
4
USEPHOENIX.COM |800-533-7533
C. Direct the outlet duct from the Guardian R HEPA System
to the room with the open combustion device(s).
This will positively pressurize the room with HEPA
filtered air, thus preventing backdrafting. As in case B,
those combustion devices must be checked after the
Guardian R HEPA System is running to guarantee that
they are not backdrafting.
3.4 Power/Speed Control
The power/speed switch is located on the control panel.
When turned on to any speed, it powers the impeller fan.
Occasionally the impeller fan may not start on low speed. If
this occurs, rotate the speed control to high speed until the
impeller fan starts, then adjust it to a lower speed.
CAUTION: Do not remove HEPA filter with the unit on.
Removing the top and filters while running will expose the
dangerous rotating impeller fan. Disconnect the appliance
before changing filters.
3.5 Resettable Circuit Breaker
The 12 AMP thermal response resettable circuit breaker
protects the unit and devices connected to its duplex GFCI
outlet.
The circuit breaker is designed to sense the total current
draw through the circuit. The circuit breaker “trips” when
more than 12 amps of electrical current are drawn through
the device’s power cord. Should an over-current condition
occur, the Guardian R on-board circuit breaker prevents
nuisance visits to a remote power junction box.
Note: The holes on the control panel plate allow the
pressure inside the control panel to equalize with ambient
air pressure.
IMPORTANT: Total amperage of the Guardian R plus all
devices plugged into the receptacle must not exceed 12
amps. The circuit breaker will not allow for loads in excess
of 12 amps, although there is a time delay before the
overloaded circuit is broken.
IMPORTANT: When the Phoenix Guardian R is plugged into
a standard “powered” wall outlet the Phoenix Guardian R’s
duplex outlet is electrically “HOT” and AC voltage is present.
3.6 GFCI Protection and the On-Board Duplex
VAC Outlet
The standard AC voltage outlet GFCI (Ground Fault Circuit
Interrupter) protection promotes operator safety in wet
applications. GFCI devices trip when a fault to electrical
“ground” is sensed.
It is recommended to check the GFCI protection prior to
operation. To check, push the “TEST” button located on the
GFCI duplex outlet. If operating properly the “RESET” button
on the GFCI outlet will pop out. A tripped GFCI is indicated
by a small LED. The device can only be “RESET” when the
Guardian R is connected to a wall outlet providing standard
voltage. This duplex AC outlet allows the inter-connection
of other AC powered devices. The sum total amperage of
all devices plugged into the receptacle must not exceed 10
amps.
3.7 Servicing
Before each use inspect for damage, blocked inlet or outlet.
Inspect the GFCI to ensure it is not in a “tripped” condition.
Push “RESET” to reset the GFCI.
When the Phoenix Guardian R is first turned on, check for
excessive vibration. If the unit vibrates excessively or if
impeller rubs on housing, turn off the unit immediately. Have
a service technician inspect the unit to locate the problem.
4 Maintenance
Use extreme caution when changing the HEPA filter as
hazardous material could be trapped in the media. Always
make sure to dispose of filters in the appropriate way. If you
are unsure of how to safely dispose of any filter-consult an
industrial hygienist to ensure that all hazardous materials
are contained and disposed of properly.
4.1 Air Filters
The standard Phoenix Guardian R HEPA System is equipped
with two filters that progressively filter out smaller particles.
An optional activated carbon/potassium permanganate
filter can be also added. These filters must be checked
regularly. Operating the unit with dirty filters will reduce the
airflow, but will do no harm to the unit. The unit can be run
indefinitely with dirty filters.
The two standard filters used are listed below (as installed in
the unit from top to bottom):
A. 30 to 35% efficient (per ASHRAE 52.1-1992), MERV-7,
pleated fabric pre-filter.
B. 99.97% DOP efficient HEPA filter.