International approvals (pending)
UL approval
Approved for Certificate in preparation.
Ordinary location
acc. UL 61010-1 and UL 61010-2-201
Hazardous location
Class , D V 2, GPS A-D
Class , D V 2, GPS F-G
Class
Class , ZN 2, C T4
Class , ZN 2, C T85°C
Class
IECEx approval
ECEx certificate Certificate in preparation.
A bient conditions

2021-04
18
VisuNet FLX Panel
Product Description
Ther al Throttling
For the Celeron processor, CPU throttling via a thermal control circuit is used. Depending on
the system load and environmental operating temperature, the performance of the CPU may be
throttled.
ECEx marking Ex ec [ic] C T4 Gc
Ex tc [ic] C T85°C Dc
Standards EC 60079-0:2017
EC 60079-11:2011
EC 60079-31:2013
EC 60079-7:2015/A1:2017
International approvals (pending)
Note
For expanded technical data regarding e.g. storage capacity and reliability refer to the
BPC3200-* manual.
Note
Assess the system performance in context with the applications intended environmental
conditions, including operating temperature range.

VisuNet FLX Panel
Product Description
2021-04
19
3.4 Di ensions and Na eplates
Di ensions
Figure 3.2 21.5" dimensions
Figure 3.3 19" dimensions
Figure 3.4 15" dimensions
68 567
358
68
485.7
410.5
67 434
283.4

2021-04
20
VisuNet FLX Panel
Product Description
Na eplates and Labels
The following nameplates and labels are attached to the VisuNet FLX Panel:
Figure 3.5 Overview of the attached labels and nameplates
(1) Main label
Figure 3.6
Note
For further information on the System dimensions refer to the VisuNet FLX System manual.
This manual suits for next models
5
Table of contents
Popular Control Panel manuals by other brands

Honeywell
Honeywell NOTIFIER AM-8200 Programming manual

Konica Minolta
Konica Minolta ViZion DR+ 1417V2 Dealers Installation manual

SuddenLink
SuddenLink connectedhome user manual

Vivo
Vivo STAND-E-102A instruction manual

GE
GE Zenith Controls MX150 Operation and maintenance manual

DSC
DSC CFP-102 instruction manual