TMS Quick Reference.doc Page 1 of 2 July 1, 2009
TMS Quick Reference Guide
Alarm LEDs* Display Mode LEDs
LEAK – In-Tank / Sensor GAL – Gross Volume (Gallons)
Net Volume (with ºF LED on)
SP1 – Above 95% (High High) %GAL – Percent of Capacity
SP2 – Above 90% (High) ULL – Ullage Vol (Gallons, Default 90%)
SP3 – Below 20% (Low) IN – Product Level (Inches)
Water Level (with “u” symbol, inches)
WATER – Above 2” ºF – Product Temperature (ºF)
Front Panel Buttons
PAPER FEED PRINT MODE TANK SELECT TEST
Press to advance Press for Current Press to display tank name. Press to select tank Press to test
paper Inventory / Sensor Press and hold until beep Press and hold until display and
Status report to select display mode beep for autoscan horn
STEP GROUP SELECT EDIT
Current Inventory / Sensor Status Report: Press PRINT button.
* If an alarm LED is blinking, an active tank alarm is present on a tank(s) not currently being displayed. When
an alarm LED is on continuously, it applies to the currently displayed tank. Note that this alarm may apply to
more than one tank, which can be determined by viewing each tank with the TANK SELECT button.
Site Name Tech Support Phone
Site Location Emergency Phone
Audible Alarm
Acknowledgment
To silence an alarm,
press any of the right
three buttons. The visual
indicator will remain
active as long as the
alarm condition persists.
A theft alarm can only
be silenced by pressing
the ACKNOWLEDGE
pushbutton located on
the inside of the front
door.
Visual Alarm
Acknowledgment
The only visual alarms
that can be cancelled
are failed in-tank leak
test and no monthly in-
tank leak test. These
visual alarms are
deactivated by pressing
the ACKNOWLEDGE
pushbutton located on
the inside of the front
door. All other visual
alarms are persistent