PCI I/O MODULE
Compliance
• UL916
• C-UL, CE EN 61326-1:2013
• RCM
•WEEE
• RoHS2, China ROHS
•FCC
This device complies with part 15 of the FCC Rules. Operation
is subject to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, includ-
ing interference that may cause undesired operation.
• EU Contact Address:
Honeywell GmbH
Boeblinger Str. 17
71101 Schoenaich
Germany
•REACH
• Open Energy Management Class 2
The PCI I/O Module is designed for remote monitoring and
control applications that enables end-to-end automation and
device-to-enterprise integration. The I/O Module allows a
PCI8000 to interface directly with simple non-intelligent inputs
and outputs remotely located up to 4,000 feet away.
Connectivity is established via an industry-standard RS 485
communications bus. Multiple I/O Modules can be utilized
with a single PCI8000, providing 250+ I/O points on that one
device.
FEATURES
• The 34-point module provides 16 Universal Inputs, 10 Relay
Outputs, 8 Analog Outputs, and can power up to 4 16-point
modules.
• The 16-point module provides 8 Universal Inputs, 4 Relay
Outputs, 4 Analog Outputs, and is powered from a 34-point
module, or 15 Vdc supply.
• PCI I/O Modules support mounting on EN50022 standard
7.5mm x 35mm DIN rails.
SPECIFICATIONS
Dimensions
• 16-point Module — 3.25" x 4.5" x 2.4" (82.5 x 116 x 61mm)
• 34-point Module — 6.8" x 4.5" x 2.4" (162 x 116 x 61 mm)
Approximate Weight
• 16-point Module — 7.7 oz (0.22 kg)
• 34-point Module — 15.2 oz (0.43 kg)
Power
• 34-Point Module: 24 Vac@28 VA minimum (includes a maximum four 16-
point modules). Dedicated UL listed Class 2 Transformer, 50/60 Hz (can
be shared with PCI8000).
• 16-Point Module: 15 Vdc @ 0.133 A (2W) external 3rd party power supply
or Phoenix Controls WPS420 DC Power Supply.
Operating System
• Niagara 4 – Requires Niagara 4.3 or later
• Niagara AX – Requires Niagara 3.8u3 or later
Maximum Expansion per PCI8000
See I/O Module Combinations and Power Options table on page 8.
Communications
RS485
RS485/NRIO Unit Loads
These components each exert the following unit load on the RS485 network:
• 16-point module = 1/4
• 34-point module = 1/4
Operating Temperature
-4 – 140°F (-20 – 60°C)
Storage temperature
-40 – 185°F (-40 – 85°C)
Humidity
5%–95%, Non-condensing
TABLE OF CONTENTS
Ordering Guide ........................................................ 2
Inputs/Outputs......................................................... 2
Applications.............................................................. 2
Dimensions/Installation............................................ 3
Wiring...................................................................... 5
Power Backup........................................................... 9
RS485 Communications .......................................... 9
Recommended Cables ............................................ 11