  9. Powers HydroGuard XP LFMM430 Series Owner's manual

Powers HydroGuard XP LFMM430 Series Owner's manual

Description n
HydroGuard®XP Series LFMM430 2 Valve
Hi/Lo Supply Fixture
Technical Instructions
IS-P-SF-MM430-2V-HiLo
Powers' HydroGuard®XP Series LFMM430 Hi/Lo's are fully assem-
bled factory tested systems, designed to provide safe water through-
out commercial and institutional facilities. HydroGuard®XP Series
LFMM430 Hi/Lo systems consist of Series LFLM490 and Series
LFMM430 thermostatic valves which utilize paraffin-based actuation
technology to sense and adjust outlet temperature. Each system
also includes a PRV, ball valves, pressure/temperature gauges and
Powers' triple-duty checkstops. Optional equipment includes cabinets.
Two-valve supply fixtures feature a low capacity valve that works
in parallel with a high capacity valve. During low demand, the
low capacity valve handles the load requirements. As the load
demand is increased, the pressure reducing valve, which is set at
a certain pressure differential, will open and allow flow through the
high capacity valve to assist the low capacity valve in meeting the
increased load requirements.
Maximum Operating Pressure .................. 125psi (861 kPa)
Maximum Hot Water Temperature ........... 200°F (93°C)
Minimum Hot Water Supply Temp*............. 5°F (3°C) Above Set-Point
Hot Water Inlet Temperature Range ........ 120 -180°F (49 - 82°C)
Cold Water Inlet Temperature Range ....... 40 - 80°F (4 - 27°C)
Minimum Flow**............................................ 0.5 gpm (1.89 lpm)
Temp. Adjustment Range *** ..................... 90 - 160°F (32 - 71°C)
Listing/Compliance (Valve Only) ................ ASSE 1017, CSA B125
* With Equal Pressure
** Minimum flow when HiLo is installed at or near hot water source recirculating
tempered water with a properly sized continuously operating recirculating pump.
*** Note: Low limit cannot be less than the cold water temperature. For best
operation, hot water should be at least 5°F (3°C) above desired set point.
Specifications n
Advanced Thermal Activation
Description n
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use infor-
mation can result in death, serious personal injury,
property damage, or damage to the equipment.
Keep this Manual for future reference.
You are required to consult the local building and plumbing
codes prior to installation. If the information in this manual is
not consistent with local building or plumbing codes, the local
codes should be followed. Inquire with governing authorities for
additional local requirements.
WARNING
!
Need for Periodic Inspection and Yearly Maintenance:
Periodic inspection and yearly maintenance by a licensed con-
tractor is required. Corrosive water conditions and/or unauthor-
ized adjustments or repair could render the valve ineffective for
service intended. Regular checking and cleaning of the valve’s
internal components and check stops helps assure maximum
life and proper product function. Frequency of cleaning and
inspection depends upon local water conditions.
FAILURE TO COMPLY WITH PROPER INSTALLATION AND
MAINTENANCE INSTRUCTIONS COULD CONTRIBUTE TO THE
VALVE FAILURE.
This Hot Water Master Tempering Valves cannot be used for
tempering water temperature at fixtures. Severe bodily injury
(i.e., scalding or chilling) and/or death may result depending
upon system water pressure changes and/or supply water
temperature changes. ASSE standard 1016, 1069 or 1070 listed
devices should be used at fixtures to prevent possible injury.
These Hot Water Tempering Valves are designed to be
installed at or near the boiler or water heater. They are not
designed to compensate for system pressure fluctuations and
should not be used where ASSE standard 1016, 1069 or 1070
devices are required. These valves should never be used to
provide “anti-scald” or “anti-chill” service.
The components of the system must be of materials with a
construction capable of withstanding the high limit output tem-
peratures of the water heating source.
WARNING
!
WARNING
!
Distributed By: M&M Control Service, Inc.
www.mmcontrol.com/powershome.php
800-876-0036 847-356-0566
Set Up Procedure n
You must follow these procedures in order to properly adjust your Hi/
Lo System. You need flow greater than the minimum shown in capac-
ity table across the valve in order to set a maximum temperature.
1. Close the low flow valve on the outlet of the low flow valve.
2. Open the ball valve at the discharge of the high flow valve.
3. Open enough fixtures to meet the minimum flow requirement as
per capacity table.
4. Set valve temperature. Refer to IS-P-LFMM430.
5. Set the PRV as follows for a 15psi differential.
a) Loosen the locknut at the top of the PRV. This must be all the
way out or you will be limiting the range of the adjustment. b)
Adjust the PRV so the outlet pressure gauge (top) reads 15psi
less than the supply pressure gauge (bottom). Turning the
adjustment screw counterclockwise will increase the differential
across the PRV (allowing the PRV to open later).
6. Close the ball valve at the discharge of the high flow valve and
open the low flow side ball valve by rotating the handle fully
counterclockwise.
7. Open enough fixtures to meet the minimum flow requirement as
per capacity table.
8. Set the temperature for the low flow valve. Refer to
IS-P-LFLM490-LFLM490-10.
9. Open the ball valve at the discharge of high flow valve.
10. Open additional fixtures to create a 20psi differential between
supply and outlet pressure gauges.
11. When water is at desired outlet temperature, verify temperature
remains at set point.
2
Supply Pressure Gauge Outlet Pressure Gauge
Lock Nut
Turn fully CCW
(counterclockwise)
before setting PRV.
Adjustment Screw
CW: Increases outlet pressure and
decreases differential across PRV or
CCW: Decreases outlet pressure and
increases differential across PRV.
Capacity n
Flow Capacity at 50-50 Mixed Ratio
Pressure Drop Across Valve
Model Min. Flow CV
5psi 10psi 20psi 30psi 45psi 60psi
to ASSE 1017 (34 kPa) (69 kPa) (138 kPa) (207 kPa) (310 kPa) (414 kPa)
LFMM431HL 0.5 gpm 9.7 22 gpm 31 gpm 43 gpm 53 gpm 65 gpm 75 gpm
1.89 lpm 83 lpm 117 lpm 163 lpm 201 lpm 246 lpm 284 lpm
LFMM432HL 0.5 gpm 13.0 29 gpm 41 gpm 58 gpm 66 gpm 87 gpm 93 gpm
1.89 lpm 110 lpm 155 lpm 220 lpm 250 lpm 329 lpm 352 lpm
LFMM433HL 0.5 gpm 19.8 44 gpm 63 gpm 86 gpm 108 gpm 133 gpm 153 gpm
1.89 lpm 167 lpm 238 lpm 326 lpm 409 lpm 503 lpm 579 lpm
LFMM434HL 0.5 gpm 24.9 56 gpm 79 gpm 111 gpm 136 gpm 167 gpm 193 gpm
1.89 lpm 212 lpm 299 lpm 420 lpm 515 lpm 632 lpm 731 lpm
LFMM435HL 3.0 gpm 27.7 62 gpm 88 gpm 124 gpm 152 gpm 186 gpm 215 gpm
11.0 lpm 235 lpm 333 lpm 469 lpm 575 lpm 704 lpm 814 lpm
12. Gradually start to close fixtures to verify that the temperature
remains constant through the full range of flow.
13. For any problem, refer to Troubleshooting section of the docu-
ment or contact Powers' Technical Support Department at
1.800.669.5430 or [email protected].
1. Flush all piping thoroughly before installing.
2. Make sure all ball valve handles are in "OFF" position.
3. In order to make any temperature adjustment to the valves,
you must open end-of-line fixtures to ensure you have ade-
quate flow across the valve.
Prior to Installation n
4. Use a thermometer at the showerhead or install an in-line
thermometer at the point-of-use.
Distributed By: M&M Control Service, Inc.
www.mmcontrol.com/powershome.php
800-876-0036 847-356-0566
See enclosed IS-P-LFLM490-LFLM490-10 and IS-P-LFMM430.
Adjusting to Individual High Flow and Low Flow Valves n
3
What to look for if:
• Outlet temperature is too hot with low ow:
1. The maximum temperature of the low flow valve was not prop-
erly set. Refer to set up procedure and reset the maximum
temperature of the low flow valve.
2. The thermal actuator of the low flow valve is not working prop-
erly. Replace accordingly to the appropriate technical instruc-
tions (IS-P-LFLM490-LFLM490-10 and IS-P-LFMM430).
• Outlet temperature is too hot with a high ow:
1. The maximum temperature of a high flow valve was not prop-
erly set. Refer to Set Up Procedure and reset the maximum
temperature of the high flow valve.
2. The thermal actuator of the high flow valve is not working prop-
erly. Replace accordingly, IS-P-LFMM430 enclosed.
• Outlet temperature too low on low and high ow:
1. The hot water temperature is too low. You must have a supply
temperature of at least 5°F (3°C) higher than the set tempera-
ture. Re-adjust the hot water supply.
2. The checkstops on the hot side of the valve are not fully open,
or may be stuck due to liming. Open and clean checkstops.
Troubleshooting n
Thermostatic water mixing valves are control devices which must
be cleaned and maintained on a regular basis.
1. Before servicing checkstops or piping, turn off the water
upstream. At least every twelve (12) months, open up the check-
stops and check for the free movement of the poppet.
2. Before servicing the valve, turn off the water supply upstream
or close the checkstops. To close the checkstops, turn the
adjusting screw clockwise.
3. When opening checkstops after servicing, turn adjusting screw
counterclockwise to fully open position then turn adjusting
screw 1/2 turn clockwise for final setting.
4. Every three (3) months, check the maximum temperature adjust-
ments.
5. Every twelve (12) months, remove the valve bonnets and check
the internal components for freedom of movement.
Preventative Maintenance n
See enclosed IS-P-LFLM490_LFLM490-10 and IS-P-LFMM430.
Parts Kits n
WARNING
!
Any changes in supply condition could effect the out-
let water temperature. Check and adjust the valves
accordingly to prevent injury to the users. After com-
pleting repairs, check discharge temperature, (105°F
[41°C]). Reset if necessary. Failure to perform this
operation could result in unsafe discharge tempera-
ture, which may cause injury or death.
3. The temperature has not been set properly on the small and/or
large valve. Refer to Set Up Procedure and reset the valves.
• Outlet ow drops off:
1. The differential across the PRV is set too high, so the high flow
valve begins controlling the system too late, and starves the
system. Refer to the Set Up Procedure and decrease the differ-
ential across PRV.
2. The checkstops on the high flow valves are not fully open or are
stuck due to liming. Open and clean checkstops.
3. The system pressure varies by more than 50% of the inlet sup-
ply pressure.
• Outlet temperature cycles between hot and cold:
1. The differential across the PRV is set too low, so the high flow
valve begins controlling the system too early and therefore,
cycles (hunt for the set point). Refer to the Set Up Procedure
and increase the differential across PRV.
2. The system pressure varies by more than 50% of the inlet sup-
ply pressure.
Distributed By: M&M Control Service, Inc.
www.mmcontrol.com/powershome.php
800-876-0036 847-356-0566

This manual suits for next models

5

Other Powers Plumbing Product manuals

Powers 440 Series User manual

Powers

Powers 440 Series User manual

Powers HydroGuard T/P e700 Series Owner's manual

Powers

Powers HydroGuard T/P e700 Series Owner's manual

Powers Hydroguard PB410 Series User manual

Powers

Powers Hydroguard PB410 Series User manual

Powers 440 Series User manual

Powers

Powers 440 Series User manual

Popular Plumbing Product manuals by other brands

KWC K.26.VB.56.700.38 Features

KWC

KWC K.26.VB.56.700.38 Features

Arcisan Synergii SY01240 INSTALLATION AND CARE INSTRUCTIONS

Arcisan

Arcisan Synergii SY01240 INSTALLATION AND CARE INSTRUCTIONS

Fieldmann FZH 5025 user manual

Fieldmann

Fieldmann FZH 5025 user manual

ESS Easy Drain Modulo M4 EDM1-4 Installation advice

ESS

ESS Easy Drain Modulo M4 EDM1-4 Installation advice

Hyundai Bibione 1 instruction manual

Hyundai

Hyundai Bibione 1 instruction manual

Kernau KSS U 61.1 1B SS manual

Kernau

Kernau KSS U 61.1 1B SS manual

Kohler K-7167 installation guide

Kohler

Kohler K-7167 installation guide

Hans Grohe Metris Classic 31478 Series Instructions for use/assembly instructions

Hans Grohe

Hans Grohe Metris Classic 31478 Series Instructions for use/assembly instructions

Symmons Duro 361SH Operation & maintenance manual

Symmons

Symmons Duro 361SH Operation & maintenance manual

Hans Grohe ShowerTablet Select 700 13184000 Instructions for use/assembly instructions

Hans Grohe

Hans Grohe ShowerTablet Select 700 13184000 Instructions for use/assembly instructions

Toto REI S TX492SRS quick start guide

Toto

Toto REI S TX492SRS quick start guide

Kohler PATIO Series installation instructions

Kohler

Kohler PATIO Series installation instructions

Clou Wash Me CL/02.13030 installation instructions

Clou

Clou Wash Me CL/02.13030 installation instructions

Spectrum Brands Pfister Iyla 016-TR1K Quick installation guide

Spectrum Brands

Spectrum Brands Pfister Iyla 016-TR1K Quick installation guide

American Standard FloWise 2479.216 installation instructions

American Standard

American Standard FloWise 2479.216 installation instructions

Kohler K-7223 Homeowner's guide

Kohler

Kohler K-7223 Homeowner's guide

Speakman S-8700 Installation, maintenance and operation instructions

Speakman

Speakman S-8700 Installation, maintenance and operation instructions

gebo Unifix Maxi FITTING INSTRUCTION

gebo

gebo Unifix Maxi FITTING INSTRUCTION

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.