3.2.5 Blowing surplus energy function:
The first situation: When the unit is turned off in heating operation, the time for blowing surplus energy is
80 seconds. When Trc<32℃, the louver is in position 5 ( Fan speed is at low level).
The second situation: When the unit enters defrosting when in heating operation, the time for blowing
surplus energy is 30 seconds. When Trc<32℃, the louver is in position 5 ( Fan speed is at low level).
The third situation: In heating operation, when the unit comes to the set temperature, the compressor
will stop. When Trc<32℃, the louver is in position 5 ( Fan speed is at low level).
The fourth situation: In heating operation, when the unit enters heating overload operation, the
compressor will stop, (Trc≥c℃and the compressor continues working for more than 5 minutes, the
compressor stops) and blow surplus energy; When the temperature of indoor pipe drops to E℃, the unit will
exist from overload protection and Indoor fan motor will operate at low level for 80 seconds. When Trc<32
℃, the louver is in position 5.
The fifth situation: If the unit has the function of starting up automatically when the electricity comes again,
the unit will judge before the starting of compressor: When Trc≥F℃, the indoor fan motor will run at low level
and the louver is in position 5. When Trc≤25℃, the indoor fan motor will stop. The unit will enter
freeze-prevention operation after the compressor starts.
3.2.6 Operation for dryness enzyme-prevention
When the unit is turned off in cooling mode, the indoor unit will continue run in low fan speed for about 3
minutes to remove the partial moisture in the room.
3.2.7 Compensation for temperature
When enters heating operation, the indoor temperature will decrease 3℃automatically.
3.3 Operating mode
3.3.1 SMART operation
The unit will judge the operation mode automatically after receiving the SMART signal.
3.3.1.1 When Tr≥24℃, turns on the unit in the original condition, the unit will turn into cooling mode.
When 20℃<Tr<24℃, the unit will turns into airflow mode.
When Tr≤20℃, the unit will turns into heating mode.
In airflow mode, when in the condition that it is necessary for cooling or heating more than 1 minute, the
unit will turn into cooling or heating mode.
3.3.1.2 The fan speed is at auto mode and adjustable, the display will change accordingly.
Note: If choosing the airflow mode, the auto airflow is set to be at low level automatically.
3.3.1.3 The airflow direction is swing and adjustable, and the display will change accordingly.