PolyGard MGC2-20 User manual

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
November 19, 2013 – Revision
Polygard® is a registered trademark of MSR MGC2-20
PolyGard Controller MGC2-20
Multi-Point Controller
Serial Number – S00
User Manual
September 29, 2011

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 02
1Description ............................................................................................................................................. 4
2 Operating Instruction ............................................................................................................................ 5
2.1 Description Keypad User Interface ................................................................................................... 5
2.2 Setting / Change Parameters ........................................................................................................... 5
2.3 Password Level ................................................................................................................................ 6
3 Menu Overview ...................................................................................................................................... 7
3.1 Malfunction management ................................................................................................................. 8
3.1.1 Acknowledge a malfunction ....................................................................................................... 8
3.1.2 History error summary ............................................................................................................... 8
3.1.3 System Errors ............................................................................................................................ 9
3.2 Stage Status ..................................................................................................................................... 9
3.3 Relay Status ..................................................................................................................................... 9
3.3.1 Manual operation of the relays ................................................................................................ 10
3.4 Menu Sensor Readings .................................................................................................................. 10
3.5 Menu Relay Setup .......................................................................................................................... 11
3.5.1 Relay Mode ............................................................................................................................. 11
3.5.2 Relay Action Steady / Flash ..................................................................................................... 11
3.5.3 Latching Mode ......................................................................................................................... 12
3.5.4 Horn Function .......................................................................................................................... 12
3.5.5 External operation of Relay. .................................................................................................... 13
3.5.6 Delay operation of Relay. ........................................................................................................ 13
3.6 Menu SP Setup .............................................................................................................................. 14
3.6.1 Activate – Deactivate SP ......................................................................................................... 15
3.6.2 Selection Type ......................................................................................................................... 16
3.6.3 Measuring range...................................................................................................................... 16
3.6.4 SP Signal ................................................................................................................................. 16
3.6.5 Stage/Setpoint / Hysteresis ..................................................................................................... 17
3.6.6 Delay time ON or OFF ............................................................................................................. 17
3.6.7 Control Mode ........................................................................................................................... 17
3.6.8 Assigned SP Fault to Relay ..................................................................................................... 17
3.6.9 Assign Relay to a Stage .......................................................................................................... 18
3.6.10 Assigned SP Signal to analog Output ...................................................................................... 18
3.7 Menu System Setup ....................................................................................................................... 19
3.7.1 Service Mode .......................................................................................................................... 20
3.7.2 Software Version ..................................................................................................................... 21
3.7.3 Maintenance Concept .............................................................................................................. 21
3.7.4 Average Value Function .......................................................................................................... 21
3.7.5 Time, Date ............................................................................................................................... 21
3.7.6 Customer Password (Code 1) ................................................................................................. 22
3.7.7 Analog Output ......................................................................................................................... 22
3.7.8 Define the Failure Relay .......................................................................................................... 22
3.7.9 Power On Time ....................................................................................................................... 22
3.7.10 Activation of expansions modules............................................................................................ 23
4 Mounting / Electrical Connection ....................................................................................................... 24
4.1 Electrical Connection ...................................................................................................................... 24
4.2 Unit position – Connection diagram ................................................................................................ 25

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 03
5 Start-up Operation ............................................................................................................................... 29
5.1 Start-up ........................................................................................................................................... 29
5.2 Checklist Start-up operation ........................................................................................................... 30
6 Configuration- and Parameter card .................................................................................................... 31
6.1 Configurations System Setup ......................................................................................................... 31
6.2 Relay Setup .................................................................................................................................... 32
6.3 Sensor Setup .................................................................................................................................. 33
7 Specifications MGC2-20 ...................................................................................................................... 34
8 Notes and General Information ........................................................................................................... 36
8.1 Intended product application ........................................................................................................... 36
8.2 Installers` responsibilities ................................................................................................................ 36
8.3 Maintenance ................................................................................................................................... 36
8.4 Limited warranty ............................................................................................................................. 36

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 04
Multi Point Controller MGC2
1 Description
The PolyGard® Multi Point Controller MGC2 is used for the monitoring and warning of sensor points exceeding
their stage setpoints. External Transmitters can monitor and warn of toxic, combustible and refrigerant gases as
well as temperature and humidity. The Controller MGC2 can measure up to twenty analog 4 to 20 mA (Gas)
Transmitters.. Each Sensor Point (SP) can have five stage thresholds. Each stage threshold can be assigned to
anyone of the relays (R1…R20). The Controller can interface via ten 4 to 20 mA outputs to any compatible
electronic analog control, DDC/PLC control or automation system.
The adjustable parameters and staged thresholds make this system very flexible for sensor measuring and
control.
The configuration of parameter settings and operation is easy to do without any programming knowledge.
PolyGard® Multi Point Controller MGC2 must not be used in areas requiring explosion proof equipment.

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 05
2 Operating Instruction
The complete configuration, parameterization and service are made via the keypad user interface in combination
with the display screen. Security is provided via two password levels.
2.1 Description Keypad User Interface
Exits programming and saves settings, returns to the previous menu level.
Enter sub menus, stores changed values.
Scrolls down & up in Main menu and Sub menus, increases or decreases a value.
Moves cursor left or right.
LED yellow Flashes when one or more stages have been exceeded or steady if the operator has manually
overridden any relays.
LED red: Flashes when a System or Sensor Failure is detected or when the Maintenance Date is needed.
2.2 Setting / Change Parameters
Desired menu window open.
Opens menu window, if the password is approved the cursor jumps to the first segment
position
Moves the cursor right or left to a segment position
Changes the parameter or value
Saving the changed parameter or value.
Finish
Fault
A
larm
INTEC Controls
01.22.05 10:28 am

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 06
2.3 Password Level
All changes of parameters and staged setpoint values are protected by four digit numeric Code (= password).
The code level 1 permits the operation of the MGC2. This code level is intended for the customer. It can be
changed in the System Setup Menu “Change Customer Password”
With the code level 2 all parameters and set points can be changed, this code level is reserved for the service
technician.
A password must be re-entered if there is 15 minutes of inactivity.
All menu windows are visible without a password.
Factory preprogrammed system password "9001".

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 07
3 Menu Overview
The Multi-Point Controller MGC2 is operated via a simple and logical menu structure which is easy to learn. The
operating menu contains the following levels:
● StartingmenuwithdateandtimeifnoSPisregistered,otherwisescrollingdisplayofthegasconcentrations
of all registered transmitters in 5-second intervals
● Mainmenu
● Submenu1and2
Reading and reset of errors
See Section 3.1
System Errors
Display of the status of actual alarms
See Section 3.2
Stage Status
Reading and change of the system parameters
See Section 3.7
System Setup
Display of the relay status
Manual operation of the relays
Reset function of the relays
See Section 3.3
Relay Status
Display of the sensor values
See Section 3.4
Sensor Readings
Reading and change of the relay parameters
See Section 3.5
Relay Setup
Reading and change of sensor point parameters
Activate or Deactivate SP
Assignment of the alarms to the alarm relay
See Section 3.6
SP Setup
Not applicable to standard MGC2 controllers;
available as a special order option
Data Logger
Starting menu Sub menuMain menu
After 30 sec.
or
INTEC
10.23.13 12:53
Power On Time Display of
Gas concentration

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 08
SP 01 < 3mA
Error Cleared
Error still
exists
3.1 Malfunction management
Malfunction management records the last 15 malfunctions with date and time stamps. In addition, “System Errors”
are recorded in “Error Memory” when the malfunction occurs. This history can be selected and cleared only by the
service technician level 2 password.
A malfunction will display a text message in the Starting Menu. When a failure occurs the relay defined in the
system setup as “Failure relay” is activated. The red LED in the front of the Controller flashes.
During the malfunction of a sensor point (SP) stages that are assigned for sensor failure are activated. Relays that
are assigned to these stages perform as if the stage has been exceeded. These assignments are programmed in
the menu “SP Setup”.
3.1.1 Acknowledge a malfunction
Note:
Resetting a malfunction is only possible if the problem is corrected.
Select Menu “System Errors”
Example: Failure SP 01 < 3 mA
Malfunction Reset?
Malfunction Reset
or
Malfunction Cleared Problem not corrected
Reset not possible
3.1.2 History error summary
The code level 2 password can open the menu “Hist Error Sum” in the main menu “System Errors”.
The last 15 error messages are listed for the service technician even if they have already been reset. These error
messages can be deleted individually
System Errors
SP 01 < 3mA
05.02 10.38
SP 01 < 3mA
Reset ??

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 09
SP 01
S1 S2
R 01
OFF
3.1.3 System Errors
System Error Messages:
SP XX > 22 mA Current signal at analog Input XX > 22 mA.
Cause: Short-circuit at analog Input or Transmitter not calibrated, Transmitter defective.
Solution: Check cable to Transmitter, Perform Calibration, Change the Transmitter.
SP XX < 3 mA Current signal to analog Input XX < 3 mA.
Cause: Open circuit at analog Input or Transmitter not calibrated, Transmitter defective.
Solution: Check cable to Transmitter, Perform Calibration, Change the Transmitter.
GC Error: Internal Communication Error I/O Board to LCD Board.
Cause: Internal Error.
Solution: Change the Controller.
EP 0X Com Error: Communication error to expansion module (EP 0X).
(Only active, if EP module announced).
Cause: EP module address not correct. (See Start up Operation 5.0)
Bus cable to EP 0X module disconnected.
No power supply at the EP 0X module.
EP module defective.
Solution: Check the EP module address.
Check the bus cable and the power supply.
Change the EP 0X module.
Maintenance: System maintenance is necessary.
Cause: Maintenance date exceeded.
Solution: Perform maintenance.
3.2 Stage Status
Displays the actual stages exceeded in the sequence that they happen. The sensor point displays with the stages
that have been exceeded. Changes can not be made in this menu.
Symbol Description Function
SP 01 Sensor Point
(
SP
)
No.
SX Stage Status
S1 = Stage 1 ON
S2 = Stage 2 ON
S3 = Stage 3 ON
S4 = Stage 4 ON
S5 = Stage 5 ON
3.3 Relay Status
Display the actual status of each relay and changes can be made for manual operation of the relays.
Symbol Description Setting
Status Function
R 01 Relay No. 01 Select Relay No.
OFF Status Relay OFF
OFF
ON
Manual OFF
Manual ON
= Relay Off (Not Activated by Stage Setpoint)
= Relay On (Activated by Stage Setpoint)
= Relay manual Off
= Relay manual On

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 10
SP 01 NH3 ppm
50 *AV 33 CV
3.3.1 Manual operation of the relays
The manual operation of the relays can be accomplished in the menu “Relay Status”. If a relay is in the Manual ON
or Manual OFF status, the yellow LED at the Controller is on continuously.
The external operation of a relay by an assigned digital input has priority before the manual operation or the Stage
set point of a sensor point being exceeded.
Manually operated relays can be reset by selecting the “Automatic” mode.
The reset of Latching relays also is a function in this menu.
Select Relay
Select Function Manual operation
Manual ON = Relay ON
Select Function Manual OFF = Relay OFF
Automatic = Automatic operation restored
Reset ? = Reset of latched relay
Relay forced to OFF Condition
3.4 Menu Sensor Readings
In this menu it displays the current value (CV) and average value (AV) with sensor unit and type for each active
sensor point (SP) as well as the defined mode of control (CV or AV mode) with “*” .
Symbol Description Setting
Status Function
SP 01 Sensor Point
No. Select SP No.
NH3 Type NH3 See 3.6.2
ppm Unit See 3.6.2
CV Current value CV Current value of Gas Concentration
AV Average value Average value (10 measured values within the time unit)
* Control mode Display for the Control mode selected. (CV or AV)
Not active SP Status Not active SP disabled
Error SP Malfunction Current signal < 3 mA or > 22 mA
R 01
OFF
Manual ON
Manual OFF
Manual OFF

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 11
3.5 Menu Relay Setup
Display and change the parameters for each relay.
(Main menu)
(Selection Relay No.)
Relay Mode
See 3.5.1
Relay Function
See 3.5.2
Activate Latching Mode
See 3.5.3
Definition of Horn Functions
See 3.5.4
Definition of external Relay Operation
See 3.5.5
Set Delay ON time
See 3.5.6
Set Delay OFF time
See 3.5.6
3.5.1 Relay Mode
Symbol Description Setting
Status Function
R 01 Relay No. Selection Relay
De-
energized Relay Mode De-
energized
De-energized
Energized
= Stage ON = Relay ON
= Stage ON = Relay OFF
3.5.2 Relay Action Steady / Flash
Symbol Description Setting
Status Function
R 01 Relay No. Selection Relay
0 Function 0
0 = Relay Function steady
> 0 = Relay Function flashing (= Periods time sec.)
Impulse / Break = 1:1
Relay Mode
De- energized
Steady / Flash
0 s
Relay Setup
R 01
Latching mode
No
Time Reset DI
0s 0 0
External mode
DI: ON = 0: OFF = 0
Delay ON time
0 s
Delay OFF time
0 s

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 12
3.5.3 Latching Mode
Definition of Latching Function
Symbol Description Setting
Status Function
R 01 Relay No. Selection Relay
No Latching Mode No No
Yes
= Latching Mode non active
= Latching Mode active
Acknowledging of a latching relay in the menu “Relay Status” is possible only if the sensor value is smaller than
the Staged set point including hysteresis. With this condition then latching is activated.
Example: Relay R2 assigned to Latching mode
Alarm 2
Display in the Menu
Status Relay
Relay 2
Reset in the Menu
Status Relay
On
Off
On
Off
On
Off
R2
Off
R2
On
R2
On
R2
On
R2
Latching
R2
Off
Gas Concentration greater smaller as Threshold
3.5.4 Horn Function
With this parameter the relay is defined as a horn relay and can be acknowledged with the following possibilities.
By pressing one of the arbitrary 6 pushbuttons. (Only possible in the starting menu).
Automatic acknowledging when the time runs out.
By an external pushbutton. (Assigned to an appropriate digital input).
The horn function is activated only if at least one of the two parameters (time or digital input) is set.
Special function Response
After acknowledging the relay via Pushbutton or external DI the time starts. If this time runs out and if the stage is
still exceeded, the relay is energized again.
Symbol Description Setting
Status Function
R 20 Relay No. Selection Relay
Reset Mode 0
0 = Acknowledge the relay at time run out, or via Pushbutton
1 = Acknowledge the relay via a Pushbutton, after time runs out
and the alarm is still active, then the relay is reactivated.
Time 120 Time in seconds for Automatic acknowledging or before
reactivating alarms defined by Reset function
DI 0 Assignment of the digital input used for remote reset of the horn.

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 13
Acknowledge the horn relay
Alarm 4
Relay 4
Gas Concentration greater smaller as Threshold
Acknowledging
signal
On
Of
On
Off
On
Off
Time
Special function “Response”. (Return of the horn relay)
Alarm 4
Relay 4
Gas Concentration greater smaller as Threshold
Acknowledging-
signal
On
Off
On
Off
On
Off
Time Time
3.5.5 External operation of Relay.
Assign one digital input (DI) for external setting of the relay ON and/or OFF. This function has priority before a
stage threshold is exceeded and/or manual switching in the menu “Relay Status”.
Symbol Description Setting
Status Function
R 01 Relay No. DI Selection Relay
DI-ON External On 0 If digital input closed, relay switch ON
DI-OFF External Off 0 If digital input closed, relay switch OFF
3.5.6 Delay operation of Relay.
Delay ON time begins when the Stage is exceeded and/or Delay OFF time when the Stage returns to normal
condition.
Symbol Description Setting
Status Function
R 01 Relay No. Selection Relay
0 s Delay Time ON 0 Stage ON: Relay is only activated at expiration of the defined
time (sec.) 0 sec. = No Delay
0 s Delay Time OFF 0 Stage OFF: Relay is only deactivated at expiration of the defined
time (sec.) 0 sec. = No Delay

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 14
3.6 Menu SP Setup
Display and Change Parameters, Assign Stage value, Assign relays to stages and activate each Sensor Point
(SP).
(Main Menu)
(Selection of a sensor point)
Activate or deactivate SP
See 3.6.1
Define Type
See 3.6.2
Define Measuring range
See 3.6.3
Define signal type of transmitter
See 3.6.4
Define Stage/Setpoint 1
See 3.6.5
Define Stage/Setpoint 2
See 3.6.5
Define Stage/Setpoint 3
See 3.6.5
Define Stage/Setpoint 4
See 3.6.5 Stage/Setpoint
Define Stage/Setpoint 5
See 3.6.5
Hysteresis
See 3.6.5
Set Delay ON time
See 3.6.6
SP Mode
active
SP Type
NH3
SP Setup
SP 01
active
Measuring range
300 ppm
SP-Signal
linear
Stage 1
100 ppm
Stage 2
100 ppm
Stage 3
200 ppm
Stage 4
200 ppm
Stage 5
300 ppm
Hysteresis
15 ppm
Delay ON time
0 s

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 15
Set Delay OFF time
See 3.6.6
Define Control Mode
See 3.6.7
Assign a SP Fault to a Stage
See 3.6.8
Assign a relay to a Stage
See 3.6.9
Assign SP signal to a Analog Output
See 3.6.10
3.6.1 Activate – Deactivate SP
Symbol Description Setting
Status Function
SP 01 Sensor point Selection SP No. (SP01 is the internal Transmitter)
Active SP Status not
active
active = Sensor point enabled for reporting
not active = Sensor point disabled for reporting
Delay OFF time
0 s
AV Mode
CV
Stage - 1 2 3 4 5
Fault - 1 1 0 0 0
S1; S2; S3; S4; S5;
01; 02; 03, 04; 05;
Analog Output
0

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 16
3.6.2 Selection Type
Assign sensor Type to active transmitters.
Symbol Description Setting
Status Type Unit Measuring
range1
SP 01 Sensor point
NH3 Type NH3
CO
Ex
NO
NO2
NH3
O2
CO2
SO2
H2S
CL2
ETC
VOC
R401
R402
R408
R409
R404
R416
R502
R410
R411
R11
R123
R134
R22
TEM
RH
Carbon monoxide
Combusible gas
Nitrogen oxide
Nitrogen dioxide
Ammonia
Oxygen2
Carbon dioxide
Sulphur dioxide
Hydrogen sulphide
Chlorine
Ethylene oxide
Air quality
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Temperature
Humidity
ppm
%LEL
ppm
ppm
ppm
%V/V
ppm
ppm
ppm
ppm
ppm
%
ppm
ppm
ppm
ppm
ppm
ppm
ppm
ppm
ppm
ppm
ppm
ppm
ppm
°C
% RH
0 – 300
0 – 100
0 – 50
0 – 25
0 – 300
0 – 25
0 – 2000
0 – 100
0 – 200
0 – 100
0 – 20
0 – 100
0 – 2000
0 – 2000
0 – 2000
0 – 2000
0 – 300
0 – 300
0 – 300
0 – 300
0 - 300
0 – 300
0 – 300
0 – 300
0 – 300
0 – 150
0 – 100
1 Range Recommendations for PolyGard sensors
2 During oxygen measurement falling signal!
3.6.3 Measuring range
The measuring range can be defined from 10 to 10000. The measuring ranges in the above table are typical and
only recommendations. For actual ranges see the sensor manufacturing specifications.
The measuring range must agree with the signal (4 to 20 mA) for active transmitters.
(4 mA = Display=0, 20 mA = Display Measuring range = max. point)
3.6.4 SP Signal
Gas transmitter with electro-chemical or catalytic bead sensors are linear for gas concentration proportional to the
4 to 20 mA signal.
Semiconductor gas sensors that are not linear and have a (exponential) signal. This signal is non-linear 4 to 20
mA signal from the gas transmitter.
The Controller MGC2 has the capability to monitor both types of gas transmitters, and other linear 4-20 mA
sensors. The type of signal is defined in this menu.
Symbol Description Setting
Status Function
SP 01 Sensor Point Selection SP No.
Linear SP Signal linear linear = Transmitter with linear Output signal
not linear = Transmitter with non linear Output signal (future).

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 17
3.6.5 Stage/Setpoint / Hysteresis
Each sensor point can have five stages with set point values. If the measured level is greater than the defined
stage/set point, the associated stage is set. If the level falls below the stage/setpoint plus the hysteresis then the
stage returns to original condition.
It is recommended that the unused stages be set to max of sensor range to avoid the alarm light from false
reporting.
For O2 measurement on depletion consider when defining stage setpoints that stages will be set on a falling
measuring signal!
Symbol Description Default
Status Function
SP 01 Sensor Point Selection SP No.
100
ppm Threshold
100
100
200
200
300
15
Stage/setpoint1
Stage/setpoint2
Stage/setpoint3
Stage/setpoint4
Stage/setpoint5
Hysteresis
Sensor Value > Stage/Set point1 = Stage 1
Sensor Value > Stage/Set point1 = Stage 2
Sensor Value > Stage/Set point1 = Stage 3
Sensor Value > Stage/Set point1 = Stage 4
Sensor Value > Stage/Set point1 = Stage 5
Sensor Value < (Stage/Set pointX –Hysteresis)
= Stage X OFF
3.6.6 Delay time ON or OFF
Delay ON time begins when the Stage is exceeded and/or Delay OFF time when the Stage returns to normal
condition.
Symbol Description Default
Status Function
SP 01 Sensor point Selection SP No.
0 s Delay Time ON 0 Concentration > Stage Threshold: Relay is only activated at
expiration of the defined time (sec.). 0 sec. = No Delay
0 s Delay Time OFF 0 Concentration < Stage Threshold: Relay is only deactivated at
expiration of the defined time (sec.). 0 sec. = No Delay
3.6.7 Control Mode
Definition of the alarm evaluation by Current value (CV) or Average value (AV).
Symbol Description Default
Status t Function
SP 01 Sensor Point Selection SP No.
CV Evaluation CV CV = Control the Current value
AV = Control the Average value
Current / Average Value Function See: 3.7.4
3.6.8 Assigned SP Fault to Relay
Define which stages are activated with a failure of the sensor point.
Symbol Description Default
Status Function
SP 01 Sensor Point Selection SP No.
Stage - 1 2 3 4 5
Fault - 1 1 0 0 0 Failure SP 1 1 0 0 0 0 = Stage not ON at SP Failure
1 = Stage ON at SP Failure

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 18
3.6.9 Assign Relay to a Stage
Any of the 5 Relays can be assigned freely to any Stage. Stages that do not activate relays receive an
assignment of 00.
Symbol Description Default
Status Function
SP 01 Sensor Point Selection SP No.
1
S1
S2
S3
S4
S5
01
02
03
00
05
01 = Stage 1 activate relay R 01
02 = Stage 2 activate relay R 02
03 = Stage 3 activate relay R 03
00 = Stage 4 does not activate a relay
05 = Stage 5 activate relay R 20 (internal horn)
3.6.10 Assigned SP Signal to analog Output
The sensor point signal can be assigned to one of the ten analog Outputs. The signal defined in the control
mode (Current Value or Average Value) is transmitted.
Analog output see also: 3.7.2
Symbol Description Default
Status Function
SP 01 Sensor Point Selection SP No.
0 A 0
0 = SP Signal not assigned to any analog output
1 = SP Signal assigned to analog output 1
X = SP Signal assigned to analog output X

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 19
3.7 Menu System Setup
Display and change the System Parameters for the Controller
(Main Menu)
See 3.7.1
See 3.7.2
See 3.7.3
See 3.7.3
See 3.7.4
See 3.7.4
See 3.7.5
See 3.7.5
See 3.7.5
See 3.7.6
See 3.7.8
See 3.7.9
Software Version
GC02- XX
Next maint. Date
MM.DD.YY
System Setup
Service Mode
OFF
Service Phone
858 578-7887
AV Overlay
0 s. 120 ppm
AV Time
1800 s
Time system
US
Date
MM.DD.YY
Customer Pass
Change ****
Failure Relay
19
Power On Time
30 s
Time
hh:mm:ss

Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR MGC2-20
PolyGard®Multi-Point Controller
User Manual - MGC2-20 Page 20
See 3.7.10
See 3.7.10
See 3.7.10
See 3.7.10
See 3.7.10
Controller address
(Reserved for future expansion; value should be left at “1”)
See 3.7.7
See 3.7.7
Siehe See 3.7.7
See 3.7.7
See 3.7.7
3.7.1 Service Mode
If the Service mode is set to (ON) then the stage/setpoints are disabled so relays are not activated during
calibration or service work. The service mode is Reset automatically after 60 minutes or when the service mode is
set to Off.
Symbol Description Default
Status Function
Off Service Mode Off Off = Stages exceeded will activate the assigned relays
On = Stages exceeded will not activate the assigned relays
EP Module 1
active
EP Module 2
active
EP Module 3
active
EP Module 4
active
EP Module 5
Not active
Analog Output 1
Max.
Calibration AO 1
4.0=4 mA 20 = 20.0
Analog Output XX
Max.
Calibration AO XX
4.0=4 mA 20 = 20.0
GC- Address
1
Analog Output
Table of contents