manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Pittway
  6. •
  7. Switch
  8. •
  9. Pittway System Sensor EPS10EXP User manual

Pittway System Sensor EPS10EXP User manual

COVER
4.9"
9.5"
LOCKING
SCREW
HEX ADJUST
SCREW
1/4" HEX HEAD
COVER
TAMPER
SET SCREW
(WRENCH
PROVIDED)
ADJUSTMENT
WHEEL
COVER
(WRENCH
PROVIDED)
MAIN ADJUSTMENT
WHEEL (TURN
COUNTERCLOSKWISE
TO INCREASE
PRESSURE)
1/2" NPT
D770-25-00 1 I56-1427-000
EPS10EXP Explosion Proof
Alarm Pressure Switch
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Important
Please Read Carefully and Save
This instruction manual contains important information
about the installation and operation of alarm pressure
switches. Purchasers who install switches for use by others
must leave this manual or a copy of it with the user.
Read all instructions carefully before installation, following
only those instructions that apply to the model you are in-
stalling.
Before installing any alarm device, be thoroughly familiar
with:
NFPA 72: Installation, Maintenance, and Use of Protec-
tive Signaling Systems
NFPA 13: Installation of Sprinkler Systems
Other applicable NFPA standards, local codes, and the re-
quirements of the authority having jurisdiction.
Failure to follow these directions may result in failure of the
device to report an alarm condition. System Sensor is not
responsible for devices that have been improperly installed,
tested, or maintained.
Operation
As pressure changes, a diaphragm actuates 2 snap action
switches. The pressure switch actuation is determined by
adjustment settings.
Specifications
Contact Ratings: 10 A, 1/2 HP @ 125/250 VAC
2.5 A @ 6/12/24 VDC
Operating Temperature Range: –40°F to +160°F
Maximum Service Pressure: 250 PSI
Maximum Adjustment Range: 4 – 20 PSI
Enclosure Rating: NEMA Type 4 — Indoor or/Outdoor Use
Hazardous Atmospheres Classification: Class I, Groups B, C, D, Div. 1
Class II, Groups E, F, G, Div. 1
Class III, Div. 1
Approximate Differential: 3 PSI throughout range
Installation
1.
Back out cover tamper set screw and remove cover (Fig. 1).
2. Mounting the Switch
The device is designed to be mounted in the upright or
horizontal position; side mounting is also acceptable.
Figure 1. Pressure switch basic dimensions:
WARNING
To prevent ignition of hazardous atmospheres, disconnect
circuits before removing cover. Keep cover closed while cir-
cuits are live. Conduit runs must have sealing fittings con-
nected within 18” of the enclosure.
Technical Manuals Online! - http://www.tech-man.com
D770-25-00 2 I56-1427-000
Locate it where vibration, shock, and mechanical loading
are minimal. Refer to piping diagram (Figure 2 on page
2).
a. Mount the device directly to the line via the 1/2"NPT
pressure connection. The use of teflon pipe sealant
tape is recommended. Be sure the fitting is tight
enough to prevent leaks.
b. Apply tightening torque to the brass hex portion of
device.
CAUTION
High voltage. Electrocution hazard. Do not handle live AC
wiring or work on a device to which AC power is applied.
Doing so may result in severe injury or death.
3. Wire the device in accordance with the National Electri-
cal Code. Two 1/2” NPT conduit entry holes have been
provided in the mounting base to accept explosion proof
conduit fittings. If necessary, remove conduit entry plug
with 3/8” square wrench.
4. Connect wiring to terminals (see Figure 3 and Table 1).
WET
SYSTEM
ALARM
CHECK
VALVE
OS & Y
VALVE
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
RETARD
WATER
MOTOR
GONG
EPS10EXP
WET
SYSTEM
ALARM
CHECK
VALVE
OS & Y
VALVE
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
RETARD
WATER
MOTOR
GONG
EPS10EXP
DRY
SYSTEM
ALARM
CHECK
VALVE
OS & Y
VALVE
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
WATER
MOTOR
GONG
CHECK
VALVE
EPS10EXP
WET SYSTEM WET SYSTEM DRY SYSTEM
WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL
WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL
WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL
TO
SPRINKLER
SYSTEM
TO
SPRINKLER
SYSTEM
TO
SPRINKLER
SYSTEM
Figure 2. Typical piping diagram for EPS10EXP
A78-2398-00
Figure 3. Switch terminals:
Table 1. Electrical connections (referenced at factory
settings):
COMMON
TERMINALS
TERMINAL
“A”
SWITCH #2
TERMINAL
“B”
GROUND
SCREW
(GREEN)
SWITCH #1
A78-2346-02
BREAK WIRE AS SHOWN FOR
SUPERVISION OF CONNECTION.
DO NOT ALLOW STRIPPED WIRE
LEADS TO EXTEND BEYOND
SWITCH HOUSING. DO NOT
LOOP WIRES.
SWITCHES AT 4-8 P.S.I. (HIGH TRIP PT.)
SWITCHES AT 0 P.S.I.
SW1 SW2
MODEL EPS10EXP
SW1 SW2
B
COM
A
B
COM
A
A
COM
B
A
COM
B
BOTH SWITCHES ACTIVATE SIMULTANEOUSLY
Technical Manuals Online! - http://www.tech-man.com
D770-25-00 3 I56-1427-000
Adjustments To Factory Settings
The EPS10EXP device is pre-adjusted at the factory to alarm
at 4–8 PSI on rising pressure (see Table 2). Pressure switch
settings may be adjusted in the field to obtain a different
pressure alarm response from 4 PSI to 20 PSI. The switch
has an override feature on the adjustment mechanism to
prevent exceeding the 20 PSI max. setting of the switch.
This override feature carries with it a tolerance band that
may limit the upper adjustment to 16–20 PSI. Care must be
used when setting the switch to ensure that the lower limit
of 4 PSI is not exceeded. This will allow the switch to reset
within the 3 PSI differential stated.
1. Install pressure switch as stated in “INSTALLATION”
portion of instruction manual. Attach pressure test
source to system.
2. Remove adjustment wheel cover and back off locking
screw (see Figure 1) to allow main adjustment wheel to
rotate freely.
3. Test trip point by slowly introducing pressure from the
pressure test source. When trip point is found, reduce
pressure to zero. Rotate main adjustment wheel (coun-
terclockwise to increase pressure) and retest until switch
trip point is at the desired pressure setting (4–20 PSI
range). Each tine on the wheel represents an approxi-
mate trip point change of 0.2 PSI. One full rotation
changes the trip point setting by approximately 2.5 PSI.
A reset differential of approximately 3 PSI is typical
throughout the entire adjustment range of switch.
4. Retest the set point several times to ensure accuracy of
setting.
5. Re-seat locking screw.
6. Re-install adjustment wheel cover.
Table 2.
NOTE: The sensor assembly is not field replaceable. Do
not attempt to disassemble these parts. If you have
any questions, consult System Sensor. System Sen-
sor recommends careful consideration of the fol-
lowing factors when specifying and installing
Alarm Pressure Switches. Always refer to the In-
stallation and Maintenance Instruction for specific
recommendations on individual devices before in-
stalling the unit.
• Electrical ratings stated in literature and on name-
plates should not be exceeded.
• Overload on switch can cause failure on the first
cycle. Always wire devices according to national and
local electrical codes.
• Install units away from shock and vibration. Proper
electrical fittings should be used to prevent moisture
from entering the enclosure via the conduit.
• Test all devices for proper operation after initial instal-
lation. Perform preventive maintenance and periodic
testing as required by the applicable NFPA standards
but not less than bi-monthly.
• Install a back-up control for all critical applications
where control failure could endanger life or property.
A backup control to serve as a high or low limit con-
trol is especially recommended for applications where
a runaway condition could result.
• Do not mount unit where ambient temperatures will
exceed published limits.
• Avoid impact or mechanical loading.
FACTORY SETTINGS (PSI)
MODEL Approx. Reset
EPS10EXP 4—8 3 PSI Diff.
Rise
Technical Manuals Online! - http://www.tech-man.com
D770-25-00 4 I56-1427-000
© System Sensor 1999
Three-Year Limited Warranty
System Sensor warrants its enclosed pressure switch to be free from de-
fects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this pressure switch. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of
the pressure switch which is found to be defective in materials or work-
manship under normal use and service during the three year period com-
mencing with the date of manufacture. After phoning System Sensor’s toll
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair Depart-
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifica-
tions, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or conse-
quential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.
Technical Manuals Online! - http://www.tech-man.com

This manual suits for next models

3

Other Pittway Switch manuals

Pittway System Sensor EPS40EXP User manual

Pittway

Pittway System Sensor EPS40EXP User manual

Pittway System Sensor EPS40 Series User manual

Pittway

Pittway System Sensor EPS40 Series User manual

Pittway System Sensor PIBV2 User manual

Pittway

Pittway System Sensor PIBV2 User manual

Pittway System Sensor PIBVEXP User manual

Pittway

Pittway System Sensor PIBVEXP User manual

Popular Switch manuals by other brands

UTAH SCIENTIFIC Utah-400 iP Setup & operation

UTAH SCIENTIFIC

UTAH SCIENTIFIC Utah-400 iP Setup & operation

Link electronics 860-XL818C Specification sheet

Link electronics

Link electronics 860-XL818C Specification sheet

Sygonix 2349922 operating instructions

Sygonix

Sygonix 2349922 operating instructions

Austin Hughes Electronics Cyberview D-117 user guide

Austin Hughes Electronics

Austin Hughes Electronics Cyberview D-117 user guide

SMC Networks LFE series Operation manual

SMC Networks

SMC Networks LFE series Operation manual

rackit Paradigm Installer/user guide

rackit

rackit Paradigm Installer/user guide

Extron electronics VEGA AUDIO SW6 user guide

Extron electronics

Extron electronics VEGA AUDIO SW6 user guide

D-Link DES-3528 - xStack Switch - Stackable user manual

D-Link

D-Link DES-3528 - xStack Switch - Stackable user manual

ADTRAN NetVanta 1524ST Specification sheet

ADTRAN

ADTRAN NetVanta 1524ST Specification sheet

Renkforce RF-3353154 operating instructions

Renkforce

Renkforce RF-3353154 operating instructions

Bentek Solar BTK6-MDSS Series Installation and operating instructions

Bentek Solar

Bentek Solar BTK6-MDSS Series Installation and operating instructions

TRENDnet TK-1601R Specifications

TRENDnet

TRENDnet TK-1601R Specifications

THOMSON GRASS VALLEY Triton TTN-BVS-1602CP installation manual

THOMSON

THOMSON GRASS VALLEY Triton TTN-BVS-1602CP installation manual

Dell EMC N20 Series manual

Dell EMC

Dell EMC N20 Series manual

SMC Networks SMC6224M Management guide

SMC Networks

SMC Networks SMC6224M Management guide

Sunricher SR-ZG2833PAC-S4 instruction manual

Sunricher

Sunricher SR-ZG2833PAC-S4 instruction manual

Honeywell Q640 instruction sheet

Honeywell

Honeywell Q640 instruction sheet

Acuity Controls rPODBA Series installation instructions

Acuity Controls

Acuity Controls rPODBA Series installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.