Pixsys DST100 User manual

1 Process Connection
DST100
5x60
6x15
6x50
6x100
Diameter x Lenght
A304 (AISI 304 - 899°C)
A316 (AISI 316 - 899°C)
Material type
0000 (no connector)
1/2”/ (sliding)
1/4”/ (sliding)
1/2”/F (F = fixed)
1/4”/F (F = fixed)
1/8”/F (F = fixed)
1/2”/FNPT (F = fixed)
1/4”/FNPT (F = fixed)
DN25FO (DN25 food)
DN25CL (DN25 clamp)
Other..
Connector / Coupling
4 SP1 (Out1)
5 SP2 (Out2)
3 Us-
1 Us+
2 Out analogue
P
U
Pin Configuration P1
2
3
54
1
2 Main features
Box 93 x 37 mm
Power supply 15..30 VDC
Power consumption Max 0,8 W
Operating conditions Temperature -25..+85 °C, humidity 35..95 RH% (Cable PVC 22: -5°C ... +60°C)
Material Sensor housing steel galvanised, display housing plastic
Weight Approx. 189 g
Sealing IP65 - FPM, NBR, EPDM
19
t_EP
Temperature end point
Temperature numeric value expressed with the selected measure unit for the retransmission on the analogue output.
Default:value greater than f.s.
Range: 50% - 100% of the nominal temperature range expressed with the selected measure unit.
20
O_nP
Output zero point
Numeric starting value expressed in tension or current selected on parameter Oana
.
NB: Value displayed but not editable.
Example: for Oana
= i, O_n P = 4.00mA
Example 2: for Oana
= u, O_n P = 0.00V
21
O_EP
Output end point
Numeric end value expressed in tension or current selected on parameter Oana
.
NB: Value displayed but not editable.
Example: for Oana
= i, O_n P = 20.00mA
Example 2: for Oana
= u, O_n P
= 10.00V
22
dAa
Damping for analogue output
Low-pass filter for analogue output. Time in seconds for the output stabilisation from 10% to 90% of the variation.
Example: temperature sensor 0..10 Bar, dAa
= 1.00s: at instantaneous temperature switch from 0 to 10Bar, the output will take
approx. 1.2s. to stabilise from 4.00 to 20.00mA or from 0.00 to 10.00V
Range: 0.00..3.00. Default: 0.00
23
diS r
Display rotate
Display orientation / rotation 0° (normal) or 180°
yes n o Default
24
diS
Display mode
Display mode defines the displayed value.
A c -3 a c t without the 3 less significant decimals**
A c -2 a c t without the 2 less significant decimals**
A c -1 a c t without the less significant decimal**
off Switches off display after 5 sec.
hi G h Maximum temperature value
Lo w Minimum temperature value
Act Actual temperature value. Default
** .. Among those displayed.
25
Dupd
Display update rate
Display update rate, updates per second.
20 Every 20 seconds
5 Every 5 seconds
2 Every 2 seconds. Default
1 Every 1 second
26
di a
Diagnostic mode
To activate a diagnostic mode.
o n the sensor simulates a temperature ramp in loop, from the min. to the max. value of the temperature range, in a cycle
time of approx. 5s. It is used to verify the functioning of the switching points and the analogue output.
o ff Default
27
s.tim
Sample time (logger)
A device integrated data logger
Range: steps of 0.0s up to 999.9s.
0.0 logger disabled. Default
The logger stores values into a circular memory of 3500 points , with time selected in s.tim
, instantaneous temperature value
and the status of SP1 and SP2 at sample time. At restart de old logger is deleted and a new one is overwritten. It is possible to
analyze the log through a software with NFC interface both with ON or OFF device.
28
code
Access code definition
0000 = no password. Default
Password input digit by digit
To modify the password press SET and using o or p select the value of each digit. Press SET to modify the next digit. To end
the operation, press SET and confirm or not with Yes or Fa Ls.
NB: If par. Co d e is modified with a number different from 0000, a new password is enabled and will be requested once (until the
next restard) to modify parameters and switching points.
DST100
Temperature transmitter
with display
User manual
PIXSYS s.r.l.
www.pixsys.net
online assistance: http://forum.pixsys.net
2300.10.283-RevA
Software Rev. 5.04
300718
Read carefully the safety guidelines and programming instructions
contained in this manual before using/connecting the device.

4
rp2
Reset point rP2
Window function*: functioning according to parameter Ou2
.
Range: depending on temperature range 0%..99% of full-scale, the decimal point depends on the sensor f.s. Default: 25% f.s.
on the selected measure unit. Attention: if par. 11 is selected as “window”, par. rP2 switches to FL2.
5 Table of complete configuration parameters (
EF
menu)
5
res
Reset
Restore default parameters
yes no
6
tCo r
Temperature Correction
Displayed temperature calibration
Range: ± 5 °C. Default: 0
7
d s1
SP1 Delay Switch
Switching delay ON, output SP1, valid for S P1
Range: 0.00..99.99 s. 0 = not active. Default: 0
8
d r1
SP1 Delay Reset
Switching delay OFF, output SP1, valid for r p1
Range: 0.00..99.99 s. 0 = not active. Default: 0
9
ds2
SP2 Delay Switch
Switching delay ON, output SP2, valid for SP2
Range: 0.00..99.99 s. 0 = not active. Default: 0
10
d r2
SP2 Delay Reset
Switching delay OFF, output SP2, valid for rp2
Range: 0.00..99.99 s. 0 = not active. Default: 0
11
O u1
Output SP1 function
H = Hysteresis, F = Window*
Fn c Out1 ON when process is out of range FH1 / FL1
Fn o Out1 ON when process is in range FH1 / FL1
Hn c Out1 OFF = process reaches SP1, ON = process
returns to rP1
Hn o Out1 ON = process reaches SP1, OFF = process
returns to rP1. Default
12
Ou2
Output SP2 function
H = Hysteresis, F = Window*
Fn c Out2 ON when process is out of range FH2 / FL2
Fn o Out2 ON when process is in range FH2 / FL2
Hn c Out2 OFF = process reaches SP2, ON = process
returns to rP2
Hn o Out2 ON = process reaches SP2, OFF = process
returns to rP2. Default
13
u ni
Temperature Unit
C Centigrade
F Fahrenheit
K Celsius
14
Lo
Lowest temperature
Lowest temperature value detected by the sensor with the current measure unit.
15
Hi
Highest temperature
Highest temperature value detected by the sensor with the current measure unit.
16
HLre
Highest Lowest Reset
Reset of par. HI and LO to the actual temperature value.
y es n o Default
17
Oana
Analogue output type
OFF Output not active (0V / 0mA in output)
UVoltage 0..10V
ICurrent 4..20mA. Default
At each output type modification, the content of par. O_n p and O_Ep changes according to the physical size of the output type.
18
t_nP
Temperature zero point
Temperature numeric value expressed with the selected measure unit for the retransmission on the analogue output.
NB: Value displayed but not editable.
* Window mode = within this range the output is activated / deactivated according to parameters 10 / 11.
2.1 Technical data
Accuracy ± 0,2% F.S. @25°C
Sensor type PT1000
Vibration 4g (10..2000 Hz)
Shock 50g / 8 ms
Measuring range - 50..150 °C
Electrical connections EN175301-803-A (DIN43650-A); M12x1 5 Pole
Housing orientation Display 335° rotatable - Electrical connection 343° rotatable
Sensor working temperature - 25..+ 85°C
2 digital outputs Transistor PNP max 500 mA
1 analogue output Selectable 4..20 mA / 0..10 V
2.2 Software features
Display 4 Digits, 1..3 decimal points
Temperature unit Selectable °C, °F, °K
Datalogger Ring buffer: 3518 data points - Sampling time: 0.1..999.9 s, Off (0)
Quick set-up options Programming via APP (NFC) for Android smartphones
2.3 Example of ordering codes
2000.01.002 DST100 - Range -50°+150°C / Fixed connection - 1/2”GAS EL = 100 mm
2000.01.003 DST100 - Range -50°+150°C / Fixed connection - 1/2”GAS EL = 150 mm
2000.15.002 DST100 - Range -50°+150°C / Sliding connection - 1/4” NPT EL = 100 mm
2000.15.003 DST100 - Range -50°+150°C / Sliding connection - 1/4” NPT EL = 150 mm
2000.93.002 DST100 - Range -50°+150°C / Clamp connection - C50 EL = 100 mm
2000.96.002 DST100 - Range -50°+150°C / Food connection - DN50 EL = 100 mm
For the complete list of ordering codes refer to the website.
3 Enter switching point configuration
Press Display Do
1 At the start, display shows the process.
2o op Slide up / down through Switching Point parameters
(SP1, rP1, SP2, rP2)
3SET Access the parameter to be modified
NB: If on par. code has been entered a password
different from 0, the device will require this password
before modifying any parameter
4o op Increase or decrease selected value. Enter the new data and press SET. To modify another
parameter back to point 2.
3.1 Enter configuration parameters
Press Display Do
5SET + o
op Select par. EF from the switching points modification
menu
6SET Access the parameter to be modified Enter the password (if enabled).
7o op Increase or decrease selected value. Enter the new data and press SET. To modify another
parameter back to point 5.
4 Table of Switching point
1
S P1
Switching point SP1
Window function*: functioning according to parameter O u1.
Range: depending %..100% of full-scale, the decimal point depends on the sensor f.s. Default: 75% f.s. on the selected measure
unit. Attention: if par. 10 is selected as “window”, par. S P1 switches to F H1 .
2
r p1
Reset point rP1
Window function*: functioning according to parameter O u1.
Range: depending on temperature range 0%..99% of full-scale, the decimal point depends on the sensor f.s. Default: 25% f.s.
on the selected measure unit. Attention: if par. 10 is selected as “window”, par. r P1 switches to F L1 .
3
SP2
Switching point SP2
Window function*: functioning according to parameter Ou2
.
Range: depending on temperature range 1%..100% of full-scale, the decimal point depends on the sensor f.s. Default: 75% f.s.
on the selected measure unit. Attention: if par. 11 is selected as “window”, par. SP2 switches to FH2.
This manual suits for next models
6
Popular Transmitter manuals by other brands

Dwyer Instruments
Dwyer Instruments AVLV Series Specifications-installation and operating instructions

HumanTechnik
HumanTechnik CM-2.4 user manual

Security Brands
Security Brands RIDGE RTE 14-RTE433T quick start guide

Becker
Becker B-Tronic EasyControl EC5401B Assembly and operating instructions

Extron electronics
Extron electronics DTP2 T 202 FB Setup guide

Kyosho
Kyosho KT-19 manual