Pneumercator RA400 User manual

RA400 Instruction Manual - 2017-07-30.docx July 30, 2017
INSTRUCTION MANUAL
RA400 REMOTE ELECTRONIC ALARM ANNUNCIATOR
This document describes the installation, programming and operation of the RA400 Remote
Electronic Alarm Annunciator, which is designed for use with the LC2000 or most TMS Series
models.
DWG NO. 20059 REV. N/C


Page
Section 1.0 PRODUCT OVERVIEW ........................................................................................ 4
1.1 TMS/LC2000 Compatibility .................................................................................... 5
1.2 TEST Pushbutton .................................................................................................. 6
1.3 RESET Pushbutton ............................................................................................... 6
1.4 Visual Alarm Strobe ............................................................................................... 6
1.5 Audible Annunciator .............................................................................................. 6
1.6 Power Indicator LED ............................................................................................. 7
1.7 User-Selectable Advisory Pocket Insert ................................................................ 7
Section 2.0 INSTALLATION ..................................................................................................... 8
2.1 Mounting ................................................................................................................ 8
2.2 Wiring .................................................................................................................. 12
2.2.1 AC Power ............................................................................................................ 12
2.2.2 Communications .................................................................................................. 13
2.2.2.1 Cable Requirements ............................................................................................ 13
2.2.2.2 RA400 Terminal Connections ............................................................................. 14
2.2.2.3 RA400 Communications Wiring Detail ................................................................ 14
2.2.2.4 RS-485 Communications Wiring Detail ............................................................... 15
2.2.2.5 Line Termination Resistor ................................................................................... 16
2.2.3 RS-2 Remote TEST/RESET Wiring .................................................................... 16
Section 3.0 CONFIGURATION .............................................................................................. 17
3.1 On-Board Programming ...................................................................................... 17
3.1.1 Setting Logical Address - S3 ............................................................................... 17
3.1.2 Setting Shutoff Delay – S4 .................................................................................. 18
3.1.3 Alarm Programming – S5, S6, S7 ....................................................................... 19
3.1.4 Miscellaneous Programming – S5 ....................................................................... 21
Section 4.0 PRODUCT SPECIFICATIONS ............................................................................ 22
TABLE OF CONTENTS

RA400 Instruction Manual - 2017-07-30.docx Page 4 of 22 July 30, 2017
1.0 Product Overview
The RA400 Remote Annunciator panel is used in applications where it is desired to receive
TMS/LC2000 series alarms from various on-site locations at distances up to 4000 feet (1200M)
away from the main console. Since the RA400 is a microprocessor-based, addressable device
communicating over the RS-485 Peripheral Expansion Bus, up to 16 RA400 panels may be
connected to a single TMS/LC2000. The RA400 is housed in a NEMA 4X enclosure for harsh
industrial/ outdoor environments. The visual indicator employs an ultra-bright, LED strobe for
maximum reliability in extreme temperatures. The membrane overlay pushbuttons are 1.75” on
centers for easy operation with gloved hands.
Figure 1.0-1 Front Panel View
DRAWING NO. 20060 REV. N/C
PNEUMERCATOR
Liquid Level Control Systems
RESET TEST
POWER
REMOTE ANNUNCIATOR
RA 400
(555) 501-0005
COMPANY ABC INC.
TANK 1 HIGH LEVEL ALARM
Sounds Call:
If Alarm

RA400 Instruction Manual - 2017-07-30.docx Page 5 of 22 July 30, 2017
Figure 1.0-2 Interior View
1.1 TMS/LC2000 Compatibility
The RA400 can be used with most TMS/LC2000 models provided appropriate firmware is loaded.
RA400 support is provided with the following TMS/LC2000 console firmware versions:
LC2000: V6x.00.08 or later
TMS2000: V2x.00.13 or later; V2x.01.xx
TMS3000: V3x.00.13 or later; V3x.01.xx
TMS2000W, TMS4000, TMS4000W: All firmware versions supported
where “xx” denotes “don’t care” values
Please contact Technical Support for an upgrade if you have firmware outside of the above range,
or if you have questions about identifying the firmware version in your console.
DRAWING NO. 20061 REV. A
6 8
7
15
4
3
2
J1 FRONT PANEL
1/2 AMP
250 VAC
FAST
ACTING
GND
NEUTRAL
HOT
AC
IN
115V
D2D3
S4
S5
SHUTOFF
DELAY
1
2
3
4
5
6
7
8
O
U
T
I
N
RS-485 COMMS.
CH. A (+)
CH. B (-)
SHIELD
ON
OFF
LINE TERMINATOR
"ON" FOR
END-OF-RUN ONLY
3BT2BT
S2
LINE TERMINATOR
SWITCH
(2) RS-485 COMMS.
PLUG-IN TERMINAL
BLOCKS
(3) DIP
SWITCHES
FUSE
LINE VOLTAGE
SWITCH
AC POWER PLUG-IN TERMINAL BLOCK
(W/ SCREWFLANGE TO SECUREPLUG)
+3.3V +5V
OPEN
SELECT
ADDRESS S3
(2) ROTARY
SWITCHES
D16
*/D15
*/D14
*/D13
W/D12
*/D11
*/D10
* / D9
SP3 / D8
SP2 / D7
SP1 / D6
LK / D5
TD / D4
TC / D3
TB / D2
TA / D1
FP ACK
ALARM
GROUP
ALARM
TYPE
OPEN
8
7
6
5
4
3
2
1
S6
2345
1 7 8
6
OPEN
8
7
6
5
4
3
2
1
S7
2345
1 7 8
6
TEST
COM
SILENCE
REMOTE
SWITCH
TB4
RS 2
PLUG-IN TERMINAL
BLOCK
FRONT PANEL
CABLE
CONNECTOR
(2) LEDS
EDIT EN
SER EN
IMPORTANT! Confirm that the installed TMS/LC2000 console firmware
version su
pp
orts RA400 communications.

RA400 Instruction Manual - 2017-07-30.docx Page 6 of 22 July 30, 2017
1.2 TEST Pushbutton
The TEST pushbutton is used to confirm operation of the front panel audible and visual alarms. For
tank fill operations, TEST should always be used to confirm RA400 operation prior to filling the tank.
1.3 RESET Pushbutton
The RESET pushbutton is used to acknowledge alarm conditions. Note that acknowledging an alarm
condition silences the audible annunciator for all existing alarms, but does not turn off the visual alarm,
which remains active until the alarm condition is removed. The audible alarm will be re-activated for
new alarms.
1.4 Visual Alarm Strobe
The visual alarm strobe is activated upon occurrence of any of the user-programmable tank, sensor,
contact closure or system alarm conditions listed in the Alarm Programming Table in section 3.1.3.
The visual alarm strobe flashes two to three times every six seconds as a result of loss of
communications between the RA400 and TMS/LC2000 console. Note that the visual alarm strobe
remains active until the alarm condition is removed.
1.5 Audible Annunciator
A front panel horn is provided to annunciate both user-selectable alarms as well as communications
failures. The horn can be silenced manually by pressing the RESET pushbutton, automatically by
eliminating the alarm condition, or by programming an audible alarm shutoff. See section 3.1.2 for
audible alarm shutoff delay programming. Under alarm conditions, the beep rate of the annunciator
varies with the alarm type as follows;
Alarm Group
A
larm T
y
pe Beep Rate
Tank
(TMS Only)
Leak Fast
(
50ms
)
SP1 Medium Fast
(
100ms
)
SP2 Medium Slow
(
200ms
)
SP3 Slow
(
400ms
)
Wate
r
Slow
(
400ms
)
Sensor
A
ll Fast
(
50ms
)
Contact Closure
A
ll Slow
(
400ms
)
S
y
stem
A
ll Slow
(
400ms
)
Communications All One Fast Beep every 6
Seconds
ms = milliseconds

RA400 Instruction Manual - 2017-07-30.docx Page 7 of 22 July 30, 2017
1.6 Power Indicator LED
A front panel LED indicator is provided to confirm that the RA400 is being supplied with AC power,
and that the RA400 DC power supply is operational.
1.7 User-Selectable Advisory Pocket Insert
The RA400 front panel includes a 0.8”H x 3.5”L clear pocket window that accepts a pocket insert
displaying alarm description and emergency contact information. Blank inserts and pre-printed
labels are provided for most alarm descriptions. These labels are applied to the blank pocket insert,
which is then installed from the inside of the front cover. Optionally, the users may print their own
labels, or write directly on the pocket insert. If writing directly on the pocket insert, an indelible marker
or other permanent ink method should be used.
DRAWING NO. 20062 REV. N/C
P/ N 313245 - 1 R E V . N/ C
TOP
If Alarm
SoundsCall:
TANK 1 HIGH LE VEL A LAR M
COMPANY ABCINC.
(555)501-0005
INSER T LABEL - P/N 313259-1-2 0
(
SAMPL E L ABE L SH OWN, SEE NO TE BEL O W)
NOTE : 20-LA BEL 8 1/2" X 11" SHEET WITH
BLANK AND PR E-PRI NTED LA BELS
PROVIDED. USE TEMPLATE (ON CD OR
DO W NLO AD F RO M www .pneume rcato r.com )
TO FILL IN AN D PRINT ADVIS OR Y A ND
EMERGENCY CONTACT INFORMATION AS
NEEDE D. LABE L INF ORMA TION M AY ALSO
B E H A N D WR IT T E N .
CARR IER INSE RT - P/N 313245- 1
INSERT W ITH LABEL
INSTALL THRU SLOT
AS SHOWN
INSTALL LABEL ON CARRIER INSERT
TOP
P/ N 313245 - 1 R E V . N/ C
(555)501-0005
COMPA NY A BC IN C.
TANK 1 HIGH LE VE L A LARM
SoundsCall:
If Alarm
OU TSID E C OV ER VIEWINSIDE COV ER VIEW
DANGER! DO NOT assume that failure of the Power Indicator LED to operate
is an indication that the AC connection is not LIVE. The LED will also not
operate if the RA400 fuse has blown, or if the DC supply or LED has failed.
TURN OFF POWER AT THE CIRCUIT BREAKER BEFORE SERVICING!

RA400 Instruction Manual - 2017-07-30.docx Page 8 of 22 July 30, 2017
2.0 Installation
The RA400 is designed for both indoor and outdoor installation. If the unit is to be installed outdoors,
the installer must pay attention to local code requirements for outdoor conduit runs containing AC
line voltage.
2.1 Mounting
The RA400 is designed for wall mounting using the four mounting holes as shown in Figure 2.1-1.
Mounting hole placement is made easy using supplied 1:1 scale mounting template in Figure 2.1-2.
Note that these mounting holes are outside of the gasketed interior of the enclosure and therefore
do not affect weatherproof performance.
Figure 2.1-1
DRAWING NO. 20025 REV. A
19
16 [39]
57
8[149]
73
32 [180]
321
32 [93]
13
16 [20]
35
8[92]
77
8[200]
51
2[140]
DIMENSIONS: INCHES [MM]
213
32 [61]
315
16 [100]
AC POWER
CONDUIT
OPENING
COVER
SHOWN
FOR REF.
(4) MOUNTING
SCREWS
SCREW
ANCHOR
(4)
MOUNTING
HOLES
Ø7
8[Ø22] HOLE TYP. 2 PLS.
FOR 1/2" NPT WATERTIGHT FITTING
OR METRIC EQUIVALENT
COMMUNICATIONS
CONDUIT OPENING
23
32 [53]
WARNING! This device is designed for Ordinary Location, Non-Hazardous
installation only, as defined by Underwriters Laboratories (UL) and the
National Electrical Code (NEC). DO NOT install where flammable vapors may
be
p
resent.

RA400 Instruction Manual - 2017-07-30.docx Page 9 of 22 July 30, 2017
(This page intentionally left blank)

RA400 Instruction Manual - 2017-07-30.docx Page 10 of 22 July 30, 2017
Figure 2.1-2 Mounting Template
DRAWING NO. 20024 REV. N/C
73
32 [180.0]
321
32 [93.0]
USE (4) #10 X 2 " LENGTH
MOUNTING SCREWS
(3/8" MAX. SCREW HEAD DIA.)
DIMENSIONS: INCHES (MM)

RA400 Instruction Manual - 2017-07-30.docx Page 11 of 22 July 30, 2017
(This page intentionally left blank)

RA400 Instruction Manual - 2017-07-30.docx Page 12 of 22 July 30, 2017
2.2 Wiring
2.2.1 AC Power
Wire AC power in accordance with Figure 2.2.1-1 below. Be sure to set 115/230VAC selector switch
to the proper voltage. Note that the AC terminal block can be wired in-place or unplugged.
Figure 2.2.1-1
DWG NO. 20026 REV. A
NEUTRAL
115/230 VAC
SWITCHABLE
115V
115/230 VAC
50/60Hz
AC
IN
HOT
GND
1/2 AMP
250 VAC
FAST
ACTING
FUSE
DANGER! AC power must be turned off at the circuit breaker before
attempting to connect AC wiring to this device.
WARNING! Do not connect or disconnect front panel display cable while
AC power is applied. Damage to display or main board may occur!

RA400 Instruction Manual - 2017-07-30.docx Page 13 of 22 July 30, 2017
2.2.2 Communications
The RA400 supports an RS-485 multi-drop cabling topology as illustrated in Figure 2.2.2-1 below.
Maximum cable distance from the TMS/LC2000 console to the furthest RA400 is 4000 feet (1200M).
Figure 2.2.2-1 TMS Communications Topology
Figure 2.2.2-2 LC2000 Communications Topology
2.2.2.1 Cable Requirements
Cable type should be 24AWG, single twisted pair, shielded, designated for RS-485 communications
having a nominal impedance of 120 ohms.
Recommended Cables:
-4 F to 176 F (-20 C to 80 C) Operation* - Belden 9841 or equivalent
-94 F to 392 F (-70 C to 200 C) Operation* - Belden 89841 or equivalent
*See Section 4.0 Product Specifications for Operating Temperature range limits of the RA400.
DWG NO. 20027 REV. B
PNEU ME RCAT OR
Liqui d Le v el Contro l S y st ems
ET D 1000
EL ECTR ON ICTA NK DISP LA Y
AC
POWER
EL ECTR ON ICTA NK DISP LA Y
ET D 1000
PNEU M E RCAT OR
Liqui d Le v el Contro l S ys te ms
JUNCTION BOX
END-OF-RUN
ETD1000 OR RA400
#2#1
TMS
4000 FEET (1200 M) MAX. DISTANCE
PNEU M E RCAT OR
Liqui d Le v el Contro l S ys te ms
TA NK MA NA GE ME NT SYSTEM
TM S
ETD1000 OR RA400ETD1000 OR RA400
PNEU M E RCAT OR
Liquid Level Control Systems
RE MOTE AN NUNCI AT OR
RA 400
PN E
Liqui d Le v e
RE MOTE AN NUN CI AT OR
RA 400
AC
POWER
AC
POWER
EL EC TR ON IC TA NK DISPL AY
ET D 1000
PN E
Liqui d Le ve
RE MOTE AN N UNCI AT OR
RA 40 0
DWG NO. 20188 REV. N/C
JUNCTION BOX
END-OF-RUN
RA400
#2#1
LC2000
4000 FEET (1200 M) MAX. DISTANCE
PNEUMERCATOR
LiquidLevel Co ntrolS ystems
RA400RA400
PNEUMERCATOR
Liquid Level C on trol Sys tems
REMOTEAN NUNCIATOR
RA 400
AC
POWER
PNEUMERCATOR
Liquid Level C on trol Sys tems
REMOTEANNUNCIATOR
RA 400
AC
POWER
PNEUMERCATOR
Liquid Level C ont rol S y st ems
REMOTEANNUNCIATOR
RA 400
AC
POWER
LC 2000
LEAK/POINTLEVELCONSOLE
IMPORTANT! Use only recommended RS-485 communications cable or
manufacturer’s DOCUMENTED e
q
uivalent.

RA400 Instruction Manual - 2017-07-30.docx Page 14 of 22 July 30, 2017
2.2.2.2 RA400 Terminal Connections
Plug-in terminal blocks TB2 and TB3 are provided for connection to the RS-485 Expansion Bus.
Both input and output terminals are provided to support multi-drop wiring to additional RA400s or
other RS-485 expansion bus peripherals.
2.2.2.3 RA400 Communications Wiring Detail
See Figure 2.2.2.3-1 below.
Figure 2.2.2.3-1 RA400 Communications Wiring
DRAWING NO. 20033 REV. N/C
O
U
T
I
N
RS-485
C
O
MMS.
CH. A (+)
CH. B (-)
SHIELD
3BT2BT
DWG NO. 20028 REV. A
WHT/BL
BL/WHT
SHD
END-OF-RUN
"ON"FOR
END-OF-RUN ONLY
LINE TERMINATOR
OFF
ON
SHIELD
CH. B (-)
CH. A (+)
RS-485 COMMS.
I
N
O
U
T
WHT/BL
BL/WHT
SHD
1/2" NPT FITTING
AND CONDUIT
(EACH ETD1000/RA400)
TO TMS RS-485
COMMS.
"OFF" POSITION
TO ADD ANOTHER
ETD1000/RA400
2 CONDUCTOR SHIELDED
RS-485 COMM. CABLE
"ON"FOR
END-OF-RUN ONLY
LINE TERMINATOR
OFF
ON
SHIELD
CH. B (-)
CH. A (+)
RS-485 COMMS.
I
N
WHT/BL
BL/WHT
SHD
"ON" POSITION
FOR LAST
ETD1000/RA400
O
U
T

RA400 Instruction Manual - 2017-07-30.docx Page 15 of 22 July 30, 2017
2.2.2.4 RS-485 Communications Wiring Detail
Current version TMS/LC2000 consoles have the same type of plug-in terminal connector and wiring
designations as the RA400, as illustrated in Figure 2.2.2.4-1 below. Previous versions have a 6-
position modular jack. If the board type is a previous version, you will need to replace it with a current
revision board. Please contact the factory for more details.
Figure 2.2.2.4-1 RS-485 Communications Connection, Current Version Boards
DRAWING NO. 20189 REV. N/
C
RS-485 COMMS.
3 POSITION
TERMINAL BLOC
K
3/4" NPT
FITTING AND
CONDUIT
1/2" NPT
FITTING AND
CONDUIT
RS-485 COMMS.
3 POSITION
TERMINAL BLOCK
– – OR – – TMS3000/TMS4000LC2000/TMS2000
ISGND
GND
NEUT
ISGND
HOT
ISGND
GND
NEUT
ISGND
HOT
RS-485
COMMUNICATIONS I/O
CH. B (BL/WHT)
SHD (SHIELD)
CH. A (WHT/BL)
CH. B (BL/WHT)
CH. A(WHT/BL)
SHD (SHIELD)
RS-485
COMMUNICATIONS I/O

RA400 Instruction Manual - 2017-07-30.docx Page 16 of 22 July 30, 2017
2.2.2.5 Line Termination Resistor
The RS-485 bus requires that the end-of-run device be terminated with a 120-ohm resistor. This is
accomplished by setting the LINE TERMINATION switch to “ON” if the selected RA400 is the last
device on the bus. Otherwise this switch should be set to “OFF”.
2.2.3 RS-2 Remote TEST/RESET Wiring
A connection is provided to externally TEST and RESET the RA400 using a Pneumercator model
RS-2 Remote TEST/RESET Switch Assembly or similar device having NORMALLY OPEN contacts.
Note that the front panel TEST and RESET pushbuttons remain active when wired for external
operation.
Figure 2.2.3-1 RS-2 Remote TEST/RESET Wiring
DRAWING NO. 20034 REV.
A
S2
"ON" FOR
END-OF-R UN ONLY
LINE TERMINATO R
OFF
ON
DRAWING NO. 20063 REV. A
1/2" NPT FITTING
AND CO NDU IT 3 CONDUCTOR 22 AWG CABLE
BELDEN 8443 OR EQUIV.
(NOTE: BELDEN CO LORS SHO WN )
REMOTE
SWITCH
SILENCE
COM
TEST
R
E
D
B
L
K
G
R
N
COVER
RESET
TEST
RA400 / RA400W
RED
BLACK
GREEN
RS-2
200 FEET (60 M) MAX. DISTANCE
1/2" NPT FITTING
AND CO NDU IT

RA400 Instruction Manual - 2017-07-30.docx Page 17 of 22 July 30, 2017
3.0 Configuration
The RA400 provides user-programmable features that allow the operator to alter audible/visual
alarm operation as well as control interaction with the TMS/LC2000 for remote alarm
acknowledgement. These programmable features are selectable using on-board dipswitches. No
programming is required at the TMS/LC2000 console.
3.1 On-Board Programming
3.1.1 Setting Logical Address – S3
The TMS/LC2000 has the ability to individually address up to sixteen (16) RA400 remote displays.
Rotary dipswitch S3 is used to select unique addresses for each RA400 connected to the same
TMS/LC2000. Note that address order is not important, and that RA400 device addresses are
independent of other TMS/LC2000 smart peripheral types. For example, an RA400 set to device
address “4” will not conflict with an ETD1000 also set to device address “4”.
Table 3.1.1-1 S3 Assignments
DRAWING NO. 20064 REV. A
S3
ADDRESS
SELECT
S3 RA400
Address
Select
Device
A
ddress
01
12
23
34
45
56
67
78
89
9 10
A
11
B 12
C 13
D 14
E 15
F 16

RA400 Instruction Manual - 2017-07-30.docx Page 18 of 22 July 30, 2017
3.1.2 Setting Shutoff Delay – S4
The RA400 provides the user with selectable automatic shutoff delays for the audible alarm. Once
initiated, the audible alarm will turn off after the selected time delay has elapsed, or immediately if
acknowledged at the front panel. This feature is useful in applications where continued operation of
an unacknowledged audible alarm poses a nuisance or noise abatement problem.
Table 3.1.2-1 S4 Assignments
DRAWING NO. 20065 REV. A
DELAY
SHUTOFF
S4
S4 RA400
Shutoff
Select
Shutoff Delay
(
Minutes
)
0NONE
11
22
33
44
55
66
77
88
99
A
10
B 11
C 12
D 13
E 14
F 15
WARNING! Use this feature only if an unacknowledged alarm will not
pose a potential safety or environmental hazard.

RA400 Instruction Manual - 2017-07-30.docx Page 19 of 22 July 30, 2017
3.1.3 Alarm Programming - S5(1-5), S6, S7
The RA400 alarm programming provides the user with considerable flexibility in the selection of
which alarms it is to annunciate. Referring to Table 3.1.3-1 below, the Alarm TYPE dipswitches
allow the user to select between four types of alarms; TANK, SENSOR, CONTACT CLOSURE and
SYSTEM. For each alarm type, the Alarm GROUP dipswitches allow the user to select a tank,
sensor or contact closure group, for example, tanks 1 thru 4, 5 thru 8, 9 thru 12, etc., or all tanks.
The user can further select individual devices within the selected Alarm GROUP. The TANK and
SYSTEM alarm types also provide specific alarm selections as indicated in Table 3.1.3-1 below.

RA400 Instruction Manual - 2017-07-30.docx Page 20 of 22 July 30, 2017
Table 3.1.3-1 Alarm Programming
ALARM PROGRAMMING
SWITCH S5 SWITCH S6 SWITCH S7
1 2 3 4 51 2 34 5 6 7 8 12345678
Type Group Tank Selec ts Tank Alarm Selects
C C C C CT1 T2T3T4LEAKSP1SP2SP3* * * W * * * -
C C C C OT5 T6T7T8LEAKSP1SP2SP3* * * W * * * -
C C C O C T9 T10 T11 T12 LEAK SP1 SP2 SP3 * * * W * * * -
C C C O O T13 T14 T15 T16 LEAK SP1 SP2 SP3 * * * W * * * -
C C O C C T17 T18 T19 T20 LEAK SP1 SP2 SP3 * * * W * * * -
C C O C O T21 T22 T23 T24 LEAK SP1 SP2 SP3 * * * W * * * -
C C O O C Select All Tanks LEAK SP1 SP2 SP3 * * * W * * * -
C C O O O Select All Tanks LEAK SP1 SP2 SP3 * * * W * * * -
Type Group Leak/Point Level Sensor Selects
C O C C CS1 S2S3S4 S5 S6S7S8S9 S10 S11 S12 S13 S14 S15 S16
C O C C O S17 S18 S19 S20 S21 S22 S23 S24 S25 S26 S27 S28 S29 S30 S31 S32
C O C O C S33 S34 S35 S36 S37 S38 S39 S40 S41 S42 S43 S44 S45 S46 S47 S48
C O C O O S49 S50 S51 S52 S53 S54 S55 S56 S57 S58 S59 S60 S61 S62 S63 S64
C O O C C S65 S66 S67 S68 S69 S70 S71 S72 S73 S74 S75 S76 S77 S78 S79 S80
C O O C O S81 S82 S83 S84 S85 S86 S87 S88 S89 S90 S91 S92 S93 S94 S95 S96
C O O O CSelect Al l Leak/Point Level Sensor s (S6, S7 settings do not apply)
C O O O O Select All Leak/Point Level Sensors (S6, S7 settings do not apply)
Type Group Contact Closure Input Selects
O C C C CC1 C2C3C4 C5 C6C7C8C9 C10 C11 C12 C13 C14 C15 C16
O C C C O C17 C18 C19 C20 C21 C22 C23 C24 C25 C26 C27 C28 C29 C30 C31 C32
O C C O C C33 C34 C35 C36 C37 C38 C39 C40 C41 C42 C43 C44 C45 C46 C47 C48
O C C O O C49 C50 C51 C52 C53 C54 C55 C56 C57 C58 C59 C60 C61 C62 C63 C64
O C O C C Select Al l Contact Closure Inputs (S6, S7 settings do not apply)
O C O C O Select All Contact Closure Inputs (S6, S7 settings do not apply)
O C O O C Select All Contact Closure Inputs (S6, S7 settings do not apply)
O C O O O Select All Contact Closure Inputs (S6, S7 settings do not apply)
Type Group System Alarm Selects
O O C C CTD PF SF - - - - - -----TK SR CC
“TD” = Theft Detect, “PF” = Probe Failure, “SF” = Sensor Fault
“TK” = Any Tank Alarm, “SR” = Any Sensor Alarm, “CC” = Any Contact Closure Alarm
Notes
“O” = OPEN
“C” = CLOSE
An alarm select is ACTIVE when the corresponding switch is OPEN.
“*” = Future Use, “-“ = Not Applicable or Don’t Care
Table of contents
Other Pneumercator Security System manuals
Popular Security System manuals by other brands

Klaxon
Klaxon Nexus Pulse 110 installation instructions

Yale
Yale HSA6200 quick guide

Panasonic
Panasonic BB-HGW700A - Network Camera Router operating instructions

Home Automation
Home Automation 10A11-1 installation manual

CrimeStopper
CrimeStopper RS901 RS900ER operating instructions

Politec
Politec PARVIS MES SMA Series manual

American Dynamics
American Dynamics AD2010N Information sheet

Alert Tech
Alert Tech EasyAssist EA200 uhf user guide

Bay Alarm Medical
Bay Alarm Medical In-Home Medical quick start guide

LifeShield
LifeShield Home Security Quick setup guide

VSAIL
VSAIL VB-6617S Installation and operation manual

Amcrest
Amcrest WLD895 user manual