Thetorchboxexhaustmustbeinstalled,buttheRFgenerator
exhaustisoptional(seenoteinTable7*).
TheRFgeneratorexhaustventisusedfortheblowerthat
cools the system power supplies and ICP generator.
Werecommendusingtwo100-mm(4in.)exhausthoses
(forboththetorchboxexhaustventandRFgenerator
exhaustvent).TheNexION300ICP-MSissuppliedwith6m
(22ft.)of100-mm(4in.)flexibletubing.Thistubingpermits
the movement of the instrument without disconnecting the
ventsfromthelaboratorysystem.SeeTables6and7for
vent specifications.
Inoperation,theroughingpumpproduces1200-1500W
(4100-5100BTU/hr)ofheat.Theheatfromtheroughing
pump is released into the laboratory. Proper ventilation is
required to remove this heat from the room or any enclosure
in which the pump is situated. There must be a minimum of
15cm(6in.)clearancebetweentherearofthepumpand
anyverticalsurfaceaswellasaminimumof35cm(14in.)
clearance in the front. It should be located away from other
heat generating sources such as the liquid cooling system.
TheambientairtemperaturemustNOTexceed40°Catthe
roughing pump control electronics.
Theheatfromtheliquidcoolingsystem(heatexchangeror
refrigeratedchiller)isalsoreleasedintothelaboratoryduring
operation. The heat exchanger will produce a maximum of
2000W(6825BTU/hr)ofheat.Therefrigeratedchillerwill
produceamaximumof3000W(10,000BTU/hr)ofheat.
Proper ventilation is required to remove this heat from the
room or any enclosure in which the liquid cooling system
is situated. Adequate clearance should be allowed on the
front, sides, and rear of the unit for access to connections
and components. The front and rear vents of the unit must
beaminimumof61cm(2ft.)awayfromwallsorvertical
surfaces so air flow is not restricted. It should be installed at
7
least1.4meters(4ft.)awayfromanyheat-generating
sources such as the roughing pump or other instruments.
Proper ventilation is critical for the heat exchanger – its
ambient air temperature must never exceed 30 ˚C.
Venting System Recommendations
Theexhaustflowrateattheinstrument(theabilitytovent
thesystem)isdependentoncustomer-providedblower,the
duct length, material and the number of elbows or bends
used. If an excessively long duct system or a system with
many bends is used, a stronger blower may be necessary to
provide sufficient exhaust volume at the instrument. Smooth
stainless steel tubing should be used instead of flexible stain-
less steel tubing, where flexibility is not required, to reduce
system friction loss or “drag.” A length of smooth stainless
steelductinghas20-30%lessfrictionlossthanacomparable
lengthofflexibleducting.Whensmoothstainlesssteel
tubing is used, elbows must be used to turn corners. These
elbowsshouldturnatnomorethan45degreesbetween
straight sections to reduce friction losses, and the number
of elbows should be minimized.
Additional recommendations on the venting system include:
• Theductcasingandventingsystemshouldbemadeof
materialssuitablefortemperaturesashighas70˚Cand
be installed to meet local building code requirements.
• Locatetheblowerasclosetothedischargeoutletaspossible.
All joints on the discharge side should be airtight, especially if
toxic vapors are being carried.
• Equiptheoutletendofthesystemwithabackdraft
damper and take the necessary precautions to keep the
exhaust outlet away from open windows or inlet vents
and to extend it above the roof of the building for proper
dispersal of the exhaust.
• Equiptheexhaustendofthesystemwithanexhaust
stack to improve the overall efficiency of the system.
Table 7. Hose Diameter and Venting Capabilities.*
Hose Hose Diameter Heat Vented Outside Lab Watts (BTU/hr)
TorchBoxExhaust 100mm(4in.) 800(2720)
RFGeneratorExhaust 100mm(4in.) 1500(5100)
*IfonlytheTorchBoxexhausthoseisused,approximately1500W(5100BTU/hr)ofheatfromtheRFgeneratorexhaustisventedintothelab.
Anindependentroomairconditioner[3000W(10000BTU/hr)]isrecommendedtoremovethisadditionalheat.
Table 6. Instrument Exhaust Ventilation Requirements.
Required airflow Required air velocity Reference airflow Reference air velocity
measured with hose connected to NexION measured with hose disconnected from NexION
TorchBox
ExhaustPort 73–100ft3/min@0.5"H2O 836–1145ft/min@0.5"H2O 110–150cfm@0"H2O 1260–1719ft/min@0"H2O
(35–47L/sec@125Pa) (4.3–5.8m/sec@125Pa) (52–71L/sec@0Pa) (6.4–8.7m/sec@0Pa)
RFGenerator
ExhaustPort 150–160ft3/min@0"H2O 1719–1833ft/min@0"H2O 150–160ft3/min@0"H2O 1719–1833ft/min@0"H2O
(71–76L/sec@0Pa) (8.7–9.3m/sec@0Pa) (71–76L/sec@0Pa) (8.7–9.3m/sec@0Pa)