4
rp2
Reset point rP2
Window function*: functioning according to parameter Ou2
.
Range: depending on temperature range 0%..99% of full-scale, the decimal point depends on the sensor f.s. Default: 25% f.s.
on the selected measure unit. Attention: if par. 11 is selected as “window”, par. rP2 switches to FL2.
5 Table of complete configuration parameters (
EF
menu)
5
res
Reset
Restore default parameters
yes no
6
tCo r
Temperature Correction
Displayed temperature calibration
Range: ± 5 °C. Default: 0
7
d s1
SP1 Delay Switch
Switching delay ON, output SP1, valid for S P1
Range: 0.00..99.99 s. 0 = not active. Default: 0
8
d r1
SP1 Delay Reset
Switching delay OFF, output SP1, valid for r p1
Range: 0.00..99.99 s. 0 = not active. Default: 0
9
ds2
SP2 Delay Switch
Switching delay ON, output SP2, valid for SP2
Range: 0.00..99.99 s. 0 = not active. Default: 0
10
d r2
SP2 Delay Reset
Switching delay OFF, output SP2, valid for rp2
Range: 0.00..99.99 s. 0 = not active. Default: 0
11
O u1
Output SP1 function
H = Hysteresis, F = Window*
Fn c Out1 ON when process is out of range FH1 / FL1
Fn o Out1 ON when process is in range FH1 / FL1
Hn c Out1 OFF = process reaches SP1, ON = process
returns to rP1
Hn o Out1 ON = process reaches SP1, OFF = process
returns to rP1. Default
12
Ou2
Output SP2 function
H = Hysteresis, F = Window*
Fn c Out2 ON when process is out of range FH2 / FL2
Fn o Out2 ON when process is in range FH2 / FL2
Hn c Out2 OFF = process reaches SP2, ON = process
returns to rP2
Hn o Out2 ON = process reaches SP2, OFF = process
returns to rP2. Default
13
u ni
Temperature Unit
C Centigrade
F Fahrenheit
K Celsius
14
Lo
Lowest temperature
Lowest temperature value detected by the sensor with the current measure unit.
15
Hi
Highest temperature
Highest temperature value detected by the sensor with the current measure unit.
16
HLre
Highest Lowest Reset
Reset of par. HI and LO to the actual temperature value.
y es n o Default
17
Oana
Analogue output type
OFF Output not active (0V / 0mA in output)
UVoltage 0..10V
ICurrent 4..20mA. Default
At each output type modification, the content of par. O_n p and O_Ep changes according to the physical size of the output type.
18
t_nP
Temperature zero point
Temperature numeric value expressed with the selected measure unit for the retransmission on the analogue output.
NB: Value displayed but not editable.
* Window mode = within this range the output is activated / deactivated according to parameters 10 / 11.
2.1 Technical data
Accuracy ± 0,2% F.S. @25°C
Sensor type PT1000
Vibration 4g (10..2000 Hz)
Shock 50g / 8 ms
Measuring range - 50..150 °C
Electrical connections EN175301-803-A (DIN43650-A); M12x1 5 Pole
Housing orientation Display 335° rotatable - Electrical connection 343° rotatable
Sensor working temperature - 25..+ 85°C
2 digital outputs Transistor PNP max 500 mA
1 analogue output Selectable 4..20 mA / 0..10 V
2.2 Software features
Display 4 Digits, 1..3 decimal points
Temperature unit Selectable °C, °F, °K
Datalogger Ring buffer: 3518 data points - Sampling time: 0.1..999.9 s, Off (0)
Quick set-up options Programming via APP (NFC) for Android smartphones
2.3 Example of ordering codes
2000.01.002 DST100 - Range -50°+150°C / Fixed connection - 1/2”GAS EL = 100 mm
2000.01.003 DST100 - Range -50°+150°C / Fixed connection - 1/2”GAS EL = 150 mm
2000.15.002 DST100 - Range -50°+150°C / Sliding connection - 1/4” NPT EL = 100 mm
2000.15.003 DST100 - Range -50°+150°C / Sliding connection - 1/4” NPT EL = 150 mm
2000.93.002 DST100 - Range -50°+150°C / Clamp connection - C50 EL = 100 mm
2000.96.002 DST100 - Range -50°+150°C / Food connection - DN50 EL = 100 mm
For the complete list of ordering codes refer to the website.
3 Enter switching point configuration
Press Display Do
1 At the start, display shows the process.
2o op Slide up / down through Switching Point parameters
(SP1, rP1, SP2, rP2)
3SET Access the parameter to be modified
NB: If on par. code has been entered a password
different from 0, the device will require this password
before modifying any parameter
4o op Increase or decrease selected value. Enter the new data and press SET. To modify another
parameter back to point 2.
3.1 Enter configuration parameters
Press Display Do
5SET + o
op Select par. EF from the switching points modification
menu
6SET Access the parameter to be modified Enter the password (if enabled).
7o op Increase or decrease selected value. Enter the new data and press SET. To modify another
parameter back to point 5.
4 Table of Switching point
1
S P1
Switching point SP1
Window function*: functioning according to parameter O u1.
Range: depending %..100% of full-scale, the decimal point depends on the sensor f.s. Default: 75% f.s. on the selected measure
unit. Attention: if par. 10 is selected as “window”, par. S P1 switches to F H1 .
2
r p1
Reset point rP1
Window function*: functioning according to parameter O u1.
Range: depending on temperature range 0%..99% of full-scale, the decimal point depends on the sensor f.s. Default: 25% f.s.
on the selected measure unit. Attention: if par. 10 is selected as “window”, par. r P1 switches to F L1 .
3
SP2
Switching point SP2
Window function*: functioning according to parameter Ou2
.
Range: depending on temperature range 1%..100% of full-scale, the decimal point depends on the sensor f.s. Default: 75% f.s.
on the selected measure unit. Attention: if par. 11 is selected as “window”, par. SP2 switches to FH2.