PowerLogic EGX100 User manual

1
Instruction Bulletin 63230-319-204A2
12/2008
PowerLogic™Ethernet Gateway EGX100
User’s Guide
Instructions en Français: page 19
Instrucciones en Español: página 39
Anweisungen auf Deutsch: Seite59
ENGLISH
TABLE OF CONTENTS IINTRODUCTION .......................................................................................2
Supported Ethernet Protocols.....................................................................2
Hardware ....................................................................................................2
Additional Resources..................................................................................3
ACCESSING THE EGX OVER A NETWORK ...........................................3
Logging into the EGX..................................................................................3
Logging Out ................................................................................................3
EGX USER INTERFACE OVERVIEW .......................................................4
SETUP........................................................................................................5
Ethernet and TCP/IP Settings.....................................................................5
Duplicate IP Address Detection.............................................................6
Serial Port...................................................................................................7
Device List ..................................................................................................8
Master Mode Device List Setup ............................................................8
Slave Mode Device List Setup ..............................................................9
User Accounts...........................................................................................10
Web Page Access.....................................................................................11
Modbus TCP/IP Filtering...........................................................................12
SNMP Parameters....................................................................................13
DIAGNOSTICS.........................................................................................14
Statistics....................................................................................................14
Interpreting Statistics...........................................................................15
Read Device Registers.............................................................................17
FIRMWARE..............................................................................................18
Finding the Firmware Version...................................................................18
Getting New Firmware..............................................................................18
Updating the Firmware File.......................................................................18

PowerLogic™ Ethernet Gateway 63230-319-204A2
Introduction 12/2008
© 2008 Schneider Electric. All Rights Reserved.2
ENGLISH
INTRODUCTION This manual is to be used with a PowerLogic™EGX100 with firmware
version 2.0 or higher. For installation information, see the installation guide.
The EGX100 is a communications device that provides connectivity
between Ethernet (Modbus TCP/IP) and serial line devices, allowing
Modbus TCP/IP clients to access information from serial slave devices. It
also allows serial master devices to access information from slave devices
distributed across an Ethernet network.
Supported Ethernet Protocols The EGX supports the following Ethernet protocols:
•Modbus TCP/IP: Modbus TCP/IP is a combination of the Modbus
protocol, which provides master-slave communication between devices,
and TCP/IP, which provides communications over an Ethernet
connection. Modbus TCP/IP is used to exchange data between the EGX
and other compatible Modbus TCP/IP devices via TCP port 502.
•Hypertext Transfer Protocol (HTTP): HTTP is a network protocol that
handles the delivery of files and data on the World Wide Web. It
provides web server functionality via TCP port 80. Remote configuration
of the EGX and the viewing of diagnostic data is possible using a web
browser.
•File Transfer Protocol (FTP): FTP is a network protocol that provides
the ability to transfer files over the Internet from one computer to
another. FTP is used to transfer firmware updates to the EGX via TCP
port 21.
•Simple Network Management Protocol (SNMP): Based on MIB2
format, SNMP provides the ability to store and send identifying and
diagnostic information used for network management purposes via UDP
port 161 .
•Address Resolution Protocol (ARP): ARP is used to convert IP
addresses to Ethernet addresses. ARP requests are sent by the EGX to
determine if its address is a duplicate IP address (see “Duplicate IP
Address Detection” on page 6).

63230-319-204A2 PowerLogic™ Ethernet Gateway
12/2008 Accessing the EGX Over a Network
© 2008 Schneider Electric. All Rights Reserved. 3
ENGLISH
Hardware
Additional Resources Documentation: Go to www.powerlogic.com, and then click the manual
you want to download.
Firmware: Go to www.powerlogic.com, and then click the firmware file you
want to download.
NOTE: If you do not have a user name and password, follow the instructions
on the web site.
ACCESSING THE EGX OVER A
NETWORK After you set up the Ethernet parameters (see the installation guide), you
can access the EGX over an Ethernet LAN using Internet Explorer 6.0 or
higher.
Logging into the EGX
Control power
RJ45 Ethernet port
LEDs for Ethernet
and serial
communications
Reset
button
Power and
Status LED
RS485 serial port
Bias, termination,
and 2-wire/4-wire
jumper switches
RS232 serial port
(RJ45 connector)
Action Result
1. Launch Internet Explorer 6.0 or higher. Opens Internet Explorer.
2. In the Address text box, type the address
of your EGX (169.254.0.10 is the default),
then press Enter.
Opens the Login dialog box.
3. Type your user name (Administrator is the
default) and password (Gateway is the
default) into the text boxes, then click OK.
Enters the user name and password, then
opens the EGX home page.
4. Click Setup to access the EGX setup page,
or click Diagnostics to access the EGX
diagnostics page.
Opens the Setup or Diagnostics pages.

PowerLogic™ Ethernet Gateway 63230-319-204A2
EGX User Interface OVERVIEW 12/2008
© 2008 Schneider Electric. All Rights Reserved.4
ENGLISH
Logging Out We recommend logging out whenever you do not need access to the EGX.
To log out of the EGX configuration session, click Logout to end your
session.
EGX USER INTERFACE
OVERVIEW The EGX ships with seven pre-installed web pages used for EGX setup and
configuration. See Table 1 for a description of each web page.
Figure 1: EGX Home Page
Menu
bar
Table 1: EGX static web pages
EGX Web Page Description See
Page
Setup
Ethernet & TCP/IP Configure Ethernet and TCP/IP communication settings. 5
Serial Port Set up or change serial communication parameters. 7
Device List Identify serial devices on the daisy chain. 8
User Accounts➀Create and edit groups and users. 10
Web Page Access➀Select web page access rights for each user group. 11
Modbus TCP/IP Filtering➀Set up which IP addresses can access the EGX through
Modbus TCP/IP. 12
SNMP Parameters➀Enable and configure the Simple Network Management
Protocol (SNMP), which allows the EGX to identify itself
to network devices requesting SNMP data.
13
Diagnostics
Statistics Displays diagnostic data used to troubleshoot network
problems. This page also contains information about
your specific EGX, including the serial number,
manufacturing date, and Media Access Control (MAC)
address.
14
Read Device Registers Allows EGX administrators to read register data from a
serial device connected to the EGX. 17
➀Accessible by administrator only

63230-319-204A2 PowerLogic™ Ethernet Gateway
12/2008 Setup
© 2008 Schneider Electric. All Rights Reserved. 5
ENGLISH
SETUP To access the Setup web page links, click Setup on the EGX menu bar.
Ethernet and TCP/IP Settings
NOTE: After making changes to the Ethernet parameters and clicking
Apply, the EGX will reboot.
Action Result
1. From the Setup page, click Ethernet &
TCP/IP.Opens the Ethernet & TCP/IP page.
2. Select your frame format and media type.
Contact your network administrator if you
do not know.
Selects the frame format and media type.
3. Enter your IP address, subnet mask, and
default gateway address assigned to your
EGX by your network administrator.
Enters the Ethernet parameters for the EGX.
NOTE: If you enter an IP address that is used
by another device, you will be prompted to
select a new IP address. See “Duplicate IP
Address Detection” on page 6.
4. Click Apply. Updates the EGX Ethernet and TCP/IP
settings.
* See Table 2 on page 5 for a list of options.
Figure 2: Ethernet & TCP/IP Page
Table 2: EGX Ethernet and TCP/IP Settings
Option Description Setting
Frame Format Used to select the format for data sent over
an Ethernet connection. Ethernet II, 802.3 SNAP
Default: Ethernet II
Media Type Used to define the physical Ethernet
connection or media type. • 10T/100Tx Auto
• 10BaseT-HD
• 10BaseT-FD
• 100BaseTX-HD
• 100BaseTX-FD
Default: 10T/100Tx Auto
IP Address Used to enter the static IP address of the
EGX. 0.0.0.0 to 255.255.255.255
Default: 169.254.0.10
Subnet Mask Used to enter the Ethernet IP subnet mask
address of your network. 0.0.0.0 to 255.255.255.255
Default: 255.255.0.0
Default Gateway Used to enter the gateway (router) IP
address used for wide area network (WAN)
communications.
0.0.0.0 to 255.255.255.255
Default: 0.0.0.0

PowerLogic™ Ethernet Gateway 63230-319-204A2
Setup 12/2008
© 2008 Schneider Electric. All Rights Reserved.6
ENGLISH
Duplicate IP Address Detection While connected to your network, the EGX publishes its IP address. To
avoid any duplicate IP address conflicts, the EGX uses the Address
Resolution Protocol (ARP) to see if any other device on your network is
using the same IP address. Table 3 below explains how the EGX handles a
duplicate IP address when it is detected.
Table 3: Duplicate IP Detection Scenarios
Scenario Duplicate IP Detected Power/Status LED
Boot Process /
Power Restore Reverts to the default EGX IP
address, subnet mask, and gateway
address.ARPrequestsare sent every
15 seconds until the IP address is
available. When the IP address
becomes available, the EGX will use
it.
Four blinks, pause pattern
Ethernet Link Detected
Manual Address Change EGX keeps it’s previous IP address
and displays a message indicating
that the IP address is already in use
by another device.
Receives an ARP request Reverts to the default EGX IP
address, subnet mask, and gateway
address if a connected device sends
four ARP requests for the EGX’s IP
address. The EGX will send ARP
requests every 15 seconds until the
IP address is available again. When
the IP address becomes available,
the EGX will use it.
Four blinks, pause pattern

63230-319-204A2 PowerLogic™ Ethernet Gateway
12/2008 Setup
© 2008 Schneider Electric. All Rights Reserved. 7
ENGLISH
Serial Port Action Result
1. From the Setup page, click Serial Port. Opens the Serial Port page.
2. Select your mode, physical interface,
transmission mode, baud rate, parity, and
response timeout (see Table 4 on page 7).
Selects the serial port options.
3. If you select Slave mode, enter the IP
addresses for the remotely connected
devices (see Table 4 on page 7).
Enters the IP addresses of the remote devices.
4. Click Apply. Updates the EGX Serial Port settings.
Figure 3: Serial Port Page
Table 4: Serial Port Settings
Option Description Setting
Mode Used to select how the COM port on the
EGX is utilized (master or slave).
NOTE: When the Mode is changed, the
EGX reboots.
Master, Slave
Default: Master
Physical Interface Used to select how the EGX serial port is
physically wired. RS485 4-wire, RS485 2-wire,
or RS232
Default: RS485 2-wire
Transmission
Mode Used to select how data is transmitted over
a serial connection. Master mode: Automatic,
Modbus ASCII
Slave mode: Modbus RTU,
Modbus ASCII
Default:
•Master mode: Automatic
•Slave mode: Modbus RTU
NOTE: Automatic mode allows
you to communicate to
Modbus RTU, Jbus, and
PowerLogic™ (SY/MAX) slave
devices on the same daisy
chain.
Baud Rate Used to select the data transmission speed
over a serial connection. 2400, 4800, 9600, 19200,
38400, 56000*, 57600*
Default: 19200
Parity Used to select if data is checked for
accuracy using a parity bit. Even, Odd, None
Default: Even
Response Timeout Used to select how long the EGX will wait
to receive a response from a serial device. 0.1 to 10 seconds
Default: 3 seconds
Remote Modbus
TCP/IP
Connections
(Slave mode only)
Used to define a list of Modbus TCP/IP
addresses for the EGX to use during slave
mode communications.
—
* Available only if the physical interface and transmission mode is RS232/Modbus ASCII.

PowerLogic™ Ethernet Gateway 63230-319-204A2
Setup 12/2008
© 2008 Schneider Electric. All Rights Reserved.8
ENGLISH
Device List Before you begin, keep in mind the following:
For master mode usage of the COM port:
•Modbus RTU/Jbus devices do not have to be defined in the Device List,
but it helps you manage your system.
•PowerLogic™ protocol (SY/MAX) devices must be defined in the Device
List.
NOTE: Do not use serial slave addresses 1 or 16 in Automatic transmission
mode on a daisy chain with mixed protocols (for example, a single daisy
chain with some devices using PowerLogic™ protocol and others using
Modbus RTU/Jbus protocol).
Master Mode Device List Setup
If you selected Master mode on the Serial Port page, follow the steps below
to set up the device list:
Figure 4: Master Mode Topology
Action Result
1. From the Setup page, click Device List. Opens the Device List page.
2. Select the number ofviewable devices (1 to
128), then click Apply.Selects the number of viewable locations that
can be used to define serial slave devices
connected to the EGX.
3. In the Local ID text box, type the local ID
(address) of the serial slave device. Enters the local address of the device.
4. Select the Protocol. Selects the protocol of the connected device.
5. Repeat steps 3 and 4until all of the devices
are entered. Enters all of the connected devices.
6. Click Apply. Updates the Device List settings.
Figure 5: Device List Page in Master Mode
Ethernet
Connection
RS485 connection
Serial Slave Devices
Up to 128 serial
slave devices
using repeaters
EGX in
master
mode

63230-319-204A2 PowerLogic™ Ethernet Gateway
12/2008 Setup
© 2008 Schneider Electric. All Rights Reserved. 9
ENGLISH
Slave Mode Device List Setup Serial port slave mode allows serial Modbus master devices to access
information from serial slave devices across a TCP/IP network. Figure 6
below illustrates how the devices are connected using the device list
settings in Figure 7.
If you selected Slave mode on the Serial Port page, follow the steps below
to set up the device list:
Figure 6: Slave Mode Topology
2 5 234 5 6 7
Ethernet
Connection
EGX in
master mode
IP address:
169.254.0.75
RS485
connection
Serial Slave Devices
RS232 or RS485
connection
Up to 16 remote IP connections
with up to 128 serial slave devices
are possible
EGX in
slave mode
EGX in
master mode
IP address:
169.254.0.28
Serial Slave Devices
RS485
connection
Action Result
1. From the Setup page, click Device List. Opens the Device List page.
2. Select the number of viewable devices (1 to
128), then click Apply.Selects the number of viewable locations that
can be used to define remote Modbus TCP/IP
devices.
3. In the Local ID text box, type the local ID
(address) of the serial slave device. Enters the address of the device that the local
Modbus master device will use to access the
remote device.
4. In the Remote ID text box, type the remote
ID (address) of the serial slave device. Enters the serial slave address of the remotely
connected device.
5. Select the Connection. Selects the Modbus TCP/IP address to
associate with the remote ID.
6. Repeat steps 3 through 5 until all of the
devices are entered. Enters all of the mapping information for the
EGX to communicate to the remote devices.
7. Click Apply. Updates the Device List settings.
Figure 7: Device List Page in Slave Mode

PowerLogic™ Ethernet Gateway 63230-319-204A2
Setup 12/2008
© 2008 Schneider Electric. All Rights Reserved.10
ENGLISH
User Accounts EGX users are assigned user names and passwords. Each user belongs to
a group, and each group has access rights to the EGX Web pages assigned
by the EGX administrator.
NOTE: There are two default user accounts: Administrator (password is
Gateway) and Guest (password is Guest).
Action Result
1. From the Setup page, click User
Accounts.Opens the User Accounts page.
2. If you want to change a group name, type a
new name in one of the Groups text boxes
(the Administrator group name cannot be
changed).
Enters a new group name.
3. In the Users section, enter a Name (1 to 24
characters) and Password (0 to 12
characters) for a new user.
NOTE: User names and passwords are
case-sensitive and can contain only
alphanumeric characters.
Enters the name and password for a user.
4. Select a group and the default language for
the new user. Selects the group and language for a user.
5. Repeat steps 3 and 4 for each additional
user you want to add. Continues adding users.
6. Click Apply. Saves all of the user account settings.
Table 5: EGX accounts and passwords
Account Default Password
Administrator Gateway
Guest Guest
User-defined accounts (up to 11 accounts possible) No default –Password is user-defined
Figure 8: User Accounts Page

63230-319-204A2 PowerLogic™ Ethernet Gateway
12/2008 Setup
© 2008 Schneider Electric. All Rights Reserved. 11
ENGLISH
Web Page Access Action Result
1. From the Setup page, click Web Page
Access.Opens the Web Page Access page.
2. In the Ethernet & TCP/IP row, select the
access level (None, Read-only, or Full) that
each user group has for the Ethernet &
TCP/IP web page.
See Table 6 below for an explanation of access
levels for each group.
3. To allow Guest access to the web page,
select Read-only under the Guest column.
NOTE: If the Guest group is Read-only,
other groups may only be set to Read-only
or Full.
Allows the default Guest group to access the
web page.
4. Repeat steps 2 and 3 for the Serial Port,
Device List, Statistics, and Read Device
Registers rows.
Selects the access level for each web page.
5. Click Apply. Saves the password settings.
Table 6: Group Access
Group Access
Administrator Full access to all web pages
NOTE: We recommend that you change the default administrator
password for system security the first time you log in.
Guest Read-only access to selected web pages.
Three user-defined
groups Choosing from the following options, the administrator assigns web
page access for each group. Access levels are as follows:
•None: a group has no access to selected web page
•Read-only: password grants a group read-only access to the
selected web page
•Full: a group has the same access as the Administrator group to the
selected web page
Figure 9: Web Page Access Page

PowerLogic™ Ethernet Gateway 63230-319-204A2
Setup 12/2008
© 2008 Schneider Electric. All Rights Reserved.12
ENGLISH
Modbus TCP/IP Filtering This function allows the administrator to specify Modbus TCP/IP client
devices that have or do not have access to serial slave devices connected
to the EGX.
NOTE: There is an anonymous Modbus TCP/IP address (***.***.***.***) that
can be set to Read-only or None. Setting it to Read-only allows any
Modbus TCP/IP client not in the filtered list to access serial slave devices
with read-only access. Setting it to None blocks all Modbus TCP/IP clients
not in the filtered list.
Action Result
1. From the Setup page, click Modbus
TCP/IP Filtering.Opens the Modbus TCP/IP Filtering page.
2. Check Enable Filtering. Activates filtering.
3. In the IP address column, enter the
Modbus TCP/IP client address Enters an IP address for a Modbus TCP/IP
client that will have access to the serial devices
connected to the EGX.
4. In the Access Level column, select Read-
only or Full. Selects the access level for the corresponding
IP address. When set to Read-only, only the
following Modbus TCP/IP function codes are
allowed:
Decimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24,
43, 100
Hexadecimal: 01, 02, 03, 04, 07, 08, 0B, 0C,
11, 14, 18, 2B, 64
5. Repeat steps 3 and 4 to add more IP
addresses. Continues adding IP addresses for filtering.
6. Click Apply. Saves the Modbus TCP/IP address filtering list.
Figure 10: Modbus TCP/IP Filtering Page

63230-319-204A2 PowerLogic™ Ethernet Gateway
12/2008 Setup
© 2008 Schneider Electric. All Rights Reserved. 13
ENGLISH
SNMP Parameters The EGX supports SNMP, allowing a network administrator to remotely
access an EGX with an SNMP manager and view the networking status and
diagnostics in the MIB2 format.
Action Result
1. From the Setup page, click SNMP
Parameters.Opens the SNMP Parameters page.
2. Check Enable SNMP to turn ON the simple
network management protocol.
NOTE: If you uncheck Enable SNMP and
click Apply, the EGX wo;; reboot and SNMP
functionality will be turned OFF.
Activates SNMP.
3. Enter the system contact, system name,
system location, read-only community
name, and the read-write community name.
Enters the SNMP system information and
community access names.
4. Click Apply. Saves the SNMP settings.
Figure 11: SNMP Parameters Page

PowerLogic™ Ethernet Gateway 63230-319-204A2
Diagnostics 12/2008
© 2008 Schneider Electric. All Rights Reserved.14
ENGLISH
DIAGNOSTICS To access the Diagnostics web page links, click Diagnostics on the EGX
menu bar.
Statistics
NOTE: This page will show accumulated readings since the EGX was last
activated. If power to the EGX is lost, all cumulative values reset to zero.
Action Result
1. From the Diagnostics page, click
Statistics.Opens the Statistics page (see Figure 12).
NOTE: The Statistics page displays data based
on the mode selected in “Serial Port” on
page 7.
2. View the data. See “Interpreting Statistics”below.
3. Click Reset. Resets the EGX cumulative diagnostic data to
0.
Figure 12: Statistics Page
Reading with Serial Port in MASTER MODE
Reading with Serial Port in SLAVE MODE

63230-319-204A2 PowerLogic™ Ethernet Gateway
12/2008 Diagnostics
© 2008 Schneider Electric. All Rights Reserved. 15
ENGLISH
Interpreting Statistics Statistic Description
Ethernet
Link Status A status string that represents the speed and
duplex setting being used to communicate with
the linking partner.
Frames Transmitted OK A counter that increments each time a frame is
successfully transmitted.
Collisions A counter that increments each time a frame is
retransmitted due to collision detection.
Excessive Collisions A counter that increments each time a frame is
not able to be sent due to reaching the
maximum collision status based on the
Truncated Binary Exponential Backoff
algorithm.
Frames Received OK A counter that increments each time a frame is
successfully received.
CRC Errors A counter that increments each time a frame is
received that has a checksum/CRC that does
not match what is calculated.
Alignment Errors A counter that increments each time a frame is
received that has a checksum/CRC error and
does not end on an 8-bit frame boundary.
Frames Too Long A counter that increments each time a frame is
received that is larger than the allowed
maximum size defined in the standards (frames
larger than 1518 bytes).
Frames Too Short A counter that increments each time a frame is
received that is smaller than the allowed
minimum size defined in the standards (frames
smaller than 64 bytes).
Modbus TCP/IP
Frames Sent A counter that increments each time a frame is
sent.
Frames Received A counter that increments each time a frame is
received.
Protocol Errors A counter that increments each time an
ill-formed message is received.
Active ConnectionscA status value that represents the number of
connections that are active at the moment the
diagnostics page is refreshed. A maximum of
32 connections are supported. Clicking Active
Connections opens a new window with a list of
all of the active client connections.
Accumulative ConnectionscA counter that increments each time a
connection is made to the EGX.
Maximum ConnectionscA status value that represents the maximum
number of connections that were active at any
given moment.
Inbound Read MessagescA counter that increments each time a read
request message is received.
Outbound Read Messages"A counter that increments each time a read
request message is sent.
Inbound Write MessagescA counter that increments each time a write
request message is received.
Outbound Write Messages"A counter that increments each time a write
request message is sent.
Inbound Reply Messages"A counter that increments each time a reply
message is received.
Outbound Reply MessagescA counter that increments each time a reply
message is sent.
cAvailable when the serial port is in Master mode.
"Available when the serial port is in Slave mode

PowerLogic™ Ethernet Gateway 63230-319-204A2
Diagnostics 12/2008
© 2008 Schneider Electric. All Rights Reserved.16
ENGLISH
Serial Port
Frames Sent A counter that increments each time a frame is
sent.
Frames Received A counter that increments each time a frame is
received.
CRC Errors A counter that increments each time a
message is received that has a CRC that does
not match what is calculated. Typically the
result of wiring issues.
Protocol Errors A counter that increments each time an ill-
formed message is received.
Timeouts A counter that increments each time a request
message is sent without receiving a
corresponding response message within the
allowed time. Timeouts are typically the result
of configuration errors or a non-responsive
device.
Inbound Read Messages"A counter that increments each time a read
request message is received.
Outbound Read MessagescA counter that increments each time a read
request message is sent.
Inbound Write Messages"A counter that increments each time a write
request message is received.
Outbound Write MessagescA counter that increments each time a write
request message is sent.
Gateway Information
Firmware Version The firmware version that is installed on the
EGX.
System Idle Time A percentage from 0% to 100% indicating the
average processor time that is not being used.
MAC Address The unique Ethernet hardware address of an
EGX.
Serial Number The serial number of the EGX.
Model Number The EGX model number (100).
Hardware Version EGX hardware version.
Manufacture Date Date the EGX was manufactured.
Statistic Description
cAvailable when the serial port is in Master mode.
"Available when the serial port is in Slave mode

63230-319-204A2 PowerLogic™ Ethernet Gateway
12/2008 Diagnostics
© 2008 Schneider Electric. All Rights Reserved. 17
ENGLISH
Read Device Registers Action Result
1. From the Diagnostics page, click Read
Device Registers.Opens the Read Device Registers page.
2. Enter the device ID, starting register
number, and the number of registers to
read.
Enters the values to begin reading registers for
the specified device.
3. Click Read Holding Registers or Read
Input Registers.Displays the values for the listed registers.
4. To change how the data is displayed in the
Value column, select Decimal,
Hexadecimal, Binary, or ASCII.
Selects how the data values are displayed.
Table 7: EGX Read Device Register Settings
Option Description Default
Device ID The address of the device that registers are read. 1
Starting Register The first register to read. 1000
Number of Registers The number of registers to read (1 to 10). 10
Register column Lists the register numbers —
Value column Lists the data stored for a register. Values
retrieved depend on the device connected to the
EGX. Refer to the documentation for the
connected device for more information about
stored register values.
—
Decimal, Hexadecimal,
Binary, or ASCII options Select an option to specify how the Value column
data is displayed. Decimal
Figure 13: Read Device Registers Page

PowerLogic™ Ethernet Gateway 63230-319-204A2
Instruction Bulletin 12/2008
ENGLISH
Electrical equipment should be installed, operated, serviced, and maintained only by
qualified electrical personnel. No responsibility is assumed by Schneider Electric for
any consequences arising out of the use of this material.
Schneider Electric
Power Monitoring and Control
295 Tech Park Drive, Suite 100
LaVergne, TN 37086 USA
Tel: +1 (615) 287-3400
www.powerlogic.com
© 2008 Schneider Electric. All Rights Reserved.
FIRMWARE Firmware on the EGX can be updated using File Transfer Protocol (FTP).
Check www.powerlogic.com or with your local sales representative for the
latest firmware update.
Finding the Firmware Version
Getting New Firmware Go to www.powerlogic.com, and then click the firmware file you want to
download.
NOTE: If you do not have a user name and password, follow the instructions
on the web site.
Updating the Firmware File
Action Result
1. Log into the EGX. Opens the EGX home page.
2. Locate the firmware version on the
bottom-left corner of the page.
NOTE: If you recently updated your
firmware, press F5 to refresh the web page
and update the displayed firmware number.
Determines the firmware version of the EGX.
3. Alternatively, you can select Diagnostics >
Statistics to find the firmware version in the
Gateway Information section.
Also determines the firmware version of the
EGX.
Action Result
1. Launch Internet Explorer, type ftp:// and the
IP address of the EGX in the Address text
box (for example, ftp://169.254.0.10), then
press Enter.
Opens the Log On As dialog box.
2. Type the user name Administrator and the
administrator password in the text boxes,
then click Log On.
Opens an FTP session with the EGX.
3. Locate the saved firmware file on your
computer, select it, then press CTRL+C. Copies the firmware file to the clipboard.
4. Right-click in the Internet Explorer window,
then click Paste.
NOTE: Instead of copying and pasting the
firmware file, you can drag-and-drop the
firmware file into Internet Explorer.
Copies the firmware to the EGX, and the EGX
reboots.
5. Click the Close button on the Internet
Explorer window. Closes Internet Explorer and ends the FTP
connection to the EGX.
6. To verify that the firmware version was
updated successfully, follow the steps in
“Finding the Firmware Version” on page 18.
Verifies the updated firmware version.

19
Manuel d’utilisation 63230-319-204A2
12/2008
Passerelle Ethernet PowerLogic™EGX100
Manuel d’utilisation
Instructions in English: page 1
Instrucciones en Español: página 39
Anweisungen auf Deutsch: Seite 59
À conserver pour une utilisation ultérieure.
FRANÇAIS
TABLE DES MATIÈRES INTRODUCTION ......................................................................................40
Protocoles Ethernet pris en charge...........................................................40
Matériel.....................................................................................................40
Ressources supplémentaires....................................................................41
ACCÈS À LA PASSERELLE EGX VIA UN RÉSEAU .............................42
Connexion à la passerelle EGX................................................................42
Déconnexion.............................................................................................42
INTERFACE UTILISATEUR EGX – VUE D’ENSEMBLE........................43
CONFIGURATION....................................................................................44
Paramètres Ethernet et TCP/IP................................................................44
Détection des adresses IP identiques.................................................45
Port série...................................................................................................45
Liste des appareils....................................................................................46
Configuration de la liste des appareils en mode Maître......................47
Configuration de la liste des appareils en mode Esclave....................48
Comptes utilisateur...................................................................................49
Accès aux pages Web ..............................................................................50
Filtrage Modbus TCP/IP............................................................................51
Paramètres SNMP....................................................................................52
DIAGNOSTICS.........................................................................................53
Statistiques ...............................................................................................53
Interprétation des statistiques .............................................................54
Lecture de registres d’appareils................................................................56
LOGICIEL EMBARQUÉ (FIRMWARE)....................................................57
Recherche de la version du logiciel embarqué.........................................57
Obtention du dernier logiciel embarqué....................................................57
Mise à jour du logiciel embarqué..............................................................57

Passerelle Ethernet PowerLogic™ 63230-319-204A2
Introduction 12/2008
© 2008 . Tous droits réservés.20
FRANÇAIS
INTRODUCTION Ce manuel doit être utilisé avec une passerelle POWERLOGIC®EGX100
équipée de la version 2.0 ou ultérieure du logiciel embarqué (firmware).
Pour les informations d’installation, voir le Manuel d’installation 63230-319-
200.
La passerelle EGX100 est un appareil de communication qui assure la
connectivité entre des appareils Ethernet (Modbus TCP/IP) et série. Elle
permet à des clients Modbus TCP/IP d’accéder aux informations d’appareils
esclaves en série. Elle permet aussi à des appareils série maîtres d’accéder
aux informations d’appareils esclaves répartis sur un réseau Ethernet.
Protocoles Ethernet pris en charge La passerelle EGX prend en charge les protocoles Ethernet suivants :
•Modbus TCP/IP : Modbus TCP/IP est une combinaison du protocole
Modbus qui permet les communications maître/esclave entre des
appareils et de TCP/IP qui permet de communiquer à travers une
connexion Ethernet. Modbus TCP/IP s’utilise pour échanger des
données entre la passerelle EGX et d’autres appareils compatibles
Modbus TCP/IP via le port TCP 502.
•Hypertext Transfer Protocol (HTTP) : HTTP est un protocole réseau
qui gère la remise de fichiers et de données sur le Web. Il fournit les
fonctionnalités de serveur Web via le port TCP 80. La configuration à
distance de la passerelle EGX et l’affichage des diagnostics sont
possibles en utilisant un navigateur Web.
•File Transfer Protocol (FTP) : FTP est un protocole réseau qui permet
de transférer des fichiers d’un ordinateur à un autre sur Internet. Le
protocole FTP s’utilise pour transférer les mises à jour dans la
passerelle EGX via le port TCP 21.
•Simple Network Management Protocol (SNMP) : basé sur le format
MIB2, SNMP permet d’enregistrer et d’identifier des informations de
diagnostic utilisées pour la gestion du réseau via le port UDP 161.
•Address Resolution Protocol (ARP) : ARP convertit des adresses IP
en adresses Ethernet. La passerelle EGX envoie les demandes pour
déterminer si son adresse IP est identique (voir « Détection des
adresses IP identiques », page 25).
Table of contents
Languages:
Other PowerLogic Gateway manuals