PESA RCP-48X User manual

Document No. 81-9059-0307-0 Rev. E
PESA Switching Systems
330A Wynn Drive
Huntsville, AL 35805
RCP-48X

Manual Updates:
06/17/94 Rev. A: Manual released for initial printing.
02-28-01 Rev. B: Not released - Agile conversion. GLT
02-28-01 Rev. C: Synchronized revision level with Agile per ECO CE00126. GLT
03-02-01 Rev. D: Deleted Printing Specification per ECO CE00113. GLT
03-16-01 Rev. E: Deleted bills of material, drawings, and schematice per ECO
CE00130. GLT

Sales Office
Service and
Ordering
Assistance
Ordering Assistance,
Service & Inquiries
PESA Switching Systems, Inc.
330A Wynn Drive
Huntsville, AL 35805
Main Numbers:
Tel: (256 726-9200
Fax: (256 726-9271
Service Department Numbers:
Tel: (256 726-9222
Fax: (256 726-9268
National Sales Office
PESA Switching Systems, Inc.
35 Pinelawn Road, Suite 99E
Melville, NY 11747
Tel: (800 328-1008
Fax: (516 845-5023

NOTE PESA reserves the right to change any information con-
tained in this manual without notice. Unauthorized copying,
modifications, distribution, or display is prohibited. All rights
reserved.
Please address all comments or suggestions concerning
this or other PESA manuals to
Publications Department
PESA Switching Systems, Inc.
330A Wynn Drive
untsville, Alabama 35805
(256) 726-9200 EXT. 145

Table of Contents
i
RCP–48X Control Panel
Section 1. INTRODUCTION
1.1 Manual Overview ...................................................................... 1.1
1.2 General Description .................................................................. 1.2
Figure 1–1 RCP–48X Front and Rear Views ...................... 1.2
1.3 System Specifications............................................................... 1.3
Section 2. INSTALLATION
2.1 Introduction ............................................................................... 2.1
2.2 Receipt Inspection .................................................................... 2.1
2.3 Location and Mounting ............................................................. 2.1
Figure 2–1 RCP–48X Chassis Installation.......................... 2.2
2.4 Polling Address ......................................................................... 2.2
Figure 2–2 DIP Switch Location ......................................... 2.3
2.5 Control Panel/Controller Interconnection .................................. 2.3
Figure 2–3 Typical Control Panel Interconnection .............. 2.3
2.6 Wiring the Control Panel Connector ......................................... 2.4
Figure 2–4 Wiring the Control Panel Connector ................. 2.4
2.7 Terminating Cable Runs ........................................................... 2.5
Figure 2–5 Terminating Cable Runs ................................... 2.5
2.8 Power Connections................................................................... 2.6
Figure 2–6 Typical Panel Power Supply ............................. 2.6
Section 3. OPERATION
3.1 Operations ................................................................................ 3.1
Introduction ......................................................................... 3.1
General ............................................................................... 3.1
Breakaway Operation ......................................................... 3.2
Operational Instructions ...................................................... 3.3

Table of Contents
ii
RCP–48X Control Panel
Section 4. FUNCTIONAL DESCRIPTION
4.1 Introductionl .............................................................................. 4.1
4.2 CPU Board................................................................................ 4.1
Power Supply...................................................................... 4.1
Microprocessor ................................................................... 4.1
Figure 4–1 Idealized Bus Cycle Timing Diagram ................ 4.2
Clock ................................................................................... 4.2
Reset .................................................................................. 4.3
Memory ............................................................................... 4.3
LED Driver Support............................................................. 4.3
RS-485 Communications .................................................... 4.4
I/O ....................................................................................... 4.4
Table 4–1 Decoder Addressing ......................................... 4.5
Miscellaneous ..................................................................... 4.5
4.3 Switchcard ................................................................................ 4.5
RCP–48X Switchcard ......................................................... 4.5
Switchcard ID...................................................................... 4.5
Keyboard Scan ................................................................... 4.6
Table 4–2 Keyboard Memory Map .................................... 4.6
LED Driver .......................................................................... 4.7
I/O Board Interface ............................................................. 4.7
Section 5. MAINTENANCE
5.1 General ..................................................................................... 5.1
5.2 Preventive Maintenance ........................................................... 5.1
5.3 Test Equipment......................................................................... 5.1
5.4 Corrective Maintenance ............................................................ 5.1
Factory Repair Service ....................................................... 5.2
Adjustment/Alignment ......................................................... 5.2
Troubleshooting .................................................................. 5.2

INTRODUCTIO
1
Section 1
page 1.1
RCP-48X Introduction
Section 1, INTRODUCTION, summarizes the manual, describes
the RCP–48X, presents a list of terms, and provides the panel
specifications.
Section 2, INSTALLATION, provides installation and setup
instructions.
Section 3, OPERATION, describes operation procedures.
Section 4, FUNCTIONAL DESCRIPTIONS, presents an in-
depth description of each RCP–48X component.
Section 5, MAINTENANCE, explains procedures for
maintenance.
This manual provides detailed instructions for installing and operating the
PESA RCP–48X. This manual is divided into five sections as shown.
1.1 Manual Overview
INTRODUCTIO
1
INSTALLATIO
N
2
OPERATION
3
FUNCTIONAL
4
DESCRIPTION
MAINTENANC
E
5

INTRODUCTIO
1
Section 1
RCP-48X
page 1.2
Introduction
1.2 General Description
The RCP–48X is designed to provide an economical solution for installa-
tions requiring fast, intuitive operation. It is a button-per-source or destina-
tion panel featuring direct take operation for up to 16 levels of control of a
router destination. This panel is recommended for applications requiring
minimum keystrokes and a limited number of sources for a limited number
destinations. The RCP-48X can access one or more router destinations.
There are two control pushbuttons on the right. One allows the operator to
Protect or Lock the assigned destination while the other allows the opera-
tor to select an individual Level(s) to be controlled or display the panel
address.
This panel comes packaged in a standard 19 inch, one rack unit (1RU)
chassis requiring only 1 1/2 inches of depth, making it suitable for tight
locations. The unit is powered by a 7.5VDC Plug-in-the-Wall type power
pack and communicates with the System Controller via a Standard RS485
Interface.
Addr
Level
Lock
Prot
PESA
CONTROL PORT
POWER
IN
ADDRESS
1
0CONTRAST
BRIGHTNESS
Figure 1–1 RCP–48X Front and Rear Views

INTRODUCTIO
1
Section 1
page 1.3
RCP-48X Introduction
1.3 Specifications
GENERAL
Mounting Standard 19" Rack
Pushbuttons LED Illuminated
INPUT
Input Type RS485
POWER
Voltage Requirements +7.5 VDC @ 800 mA
MECHANICAL
One Rack Unit 19"W x 1 1/2"D x 1 3/4"H
(482.6mmx38.1mmx44.45mm)
ENVIRONMENTAL
Temperature 0°C to 40°C
Humidity 20% to 90%
Non-Condensing

INTRODUCTIO
1
Section 1
RCP-48X
page 1.4
Introduction

INSTALLATIO
N
2
Section 2
page 2.1
RCP-48X Installation
2.1 Introduction
This section details RCP-48X installation procedures. The following topics
are discussed:
• Receipt Inspection
• Location and Mounting
• Polling Address
• Control Panel/Controller Interconnection
• Power connections
2.2 Receipt Inspection
The RCP–48X was inspected and tested prior to leaving the PESA fac-
tory. Upon receipt, please inspect the unit for shipping damage. If damage
is detected, notify the carrier immediately and hold all packing material for
inspection. If assistance is required, please contact PESA Customer
Service at the telephone number listed in the front of this manual.
After unpacking, compare all parts received against the packing list. If the
unit is undamaged and all components have been received, proceed with
installation.
2.3 Location and Mounting
The RCP-48X has been designed to fit in a standard E.I.A. 19" equipment
rack and uses 1 rack unit of space (1 3/4"). An area should be selected
where temperature does not exceed 40°C inside the equipment rack, and
where air can circulate freely. The unit should be mounted in an area
convenient to control and power connections. Sufficient space must be
provided behind the rack to allow for the control and power cables. All
mounting holes should be utilized and hardware tightened securely. All
cables should be strained relieved and secured to racks or other support-
ing structures. Failure to provide adequate cable support can result in
cables separating from connectors. If cable runs are to be stored under an
elevated floor, they should be tied to the racks as a guide. If cables are
run along the floor, do not allow them to lay in the work area behind the
racks. Stepping or tripping on the cables may result in connections being
pulled free or wire breakage inside the insulation.

Section 2
INSTALLATIO
N
2
page 2.2
RCP-48X Installation
Figure 2–1 illustrates chassis installation.
To install the RCP–48X chassis follow these steps:
1. Align the chassis with the slotted opening in the rack.
2. Install the bottom screws first.
3. Install the two top screws
4. Tighten all four screws securely.
Figure 2–1 RCP–48X Chassis Installation
Location and Mounting Continued:
2.4 Polling Address
For the controller to identify a particular control panel, a specific device
number or polling address must be assigned to each panel. Valid polling
addresses are in the range of 1 to 128. Systems requiring more than 128
panels are possible with enhanced controllers, refer to your Pesa Sales
Representative for details. The appropriate binary number is entered into
the control panel by setting a 10-position DIP switch to the binary number.
The DIP switch is located on the remote CPU board and is accessible
from the rear of the unit. The panel address is normally assigned and
entered at the factory if the panel is purchased as part of a system and a
design guide has been completed by the user. If the panel is purchased
separately, the user may be required to set the panel address.
Example: To select polling address 21, set switches 6, 8, and 10 in the
"ON" or "1" position. See Figure 2–2.

INSTALLATIO
N
2
Section 2
page 2.3
RCP-48X Installation
2.4 Polling Address (Device Number) Continued:
2.5 Control Panel/Controller Interconnection
Each panel has a single 3-pin MTA connector located on the rear panel.
Control panels are daisy chained to a port on the rear of the Controller.
Use shielded twisted pair cable. See Figure 2–3.
PS
PS
CP = Control Panel
PS PS
(TWISTED PAIR) - TO CP'S
(TWISTED PAIR) - TO CP'S
(TWISTED PAIR) - TO CP'S
CONTROLLER
Control
Panel
Control
Panel Control
Panel
Control
Panel
(TWISTED PAIR)
TERMINATE AT THE
THE END OF THE RUN
(120 OHM RESISTOR)
Figure 2–3 Typical Control Panel Controller Interconnection
Figure 2–2 DIP Switch Location

Section 2
INSTALLATIO
N
2
page 2.4
RCP-48X Installation
Figure 2–4 Wiring the Control Panel Connector
Should an additional control panel be added to your system, it will be
necessary to wire the connector using shielded twisted pair cable and a 3-
pin MTA connector. See Figure 2–4.
1. Remove approximately 1 1/2" of insulating jacket from each of the two
wires.
2. Remove approximately 1/2" of wire insulation from the black and red
wires.
3. Twist together and insert the two black wire ends into positon 1.
Crimp down using a screw driver.
4. Twist together and insert the two shield wires into position 2. Crimp
down using a screwdriver.
5. Twist together and insert the two red wire ends into position 3.
Crimp down using a screwdriver.
2.6 Wiring the Control Panel Connector

INSTALLATIO
N
2
Section 2
page 2.5
RCP-48X Installation
Figure 2–5 Terminating Cable Runs
2.7 Terminating Cable Runs
Each cable run should be terminated at the end of the run with a 120ý,
1/4 watt 5% resistor. The cable is terminated internally at the controller.
See Figure 2–5.
1. Uncrimp the black and red leads in position 1 and 3.
2. Insert the resistor ends into position 1 and position 3 along with the
black and red leads.
3. Crimp down using a screwdriver.
4. The shield wire remains in position 2.

Section 2
INSTALLATIO
N
2
page 2.6
RCP-48X Installation
2.8 Power Connections
Power for the RCP-48X is supplied by an external 7.5 Vdc, 800 mA power
supply.
Remove the Power Supply from the box it was shipped in and check to
insure that no damage has occurred in shipping. Verify that the Power
Supply is rated for the proper AC voltage (i.e. 115 VAC or 230 VAC)
before connection to the AC voltage. The power connector can now be
plugged into the POWER IN position on the RCP–48X. The Power Pack
will immediately power the unit upon connections to AC Voltage. See
Figure 2–6.
Figure 2–6 Typical Panel Power Supply

OPERATION
3
page 3.1
RCP–48X Section 3
Operations
3.1 Operations of the RCP–48X
Introduction
The RCP–48X is controlled by the RC5500 Controller. Operations of the
RCP–48X require that it be configured at the controller and have the
appropriate polling address assigned. Connections and power up proce-
dures should be performed on each panel controlled.
General
All RCP–48X panels in a routing switcher system are custom configured
at the factory prior to shipment. The information needed to configure the
panels comes from the System Design Guide filled out by the customer.

OPERATION
3
page 3.2
Section 3
RCP–48X Operations
Breakaway operation allows you to select an input to be switched to an
output on one or more specific levels. Assumptions: Panel is currently in
Direct Take mode (default mode) and no level has been selected for break-
away (Level/Disp. LED is not illuminated or blinking).
To Make a Breakaway Switch: Results:
Depress Level/Address Key Level/Address Key lights.
Panel enters Level Select Mode.
Data Keys represent Levels.
Depress Data Key associated Data Key(s) selected light to show
with level(s) you wish to breakaway level selection(s).
Depress Level/Address Key again Level/Address key blinks.
Panel returns to Direct Take Mode but
with Level(s) selected for breakaway.
Data Key whose associated input
matches the current status on the
selected level(s) will be illuminated.
Depress the Data Key associated The destination controlled by the
with the input you desire on the panel will be switched to the input
level(s) selected assigned to the Data Key pressed for
each level selected.
To Return to Follow Operation: Results:
Depress the Level/Address Key Level/Address Key lights.
again Panel enters Level Select Mode again.
Data Keys associated with currently
selected level(s) light.
Depress Data Key(s) currently lit Data Key LEDs are extinguished and
associated levels are no longer
selected for breakaway operation.
Depress Level/Address Key again Level/Address Key LED is extinguished
Panel returns to Direct Take Mode but
with no levels broken away (Follow
operation). Data Key whose source
matches the current status is
illuminated.
Breakaway Operation

OPERATION
3
page 3.3
RCP–48X Operations Section 3
Data Keys: 48 Data Keys are located towards the left of the panel. Data Keys are associated with
sources or destinations in Direct Take mode and levels in the Level Select mode. The source/destination
assigned to each Data Key is configurable from the controller.
Function Keys: Two function keys are located to the far right of the panel: Protect / Lock and Level
/ Display Address. Each function key works as a toggle; the primary function is listed first, followed by
the secondary function. NOTE: The primary function is executed when the key is held down less
than 2 seconds. The secondary function is executed when the key is held down more than 2
seconds.
The RCP–48X has 2 Modes of Operation:
Direct Take - Selects sources to be switched to the destination controlled by the panel by depress-
ing associated Data Keys. Switch requests are sent immediately. Direct Take is the default mode;
deselecting the Level Select mode will always return you to the Direct Take mode. The Level/
Address Key will not be illuminated if the panel is in Follow or blinking if you have selected
Breakaway level(s).
Level Select - Selects which levels are to be affected when selecting switches in Direct Take mode.
Enter the Level Select mode by depressing the Level/Address key for less than 2 seconds. The
Levels/Address key is illuminated in this mode of operation.
Default Status Level Status: Panel will always display the status of the Default Status
Level.
Default Destination Group: Destination group to be controlled by the panel on panel boot-up.
Default Status Level: The level that will be statused when panel is in Follow operation and status
is not determined by the Group Status (refer to the preceding Status Method description).
Level List: List of levels to be controlled by the panel. Any level not in the assigned Level List will
not be accessible to or affected by panel operations.
Key Assignment List: List containing the assignment of source/destination groups to each of the
Data Keys.
PANEL CONFIGURATION:
Address: Decimal number from 1 to 128 which is used to distinguish each panel on the panel
communications bus. Address must match the dip switch setting on the rear of the panel. Systems
requiring more than 128 panels are possible with enhanced controllers: refer to your Pesa Sales
Representative for details.
Panel Name: Any 8 alphanumeric characters. Currently used only by the controller configuration
program to provide a user-friendly method of referring to each panel.
Priority: Choice of 3 priorities: Master, Supervisory, or Non-Supervisory. Priorities are used when
panel attempts to set or clear a destination Protect/Lock. Only the panel which set a Protect/Lock, or
someone of higher priority can unlock a destination. The default setting is Non-Supervisory.
Status Method: The panel displays status differently based on whether the panel is set for Follow
(changing all levels assigned to panel) or Breakaway (changing only selected levels) operation. In
addition, you may select between 2 methods of displaying status when in Follow (NOTE: these
methods only apply when the panel is set for Follow operation):
Group Status: Panel will display status based on the Source Group which changed the cur-
rent destination. If the panel receives status due to a Breakaway change request, or due to a
change made elsewhere in the system, the panel will display the status of the Default Status
Level (refer to the Controller Operations Manual for more details).

OPERATION
3
page 3.4
RCP–48X Operations Section 3
Breakaway Statusing
LED Illuminated Solid (not blinking)
- The current status matches the source assigned to the Data
Key for the highest priority level selected (level 1 is highest priority) and the source(s) assigned to
the Data Key for other levels selected either match the current status or are not configured.
LED Blinking
- The current status matches the source assigned to the Data Key for the highest
priority level selected (level 1 is the highest priority) but the source(s) assigned to the Data Key for at
least one other selected level does not match the current status.
No LED Illuminated
- The current status does not match the source assigned to any Data Key on
the highest priority level selected (level 1 is the highest priority).
STATUSING:
Status by Group Status
LED Illuminated Solid (not blinking)
- The current status matches the source(s) assigned to the
Data Key.
LED Blinking
- The current status matches the source(s) assigned to the Data Key on some,
but
not all
, levels.
No LED Illuminated
- The current status does not match the source(s) assigned to any Data Key.
Status by Default Status Level
LED Illuminated Solid (not blinking)
- The current status matches the source assigned to the Data
Key for the default status level and the source(s) assigned to the Data Key for other levels either
match the status on the default status level or are not configured.
LED Blinking
- The current status matches the source assigned to the Data Key for the default
status level and the source(s) assigned to the Data Key for at least one other level does not match
the status on the default status level.
No LED Illuminated
- The current status does not match the source assigned to any Data Key on
the default status level.
NOTE: If the destination group being controlled by the panel matches a Destination Data Key, the
Destination Data Key's LED will be illuminated.
Table of contents
Other PESA Switch manuals