Service Manual
10
Temperature control precision:±1℃;
Characters on control:
4-way reversing valve opens.
When Tr≤Ts-1℃, compressor , 4-way reversing valve and external fan motor all open .
When Tr≥Ts+1℃, compressor and external fan motor both close. Indoor fan motor blows breeze.
When Trc (Trc: The indoor coiled temperature) drops blow F℃, Air conditioner enters into cool- air-
flow prevention operation; Pause indicator lights.
Fan speed control:
Manual: Users can select the fan speed of high, medium or low level as needed in the turn-on
status.
Auto: When Tr< Ts-2℃, high.
When Tr≥Ts-2℃,medium.
Louver adjustment:
Manual: Users can set the position as needed.
(Positions 1-6 in the figure)
Auto: When Trc<39℃,the sweep range is at position 5.
When Tr≥42℃, the sweep range is at position 4.
When 39℃≤Tr<42℃,the sweep range keeps at original position.
Compressor control:
The control circuit will stop compressor only after it has run at least 5 minutes. Compressor can be
restarted 5 minutes later the turn-off.
3.3 Protect functions
3.3.1 Delay-starting protection for the compressor.
Compress will restart working 3 minutes (5 minutes in heating) later the turn-off of compressor or
power-off to keep the pressure balance of the cooling system.
3.3.2 Cooling air flow protection:
In heating operation, when Trc<F℃,and compressor stops or the running time of compressor is
not more than 5 minutes. Air conditioner will enter into the cool-air-flow protection. Louver runs into the
position 6 and can ’t be controlled. Internal fan motor stops and pause indicator lights.
3.3.3 Freeze-prevention: To prevent indoor heat exchanger freezing in cooling and
dehumidification operation.
Compressor will stop running when it runs at least 10 minutes and Trc≤-2℃. If compressor is off
for more than 6 minutes, or the coiled pipe temperature rises above 8℃and compressor is off at least 3
minutes. Compressor will restart working.
3.3.4 Heating overload working:
When Trc≥A℃, the unit enters into overload protection. And indoor fan speed should be adjusted
to a higher level automatically.
When Trc≥B℃, outdoor fan stops. And it will restart working when coiled pipe temperature drops