200012-A
LED INDICATOR LIGHT
POWER WIRES
IONIZATION BRUSHESMOUNTING FLANGEMOUNTING HOLE
AIR FLOW
FIGURE 1
FAN
DISCHARGE
FAN INLET
IN LINE 500 mA
GLASS CARTRIDGE FUSE
CONNECT
TO POWER
FIGURE 2
PA600 SERIES
MOUNTING HOLES
INTRODUCTION
The Plasma Air 600 (PA600) Series is a needlepoint brush type ionizer
producing an equal amount of positive and negative ions. This ionization
equipment is effective in reducing harmful pathogens, pollutants and odors
by introducing positive and negative ions into the system airflow. This unit is
highly versatile as it may be installed in an air handling unit, fan coil unit,
PTAC, heat pump and even a ductless split system. The PA600 Series is self
contained in a potted enclosure which has molded flanges with mounting
holes. Models are available to accept 12V DC, 24V AC / 24V DC, 120V AC
or 208 - 240V AC without the use of an external power supply.
MECHANICAL INSTALLATION INSTRUCTIONS
GENERAL MOUNTING CRITERIA:
WARNING: Do not connect to power before mechanical
installation is complete.
1. Mount ionization unit to allow access for general maintenance. Ensure the
brush tips are not within ¾" of any metallic surface to prevent arcing.
2. Mount the unit at or near the fan inlet using the holes in the mounting
flanges, ensuring that the air stream flows over the 2 brushes
simultaneously. See figures 1 & 2.
3. For best results, the unit should be mounted downstream of the filter.
4. For best results avoid locations directly after a cooling coil or humidifier.
Note: Ionizer may be mounted
downstream of the fan if fan
inlet area is not accessible.