Phoenix vantage PRT-PCI-IO-R-16 User manual

75 Discovery Way • Acton, MA 01720 •Tel (978) 795-1285 •Fax (978) 795-1111 • www.phoenixcontrols.com
©2018 Phoenix Controls. Specifications subject to change without notice. Rev. 05/2018 MKT-0431 MPC-2355
PCI I/O MODULE
Compliance
• UL916
• C-UL, CE EN 61326-1:2013
• RCM
•WEEE
• RoHS2, China ROHS
•FCC
This device complies with part 15 of the FCC Rules. Operation
is subject to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, includ-
ing interference that may cause undesired operation.
• EU Contact Address:
Honeywell GmbH
Boeblinger Str. 17
71101 Schoenaich
Germany
•REACH
• Open Energy Management Class 2
IO-R-34 Module
The PCI I/O Module is designed for remote monitoring and
control applications that enables end-to-end automation and
device-to-enterprise integration. The I/O Module allows a
PCI8000 to interface directly with simple non-intelligent inputs
and outputs remotely located up to 4,000 feet away.
Connectivity is established via an industry-standard RS 485
communications bus. Multiple I/O Modules can be utilized
with a single PCI8000, providing 250+ I/O points on that one
device.
FEATURES
• The 34-point module provides 16 Universal Inputs, 10 Relay
Outputs, 8 Analog Outputs, and can power up to 4 16-point
modules.
• The 16-point module provides 8 Universal Inputs, 4 Relay
Outputs, 4 Analog Outputs, and is powered from a 34-point
module, or 15 Vdc supply.
• PCI I/O Modules support mounting on EN50022 standard
7.5mm x 35mm DIN rails.
SPECIFICATIONS
Dimensions
• 16-point Module — 3.25" x 4.5" x 2.4" (82.5 x 116 x 61mm)
• 34-point Module — 6.8" x 4.5" x 2.4" (162 x 116 x 61 mm)
Approximate Weight
• 16-point Module — 7.7 oz (0.22 kg)
• 34-point Module — 15.2 oz (0.43 kg)
Power
• 34-Point Module: 24 Vac@28 VA minimum (includes a maximum four 16-
point modules). Dedicated UL listed Class 2 Transformer, 50/60 Hz (can
be shared with PCI8000).
• 16-Point Module: 15 Vdc @ 0.133 A (2W) external 3rd party power supply
or Phoenix Controls WPS420 DC Power Supply.
Operating System
• Niagara 4 – Requires Niagara 4.3 or later
• Niagara AX – Requires Niagara 3.8u3 or later
Maximum Expansion per PCI8000
See I/O Module Combinations and Power Options table on page 8.
Communications
RS485
RS485/NRIO Unit Loads
These components each exert the following unit load on the RS485 network:
• 16-point module = 1/4
• 34-point module = 1/4
Operating Temperature
-4 – 140°F (-20 – 60°C)
Storage temperature
-40 – 185°F (-40 – 85°C)
Humidity
5%–95%, Non-condensing
TABLE OF CONTENTS
Ordering Guide ........................................................ 2
Inputs/Outputs......................................................... 2
Applications.............................................................. 2
Dimensions/Installation............................................ 3
Wiring...................................................................... 5
Power Backup........................................................... 9
RS485 Communications .......................................... 9
Recommended Cables ............................................ 11

2 PCI I/O MODULE MKT-0431 MPC-2355 ©2018 Phoenix Controls. Specifications subject to change without notice. Rev. 05/2018
ORDERING GUIDE
INPUTS AND OUTPUTS
I/O modules offer a wide variety of input configurations which are jumper selectable and software configurable. Each
model offers different quantities of outputs to suit the specific application.
APPLICATIONS
The Phoenix Controls PCI I/O Module is a programmable input/output module that can be used as:
• A standalone controller
Physical sensors and switches may be connected to the PCI I/O Module, which then performs the desired control by using built-
in functions (see section below) to switch or modulate PCI I/O Module outputs.
• An input/output (I/O) expansion module
Physical sensors, switches and actuators may be connected to the PCI I/O Module and their values passed across the PCI8000 to
valve controllers on the room-level network1for use in their control sequences. Data from the PCI I/O Module may also be
passed across the building-level network to the BMS for monitoring purposes.
Part Number Description
PRT-PCI-IO-R-16 16 point I/O module (powered from PRT-PCI-IO-R-34, or 15 Vdc)
PRT-PCI-IO-R-34 34 point I/O module (powered from 24 Vac)
Model Number Universal Inputs Digital Outputs
(Form A Relays) Analog Outputs
I-OR-16844
I-OR-34 16 10 8
Universal Inputs (software configurable)
Input Types
• Voltage 0 to 10 Vdc (input impedance >5K )
• Current 0 to 20 mA requires an external 499 resistor wired in parallel
• Digital Dry contact: 500 ms minimum On/Off
• Pulse Dry contact: 25 ms minimum On/Off; Frequency up to 20 Hz with a 50% duty cycle
Resistors
• Thermistor 10K Type 3 (10K @ 77 °F/25 °C); Range -40 °F to 302 °F (-40 °C to 150 °C) standard or custom tabular
thermistor inputs
• Potentiometer 0 to 100K
Outputs
•Digital • Form-A relay contacts for On/Off control
• 24 Vac/dc at 0.5 A maximum
• Includes MOV (Metal Oxide Varistor) outputs to support inductive-type loads
• Analog • 0-10 Vdc
• Minimum resistance 2500 for 0 to 10 Vdc
• 4 mA maximum

©2018 Phoenix Controls. Specifications subject to change without notice. Rev. 05/2018 MKT-0431 MPC-2355 PCI I/O MODULE 3
• A controller integrated into the Celeris, Theris or Traccel system
Data may be passed, through the PCI8000, between valve mounted controllers on the room-level network1and the PCI I/O
Modules on their BACnet network to supplement the control functions of either device. An example might be interlocking door
locks between an anteroom and a space under control so that doors may not be opened until the pressure stabilizes or a certain
number of air changes have occurred.
1. LON = Celeris, Traccel, or Theris; BACnet = Traccel or Theris.
The PCI I/O Module can also be used to implement virtually any room-level control sequence that relies on inputs
from physical sensors, switches or network based variables to develop the desired control output, function or interlock.
Typical control applications include lighting, temperature (spaces adjacent to controlled spaces), and access.
DIMENSIONS AND INSTALLATION
Dimensions: 16-Point Module

4 PCI I/O MODULE MKT-0431 MPC-2355 ©2018 Phoenix Controls. Specifications subject to change without notice. Rev. 05/2018
Dimensions 34-Point Module
Installation
1 Choose a location where the operating conditions may be maintained within the specified environmental limits:
• The device is not subject to shock and vibration.
• Cable lengths are kept to a minimum.
• The device is protected from dripping or spraying liquids, airborne dust and metallic particles.
2. When mounting the device:
• Mount vertically with the ventilation slots on top.
• Mount on a smooth, flat surface using 35mm DIN rail mounting screws.
• Allow two-inch clearance on all sides for proper ventilation, routing of cables.

©2018 Phoenix Controls. Specifications subject to change without notice. Rev. 05/2018 MKT-0431 MPC-2355 PCI I/O MODULE 5
DIN Rail Mounting
IO-R-16 Tab Mounting Dimensions

6 PCI I/O MODULE MKT-0431 MPC-2355 ©2018 Phoenix Controls. Specifications subject to change without notice. Rev. 05/2018
IO-R-34 Tab Mounting Dimensions
WIRING
All wiring connections are via terminal blocks on the base plate that accommodate wire sizes from 22 to 12 AWG (0.14
to 2.5 mm). Multiple conductors may be placed under one terminal, providing the cumulative diameter does not exceed
0.1" (2.5 mm).
U1 0V U2 U3 0V U4 U5 0V U6 U7 0V U8
DIGITAL
UNIVERSAL INPUTS(U1-8)
IO-R-16
-P
+P
RS485 -
RS485 +
RS485 S
- P
+ P
RS485 -
RS485 +
RS485 S
OUTPUTS(D1-4)
D1 1C2 D2 D3 3C4 D4 A01 0V A02 A03 0V A04
ANALOG
OUTPUTS(A01-4)
U1 0V U2 U3 0V U4 U5 0V U6 U7 0V U8 U9 0V U10 U11 0V U12 U13 0V U14 U15 0V U16 24VAC
D1 1C2 D2 D3 3C4 D4 D5 5C6 D6 D7 7C8 D8 A01 0V A02 A03 0V A04 A05 0V A06 A07 0V A08
D9 9C10 D10
ANALOG OUTPUTS(A01-8)DIGITAL OUTPUTS (D1-D10)
UNIVERSAL INPUTS(U1-16)
IO-R-34
-P
+P
RS485 -
RS485 +
RS485 S
- P
+ P
RS485 -
RS485 +
RS485 S

©2018 Phoenix Controls. Specifications subject to change without notice. Rev. 05/2018 MKT-0431 MPC-2355 PCI I/O MODULE 7
Phoenix Controls Wiring Recommendations
• All circuits must conform to the requirements of an NEC Class 2 (dry) circuit.
• Use multiple transformers instead of larger transformers when more than 100 VA is required.
• Each pressurization zone should have either a dedicated single-phase primary circuit, or a secondary circuit discon-
nect
• Use stranded wire for ease of installation.
• Follow good wiring practices:
• Locate cables away from sources of electrical interference (EMI/RFI).
• Do not run signal or communication cable in the same conduit or wire way as power cables.
• If signal cable must cross power cables place these at a 90-degree angle.
• Shield or drain wires, if required, should be wrapped with insulating tape to prevent contact with exposed
conductors or contacts.
• Maintain a consistent color code or polarity all the way through the wiring system.
• Power supply and signal isolation on I/O devices vary from manufacturer to manufacturer. Verify the wiring device
manufacturer’s recommendations for isolating power and signal common connections and maintain polarity.
• Local and national electrical codes take precedence.
• Strip 0.25" (6.4 mm) of insulation from each conductor, twist the strands, insert the conductor fully into the terminal
block, and tighten the terminal.
• Test the wire connection by pulling on each conductor.
•See
Phoenix Recommended Cables for approved cable manufacturers and wire types.
Ground Wire
An earth ground spade lug (0.187") is provided on the base of the IO-R-34 for connection to earth ground. For
maximum protection from electrostatic discharge or other forms of EMI, connect each earth ground using #16 AWG or
larger wire. Keep these wires as short as possible. The following figure shows the location of the IO-R-34 earth
grounding wire.

8 PCI I/O MODULE MKT-0431 MPC-2355 ©2018 Phoenix Controls. Specifications subject to change without notice. Rev. 05/2018
I/O Module Combinations and Power Options
The following table shows possible module combinations and their power sources. For example, Option 2 includes a
total of fourteen IO-R-16s and one IO-R-34. Four of the IO-R-16s are powered by the IO-R-34; the remaining ten IO-
R-16s must be powered by an external source.
Power Wiring: IO-R-34
The IO-R-34 can be powered by wiring to a dedicated Class 2, 24 V transformer, or to a 24 Vdc power source. The IO-
R-34 can share transformer power with a PCI8000.
• If powering an IO-R-34 from a 24 V transformer other than a PCI8000, do not power other equipment from the
same transformer or conducted noise may result. And do not ground either side of the transformer’s 24 V secondary.
• Do not connect two or more IO-R-34 modules together. Connecting IO-R-34 modules directly to each other may
allow for hardware configurations that lead to equipment damage.
• Do not apply power until all other wiring is completed.
The following figure shows power wiring to a 24 Vac/Vdc power source. Note the position of the power connector at
the lower corner of the unit. Unplug the connector from the module and install wire connections to the connector as
shown.
Combinations Module Maximum Number
of Modules
Number Powered by
IO-R-34s
Powered by
External Supply
Option 1
IO-R-16 16 0 16
IO-R-34 0 — —
Option 2
IO-R-16 14 410
IO-R-34 1 — —
Option 3
IO-R-16 12 8 4
IO-R-34 2 — —
Option 4
IO-R-16 10 10 0
IO-R-34 3 — —
Option 5
IO-R-16 8 8 0
IO-R-34 4 — —
Option 6
IO-R-16 660
IO-R-34 5 — —
Option 7
IO-R-16 4 4 0
IO-R-34 6 — —
Option 8
IO-R-16 220
IO-R-34 7 — —
Option 9
IO-R-16 0 0 0
IO-R-34 8 — —

©2018 Phoenix Controls. Specifications subject to change without notice. Rev. 05/2018 MKT-0431 MPC-2355 PCI I/O MODULE 9
Power Wiring: IO-R-16
Typical power for an IO-R-16 is provided through the 5-pin connector using 15 Vdc from an IO-R-34, which can
support up to four IO-R-16 modules. Power for the IO-R-16 can be taken directly from the IO-R-34 by connecting
modules together as shown in the previous illustration.
In other cases, the IO-R-16 may be remote mounted from the IO-R-34 module. The maximum allowable voltage drop
due to wiring is 1.5 Vdc. The maximum draw of an IO-R-16 module using four relay outputs is 0.133A/2.00W. If the
IO-R-16 module is remote mounted from an IO-R-34, use the following table for the recommended voltage and wire
gauge.
For an example, consider a system where two IO-R-16 modules are mounted remotely in a location 500 feet (152m)
away. The worst case amps used by each remote IO-R-16 is 0.133 A. Looking at the table above, in the 0.25 A column,
a 16 AWG paired cable drops 0.20 V per 100 feet, meaning a 500 foot run would drop 1 V. This would be a better
choice than an 18 AWG paired cable, which would drop 1.6 V, exceeding the 1.5 V maximum allowable drop.
The IO-R-16 may also be powered by a Phoenix Controls WPS420 or a 3rd party 13.5 - 15.75 Vdc power supply (±4%
regulation) wired to the P+ and P- terminals of an IO-R-16 module 5-position connector. See the IO-R-16 Installation
Guide.
Voltage Drop Per 100 Feet Run (30m) of Paired Wire
Gauge Load Current
(AWG) 0.10A 0.25A 05A 1.0A 1.5A 2.0A 4.0A
10 0.020 0.05 0.10 0.20 0.30 0.40 0.80
12 0.032 0.08 0.16 0.32 0.48 0.64 1.27
14 0.050 0.13 0.25 0.50 0.75 1.01 2.02
16 0.080 0.20 0.40 0.80 1.20 1.60 3.20
18 0.127 0.32 0.64 1.27 1.91 2.54 5.08
20 0.202 0.50 1.01 2.02 3.03 4.03 8.07
22 0.320 0.80 1.60 3.20 4.80 6.40 12.81

10 PCI I/O MODULE MKT-0431 MPC-2355 ©2018 Phoenix Controls. Specifications subject to change without notice. Rev. 05/2018
IMPORTANT: IO-R-16 and IO-R-34 Power Backup
Typical power for an IO-R-16 module is provided by IO-R-34. UPS backup power to the IO-R-16 and IO-R-34 is
recommended to prevent the following possible issues:
• Load cycling from I/O relays dropping out.
• Totalized counts zeroed out.
• History (logging) entries for associated I/O points are down and NRIO device down alarms.
• Interruption of I/O firmware upgrade may cause module to be inoperable.
Default settings for AOs and DOs can be set in case of power outage or communication loss. See the Niagara NRIO
Drive Guide for details.
15VDC Power Options (UPS or Battery Backup recommended) for IO-R-16
RS485 Communications
RS485 communications from the PCI8000 controller to each I/O module, or between an assembly of modules, requires
a continuous daisy-chain wiring topology using a shielded, twisted-pair cable using 5-position end connectors.
Using shielded 18-22 AWG wiring (refer to TIA-EIA-485 standard), wire in a continuous multi-drop: positive to
positive, negative to negative, shield to shield. Connect the shield wire (reference ground) to earth ground at one end
only, such as at the PCI8000. See the PCI8000 Product Data Sheet (MKT-0430) for the correct RS485 bias settings.
Daisy Chain Wiring
Connect S terminal wiring as shown in the following illustrations or communication errors may result. The S terminal
serves as a reference ground between isolated RS-485 ports on the PCI8000 and IO-R-16 and IO-R-34 modules.
U1 0V U2 U3 0V U4 U5 0V U6 U7 0V U8
DIGITAL
UNIVERSAL INPUTS(U1-8)
-P
+P
RS485 -
RS485 +
RS485 S
- P
+ P
RS485 -
RS485 +
RS485 S
OUTPUTS(D1-4)
D1 1C2 D2 D3 3C4 D4 A01 0V A02 A03 0V A04
ANALOG
OUTPUTS(A01-4)
+15VDC
GND
-15VDC
WPS420
L1/24V
PGND
L2/24V
RED
BLK
RED
BLK
3rd Party Power Supply
+15VDC
GND
RED
BLK
RECTIFIER OUTPUT
BATTERY
AC LINE
BATTERY
TRANSFORMER
(13.5-15.75 VDC)
(120 VAC TYPICAL)
OR
24VAC +/-10%
INPUT
NOTE: Not shown is RS485 Communication
wiring, on the bottom 3 positions of the
5-position connector plug.
Single pair cable from power source
to IO-R-16 enclsoure (P-, P+).
IO-R-16
-P
+P
RS485 -
RS485 +
RS485 S
- P
+ P
RS485 -
RS485 +
RS485 S
RED
BLK
OR
IO-R-34

©2018 Phoenix Controls. Specifications subject to change without notice. Rev. 05/2018 MKT-0431 MPC-2355 PCI I/O MODULE 11
RS485 Wiring: PCI8000 to One or More IO-R-16 Modules
RS485 Wiring: PCI8000 to One or More IO-R-34 Modules

12 PCI I/O MODULE MKT-0431 MPC-2355 ©2018 Phoenix Controls. Specifications subject to change without notice. Rev. 05/2018
SPARE PARTS
Phoenix Controls
Catalog Number
For PRT-PCI-IO-R-xx Parts List Description
PRT-10429 16 6-position end mount, screw terminal connector plug for expansion modules not
mounted in line.
PRT-10598 34 2-position screw terminal connector plug, 180 degree.
PRT-10599 34 12-position screw terminal connector plug, 180 degree.
PRT-10600 34 15-position screw terminal connector plug, 180 degree.
PRT-32327802 16: Qty = 1
34: Qty = 2
Accessory Kit:
- One ground wire with quick-disconnect 0.187" female connector
- Eight 499-ohm resistors, +/- 1%, 0.6W; used for 4-20mA inputs
PRT-32330828 16 or 34 5-position screw terminal connector plug, 180 degree.

©2018 Phoenix Controls. Specifications subject to change without notice. Rev. 05/2018 MKT-0431 MPC-2355 PCI I/O MODULE 13
PHOENIX RECOMMENDED CABLES
Cable
Type
Plenum
Rated Function Wire
Gauge
Primary
Vendor/Part #
Alternate Vendor/
Part # Color Code Notes
2C
Round
No 24 Vac power 18 Belden 9409 1: Red
2: Black
Must be
stranded
14 Belden 9411
2C
Round
Yes 24 Vac power 18 Belden 82740 Windy City
NP002360
1: Red
2: Black
Must be
stranded
14 Windy City
NP007960
TSP No I/O signal wiring 22 Belden 9501 1: Black&Red Twisted
Shielded
Pair
2 TSP No I/O signal wiring 22 Belden 9502 1: Black&Red
2: Black&White
Two Twisted
Pair,
Shielded
3C
Round
No Signal 22 Belden 8443 1: Red
2: Black
3: Green
Must be
stranded
3C or
4C
Round
Yes Signal 22 Belden 88444 Windy City
004380
1: Red
2: Black
3: Green
4: White (not used as
3C)
Must be
stranded
4C
Round
No Signal 22 Belden 8444 Manhattan
M13304
1: White
2: Green
3: Black
4: Red
Must be
stranded
5C
Round
No Signal 22 Belden 8445 Manhattan
M13305
1: White
2: Brown
3: Black
4: Red
5: Green
Must be
stranded
8C No Signal 22 Belden 9421 Manhattan
M13308
1: White
2: Orange
3: Black
4: Red
5: Green
6: Yellow
7: Blue
8: Brown
No substi-
tutes
8C Yes Signal 22 Comtran 4956 1: White
2: Orange
3: Black
4: Red
5: Green
6: Yellow
7: Blue
8: Brown
No substi-
tutes
3C
MS/TP
No Shielded 22 Belden 3106A
(120 ohm)
1: White with Orange
stripe
2: Orange with White
stripe
3: Blue with White
stripe
Shielded
with drain
3C
MS/TP
Yes Shielded 22 Connect-Air
W223C-
2060YPC
1: Black
2: White
3: Red
Foil shield
with drain
wire
This manual suits for next models
1