www.powershield.com.au 2
Use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof
outlet).
Use only VDE-tested, CE-marked power cables to connect the loads to the UPS
system.
When installing the equipment, ensure that the sum of the leakage currents of the
UPS and the connected devices do not exceed 3.5mA.
1-4. Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations as this will cancel and invalidate the
protective earth of the UPS system and of all connected loads.
As the UPS system features its own internal current source (high capacity
batteries), the UPS output sockets may be electrically live even if the UPS system is
not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
Prevent fluids or other foreign objects from entering inside the UPS system.
1-5. Maintenance, service and faults
The UPS system operates with hazardous voltages. Repairs should only be carried
out by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains,
building wiring outlet, components inside the UPS system are still connected to the
battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance; switch off mains
power, then disconnect the batteries and verify that no hazardous voltages are
present at the terminals of the large storage capacitors (the BUS-capacitors).
Only persons who are adequately familiar with high capacity batteries, and with the
understanding of the required precautionary measures outlined below, are
permitted to replace batteries and supervise operations. Unauthorized persons must
be kept well away from the batteries.
Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the
ground. Before touching, always verify that no voltage is present!
Batteries may cause electric shock and have very high short-circuit currents. When
working with batteries always ensure the following precautionary measures are
adhered to:
-remove all jewellery items (wristwatches, rings and metal objects)
-use only tools with insulated grips and handles.
When changing batteries, always install the same model and type of batteries.
Do not attempt to dispose of batteries by burning as they may explode.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin
and eyes and may be toxic.
Replacement fuses must be of the same type and amperage (current rating) in
order to avoid fire hazards.
Do not dismantle the UPS system.