PRODIGY®- DIGITAL VAV DIFFUSERS
4DMS - Manual |priceindustries.com
Information Menu LCD Stats Only
The info menu shows information about the controller status regarding room load, damper position and BACnet address info. No
values can be changed from this menu and it is not locked or protected in any way.
The Info Menu is accessed by pressing the Menu button, scroll through with Up and Down buttons.
CONTROL MODULE
2
1. Manual Adjustment at Diffuser
2. Adjustment at Thermostat
OCCUPANCY
ON-CONTACT Occupancy – The Occupancy can be determined by contact closure, motion or by a user pressing a button.
COOLING MODE
LOAD -100%
Room Load
· Cooling Mode is shown as a load from -1 to -100%. (-100% = max).
· Heating Mode is shown as a load from 0 to 100%. (+100% = max).
· Dead band Mode will be shown as 0%, where the room is satisfied.
SUPPLY AIR TEMP
85.0 °F
Duct Temp (S.A.T) Measurement
· If no supply probe is present, LCD will display No Probe.
· If supply probe present, LCD will display temperature.
AIR FLOW
200 cfm
Air Flow Measurement
· If no DMS flow option is present, item will not display
· If DMS flow option is present, LCD will display air flow rate
DAMPER POS.
50%
Damper Position
· This indicates the current position of the damper in percent (%).
· Range is 0-100% (100% = full open or maximum air).
DAMPER TARGET
50%
Target (damper target % in VVT mode)
· Shows the current flow target in % (VVT).
CO2 READING
300 ppm
CO2 Measurement
· If no CO2/Humidity tstat connected, item will not display
· If CO2/Humidity tstat is connected, LCD will display CO2
HUMIDITY READING
65%
Humidity Measurement
· If no CO2/Humidity tstat connected, item will not display
· If CO2/Humidity tstat is connected, LCD will display CO2
MAC ADDRESS
10
MAC Address (MAC address must be unique on the network segment)
· Shows the BACnet MAC address. Range 1-99.
· MAC Address can be set via dip switch.
· If no BACnet module attached, LCD will display MAC address None.
DEVICE INST.
210
Device Instance (Instance must be ‘globally’ unique on your site)
· Displays controller’s BACnet Device Instance (if BACnet is attached).
· Device Instance can range from 0 – 4,194,303.
POWER FREQ
60 HZ
Device Power Frequency Setting
· Displays controller frequency setting.
· Must be set to match frequency of the supply power.
PRODIGY APP
SQUARE
Prodigy Application Model
· Displays model (geometry) of Prodigy diffuser.
PRESS MENU
TO EXIT
Exit – This will exit the info menu if you select Yes.
Note: Info menu will automatically time out after 60 seconds.