11
PM-20
Operating Instructions (Cont’d)
Technical Note 32 explains the use of GUARD (G) terminal in order to minimize the effect of stray re-
sistances. When measurement is carried out between parts where none of them is grounded, (like between
high-side and low-side windings of a transformer), GUARD terminal must be connected to ground in order
to fix the apparatus potential. At any time a measurement is performed, either the -R or GUARD termi-
nals must be connected to ground but never both simultaneously. If none of these terminals are con-
nected to ground, the insulation tester can reach a high potential that may result in an unstable, non-reliable
reading. If both terminals are simultaneously connected to ground, there is a short-circuit between
them, and consequently the insulation tester will measure with error.
NOTE: The insulation tester is unable to generate test voltage while it is connected to mains. The power
cable has to be unplugged from mains prior to pressing the Start button.
4. Turn On the apparatus by pressing the ON / OFF key. The ON led begins to brighten.
5. Press the Start key. The high-voltage generator starts operating and the corresponding indicator light
turns on at the front panel. The meter pointer will indicate the value of the unknown resistance. If the ele-
ment to be measured is strongly capacitive, it will initially indicate a low resistance value that will be grad-
ually increased while the charging of that capacitance takes place. The instrument will always begin in the
scale A.
6. When the measured resistance exceeds the maximum value in range A, press range Bkey, and if the
value is not achieved, press keys of ranges Cor C x 10, as required.
7. Always remember to multiply the reading by the factor stated in the following table, depending on selected
test voltage.
8. When key C x 10 is used, reading will be carried out in range Cand will be multiplied by 10, in addition to
the factor corresponding to the test voltage.
9. When you press the Stop key, the insulation tester will start discharging the potentials accumulated in the
unit’s internal capacitances and in those of the element under test as well. When this discharging process
is over (up to 60 seconds after turn off), the High voltage will turn off automatically. The test leads may
be disconnected. To finish measurement press On/Off switch.