Pro-Elec PELL0309 User manual

1
LOCAL DEHUMIDIFIER
Model: PELL0309 and PELL0310

2
IMPORTANT SAFETY INFORMATION
• Do not use any means to accelerate the defrosting process or to clean, other than
those recommended by the manufacturer.
• The appliance shall be stored in a room without continuously operating ignition
sources (for example: open ames, an operating gas appliance or an operating
electric heater).
• Do not pierce or burn.
• Be aware that refrigerants may not contain an odour.
• The appliance shall be installed, operated and stored in a room with a oor area
larger than 4m2.
• Keep any required ventilation openings clear of obstruction.
• Servicing shall be performed only as recommended by the manufacturer.
• The appliance shall be stored in a well-ventilated area where the room size
corresponds to the room area as specied for operation.
• Any person who is involved with working on or breaking into a refrigerant circuit
should hold a current valid certicate from an industry-accredited assessment
authority, which authorises their competence to handle refrigerants safely in
accordance with an industry recognised assessment specication.
• Servicing shall only be performed as recommended by the equipment
manufacturer. Maintenance and repair requiring the assistance of other skilled
personnel shall be carried out under the supervision of the person competent in
the use of ammable refrigerants.
• All working procedure that affects safety means shall only be carried by competent
persons.
• The appliance is only suitable for indoor use, and is not suitable for other
applications.
• Follow local grid interconnection rules while installing the appliance and ensure
that it is properly grounded. If you have any question on electrical installation,
follow the instructions of the manufacturer, and if necessary, ask a professional
electrician to install it.
• Place the appliance in a level and dry place and keep a distance of above 20cm
between the machine and the surrounding objects or walls.
• After the appliance is installed, ensure that the mains plug is intact and rmly
plugged into the power outlet, and place the power cord to avoid a trip hazard.
• Do not put any object into the air inlet and outlet of the air conditioning. Keep the
air inlet and outlet free from obstructions.
• When drainage pipes are installed, ensure that the drainage pipes are properly
connected, and are not distorted or bent.
• When moving the appliance, make sure that it is in an upright position.
• The appliance should be kept away from gasoline, ammable gas, stoves and
other heat sources.
• Don’t disassemble, overhaul and modify the appliance arbitrarily, otherwise it may
cause a malfunction or harm to persons and properties.
• To avoid danger, if a machine failure occurs, refer to a professional for repair.
• Do not install and use the appliance in a bathroom or other humid environments.
• Do not pull out the mains plug to turn off the appliance.
Please read these instructions carefully before use and retain for future reference.

3
TRANSPORTATION AND STORAGE
•Do not place cups or other objects on the appliance to prevent water or other
liquids from spilling into the air conditioning.
•
•Do not wipe or wash the appliance with chemical solvents such as gasoline and
supply, and clean it with a moist soft cloth. If the machine is really dirty, use a mild
detergent.
•The appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities if they have been given
supervision or instruction concerning use of the appliance in a safe way and
understand the hazards involved.
•Children shall not play with the appliance. Cleaning and maintenance shall not be
made by children without supervision.
•If the supply cord is damaged, it must be replaced by the manufacturer, its service
•The appliance shall be installed in accordance with local wiring regulations.
Transportation and labelling
•
with the transport regulations.
•Marking of equipment using signs in compliance with local regulations
•
regulations.
Storage of equipment/appliances
•The storage of equipment should be in accordance with the manufacturer’s
instructions.

4
PRODUCT OVERVIEW
Positioning
Warning: before using the unit, keep it upright for at least two hours.
• The unit must stand upright on an even surface.
• Do not position near a bath, sink or other permanently damp or wet areas.
• Place the unit at least 20cm away from any other wall, curtains or heat sources to
ensure adequate air circulation.
• Ensure that the mains socket outlet remains accessible when the unit is in use.
• Ensure that there is free access to the air-inlet and air-outlet vents.
POSITIONING & INSTALLATION
1. Water TankHandle
2. Front Panel
3. Handle
4. Air Outlet
5. Control Panel
6. Filter
7. Frame
8. Power Cord
9. Rear Panel
10. Caster
Activated carbon lter cloth
(Optional) PU Filter Layer (Optional)

5
CONTROL PANEL
The LED indicator display features the following functions:
• When the unit is plugged in, it will indicate the room humidity level.
• If you set the humidity desired, it will indicate the humidity that you have selected
• When you program the time for the unit to turn on and off, it will show the hours.
• When the environment humidity is lower than 35%, it will show “LO”
• When the environment humidity is higher than 95%, it will show “HI”
1. Power Indication Light will light when the unit is plugged in, regardless of whether
the unit is operating or not.
2. Water full indication light illuminates red when the drainage tank is full. If light
is on, empty the water out of the drainage tank and make sure that the tank is
repositioned properly.
3. Swing Indication illuminates when ‘Swing’ is selected and the air outlet louvre will
oscillate.
4. Timer indication light will illuminate green when you program the timer function to
turn on and turn off automatically.
5. Setting indication light will illuminate during setting of the humidity level.
6. High indication light will illuminate when you program the unit to run in the high fan
speed.
7. Low indication light will illuminate when you program the unit to run in the low fan
speed.

6
OPERATION
WARNING: Before you start the unit, please make sure that the air outlet is open. If the
ap is left closed, the unit may overheat.
Power ON/OFF
• Press the power button to start the unit, and press again to shut down.
• The buzzer will sound when the unit is powered on, and the LED display will show
the default humidity level setting of 60% and start up with a low fan speed.
Swing Mode
• Press the button once to swing the air outlet louvre, press the button again to
stop.
Timer Setting
When plugged in, press button rst and then press to set boot time.
When unit is operating, press button and then press button to set shut
down time.
Adjusting Humidity
• Press to set the desired humidity level in the room, which can be set in the
order of:40-80% in 5% increments using the button.
NOTE: When the relative humidity in the room is lower then the selected humidity, the
operation of the unit will stop automatically.
Fan Speed Setting
• Press to set the desired fan speed. It can be adjusted between high speed
and low speed.
Setting IONIC/UV level
Press to set the Ion/UV function. The green/ blue LED light will turn on when the
ionic/UV function is operating. Press the button again to cancel the ionic/ UV function.
WATER DRAINAGE
• The dehumidier has an internal water tank to collect water that accumulates
during the cooling process. This tank will need to be emptied periodically.
• When the internal water tank is full the unit will go into standby mode and the
buzzer will sound 15 times.
• The water tank will need to be emptied before normal operation can be resumed.
• Lightly press on the sides of the tank with both hands and pull the tank out gently.
• Discard the collected water.
• Replace the drainage tank by pressing it into place rmly on both sides, and when
correctly positioned, normal operation can resume.

7
WARNING: Do not remove the oat from the water tank.
The water full sensor will no longer be able to detect the
water level correctly without the oat and water may leak
from the water tank.
CONTINUOUS WATER DRAINAGE
• The dehumidier features a continuous drainage port. Using a plastic pipe (with an
inner diameter of 10mm) inserted into the drain hole (on intermediate plate), and
arrange the drain pipe neatly.
• The water in the drainage tank can be
continuously drained from the continuous port
on the unit into a suitable drain.
Drainage port

8
MAINTENANCE
Important: In order to avoid an electric shock, power-off the dehumidier and
disconnect the mains plug before performing any maintenance or repair activities.
Cleaning
• Unplug from the mains supply before cleaning.
• Do not splash water into the dehumidier.
• Clean the outside of the dehumidier with a damp, not wet, cloth and dry
thoroughly before using.
• Do not use any chemicals, abrasives or solvents, which may damage the surface
of the dehumidier.
Filters
Clean the lters every two weeks. If the lters become blocked by dust, the efciency
of the dehumidier will be reduced.
• Remove the air lters on the front of the unit.
• Run a vacuum cleaner lightly over the surface of the lters to remove dust.
• If the lters are exceptionally dirty wash them in warm water and a mild detergent
and allow to dry thoroughly before retting.
Note: Do not operate the air dehumidier without the lters.

9
Long term storage
If the dehumidier is not going to be used for a long time, please follow the steps
below:
• Unplug the unit from the mains.
• Remove the internal water tank and empty it and replace it.
• Clean and dry the lters and then reinstall them.
• Put the dehumidier back in its original carton and store in a cool, dry place.
FURTHER SAFETY INFORMATION
Information on servicing
• Checks to the work area prior to beginning work on systems containing ammable
refrigerants, safety checks are necessary to ensure that the risk of ignition is
minimised. For repair to the refrigerating system, the following precautions shall be
complied with prior to conducting work on the system.
Work procedure
• Work shall be undertaken under a controlled procedure so as to minimise the risk
of a ammable gas or vapour being present while the work is being performed.
General work area
• All maintenance staff and others working in the local area shall be instructed on
the nature of work being carried out. Work in conned spaces shall be avoided.
The area around the workspace shall be sectioned off. Ensure that the conditions
within the area have been made safe by control of ammable material.
Checking for presence of refrigerant
• The area shall be checked with an appropriate refrigerant detector prior to
and during work, to ensure the technician is aware of potentially ammable
atmospheres. Ensure that the leak detection equipment being used is suitable
for use with ammable refrigerants, i.e. non-sparking, adequately sealed or
intrinsically safe.
Presence of re extinguisher
• If any hot work is to be conducted on the refrigeration equipment or any associated
parts, appropriate re extinguishing equipment shall be available to hand. Have a
dry powder or CO2 re extinguisher adjacent to the charging area.
No ignition sources
• Any person carrying out work in relation to a refrigeration system which involves
exposing any pipe work that contains or has contained ammable refrigerant shall
use any sources of ignition in such a manner that it may lead to the risk of re
or explosion. All possible ignition sources, including cigarette smoking, should
be kept sufciently far away from the site of installation, repairing, removing and
disposal, during which ammable refrigerant can possibly be released to the
surrounding space. Prior to work taking place, the area around the equipment is
to be surveyed to make sure that there are no ammable hazards or ignition risks.
“No Smoking” signs shall be displayed.

10
Ventilated area
• Ensure that the area is in the open or that it is adequately ventilated before
breaking into the system or conducting any hot work. A degree of ventilation shall
continue during the period that the work is carried out. The ventilation should
safely disperse any released refrigerant and preferably expel it externally into the
atmosphere.
Checks to the refrigeration equipment
• Where electrical components are being changed, they shall be t for the purpose
and to the correct specication. At all times the manufacturer’s maintenance
and service guidelines shall be followed. If in doubt consult the manufacturer’s
technical department for assistance.
The following checks shall be applied to installations using ammable refrigerants:
1. The charge size is in accordance with the room size within which the
refrigerant containing parts are installed.
2. The ventilation machinery and outlets are operating adequately and are not
obstructed.
3. If an indirect refrigerating circuit is being used, the secondary circuit shall be
checked for the presence of refrigerant.
4. Marking to the equipment continues to be visible and legible. Markings and
signs that are illegible shall be replaced.
5. Refrigeration pipe or components are installed in a position where they
are unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components are constructed of materials
which are inherently resistant to corrosion or are suitably protected against
corrosion.
Checks to electrical devices
• Repair and maintenance to electrical components shall include initial safety
checks and component inspection procedures. If a fault exists that could
compromise safety, then no electrical supply shall be connected to the circuit until
it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is
necessary to continue operation, an adequate temporary solution shall be used.
This shall be reported to the owner of the equipment so all parties are advised.
Initial safety checks shall include:
1. That capacitors are discharged: this shall be done in a safe manner to avoid
possibility of sparking.
2. That there no live electrical components and wiring are exposed while
charging, recovering or purging the system.
3. That there is continuity of earth bonding.
Repairs to sealed components
• During repairs to sealed components, all electrical supplies shall be disconnected
from the equipment being worked upon prior to any removal of sealed covers,
etc. If it is absolutely necessary to have an electrical supply to equipment during
servicing, then a permanently operating form of leak detection shall be located at
the most critical point to warn of a potentially hazardous situation.
• Particular attention shall be paid to the following to ensure that by working on
electrical components, the casing is not altered in such a way that the level of

11
protection is affected. This shall include damage to cables, excessive number
of connections, terminals not made to original specication, damage to seals,
incorrect tting of glands, etc.
• Ensure that apparatus is mounted securely. Ensure that seals or sealing materials
have not degraded such that they no longer serve the purpose of preventing the
ingress of ammable atmospheres. Replacement parts shall be in accordance with
the manufacturer’s specications.
Note: The use of silicon sealant may inhibit the effectiveness of some types of leak
detection equipment. Intrinsically safe components do not have to be isolated prior to
working on them.
Repair to intrinsically safe components
• Do not apply any permanent inductive or capacitance loads to the circuit without
ensuring that this will not exceed the permissible voltage and current permitted for
the equipment in use.
• Intrinsically safe components are the only types that can be worked on while live
in the presence of a ammable atmosphere. The test apparatus shall be at the
correct rating.
• Replace components only with parts specied by the manufacturer. Other parts
may result in the ignition of refrigerant in the atmosphere from a leak.
Cabling
• Check that cabling will not be subject to wear, corrosion, excessive pressure,
vibration, sharp edges or any other adverse environmental effects. The check shall
also take into account the effects of aging or continual vibration from sources such
as compressors or fans.
Detection of ammable refrigerants
• Under no circumstances shall potential sources of ignition be used in the
searching for or detection of refrigerant leaks. A halide torch (or any other detector
using a naked ame) shall not be used.
Leak detection methods
• The following leak detection methods are deemed acceptable for systems
containing ammable refrigerants.
• Electronic leak detectors shall be used to detect ammable refrigerants, but the
sensitivity may not be adequate, or may need re-calibration.
(Detection equipment shall be calibrated in a refrigerant-free area).
• Ensure that the detector is not a potential source of ignition and is suitable for the
refrigerant used. Leak detection equipment shall be set at a percentage of the
LFL of the refrigerant and shall be calibrated to the refrigerant employed and the
appropriate percentage of gas (25%maximum) is conrmed.
• Leak detection uids are suitable for use with most refrigerants but the use of
detergents containing chlorine shall be avoided as the chlorine may react with the
refrigerant and corrode the copper pipe-work.
• If a leak is suspected, all naked ames shall be removed/ extinguished.
• If a leakage of refrigerant is found which requires brazing, all of the refrigerant
shall be recovered from the system, or isolated (by means of shut off valves) in a
part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be
purged through the system both before and during the brazing process.

12
Removal and evacuation
• When breaking into the refrigerant circuit to make repairs – or for any other
purpose – conventional procedures shall be used. However, it is important that
best practice is followed since ammability is a consideration. The following
procedure shall be adhered to:
1. Remove refrigerant.
2. Purge the circuit with inert gas.
3. Evacuate.
4. Purge again with inert gas.
5. Open the circuit by cutting or brazing.
• The refrigerant charge shall be recovered into the correct recovery cylinders. The
system shall be “ushed” with OFN to render the unit safe. This process may need
to be repeated several times. Compressed air or oxygen shall not be used for this
task.
• Flushing shall be achieved by breaking the vacuum in the system with OFN
and continuing to ll until the working pressure is achieved, then venting to
atmosphere, and nally pulling down to a vacuum. This process shall be repeated
until no refrigerant is within the system. When the nal OFN charge is used, the
system shall be vented down to atmospheric pressure to enable work to take
place. This operation is absolutely vital if brazing operations on the pipe-work are
to take place.
• Ensure that the outlet for the vacuum pump is not close to any ignition sources and
there is ventilation available.
Charging procedures
• In addition to conventional charging procedures, the following requirements shall
be followed.
1. Ensure that contamination of different refrigerants does not occur when using
charging equipment. Hoses or lines shall be as short as possible to minimise
the amount of refrigerant contained in them.
2. Cylinders shall be kept upright.
3. Ensure that the refrigeration system is earthed prior to charging the system
with refrigerant.
4. Label the system when charging is complete (if not already).
5. Extreme care shall be taken not to overll the refrigeration system.
6. Prior to recharging the system it shall be pressure tested with OFN.
7. The system shall be leak tested on completion of charging but prior to
commissioning. A follow up leak test shall be carried out prior to leaving the
site.
Decommissioning
• Before carrying out this procedure, it is essential that the technician is completely
familiar with the equipment and all its detail. It is recommended good practice
that all refrigerants are recovered safely. Prior to the task being carried out, an oil
and refrigerant sample shall be taken in case analysis is required prior to re-use
of reclaimed refrigerant. It is essential that electrical power is available before the
task is commenced.
• Become familiar with the equipment and its operation.

13
• Isolate system electrically.
• Before attempting the procedure ensure that:
1. Mechanical handling equipment is available, if required, for handling
refrigerant cylinders.
2. All personal protective equipment is available and being used correctly.
3. Pump down refrigerant system, if possible.
4. If a vacuum is not possible, make a manifold so that refrigerant can be
removed from various parts of the system.
5. Make sure that cylinder is situated on the scales before recovery takes place.
6. Start the recovery machine and operate in accordance with manufacturer’s
instructions.
7. Do not overll cylinders. (No more than 80 % volume liquid charge).
8. Do not exceed the maximum working pressure of the cylinder, even
temporarily.
9. When the cylinders have been lled correctly and the process completed,
make sure that the cylinders and the equipment are removed from site
promptly and all isolation valves on the equipment are closed off.
10. Recovered refrigerant shall not be charged into another refrigeration system
unless it has been cleaned and checked.
Labelling
• Equipment shall be labelled stating that it has been de-commissioned and emptied
of refrigerant. The label shall be dated and signed. Ensure that there are labels on
the equipment stating the equipment contains ammable refrigerant.
Recovery
• When removing refrigerant from a system, either for servicing or decommissioning,
it is recommended good practice that all refrigerants are removed safely.
• When transferring refrigerant into cylinders, ensure that only appropriate
refrigerant recovery cylinders are employed. Ensure that the correct number of
cylinders for holding the total system charge is available.
• All cylinders to be used are designated for the recovered refrigerant and labelled
for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders
shall be complete with pressure relief valve and associated shut-off valves in good
working order.
• Empty recovery cylinders are evacuated and, if possible, cooled before recovery
occurs.
• The recovery equipment shall be in good working order with a set of instructions
concerning the equipment that is at hand and shall be suitable for the recovery
of ammable refrigerants. In addition, a set of calibrated weighing scales shall
be available and in good working order. Hoses shall be complete with leak-free
disconnect couplings and in good condition. Before using the recovery machine,
check that it is in satisfactory working order, has been properly maintained and that
any associated electrical components are sealed to prevent ignition in the event of
a refrigerant release. Consult manufacturer if in doubt.
• The recovered refrigerant shall be returned to the refrigerant supplier in the correct
recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix
refrigerants in recovery units and especially not in cylinders.

14
• If compressors or compressor oils are to be removed, ensure that they have been
evacuated to an acceptable level to make certain that ammable refrigerant does
not remain within the lubricant. The evacuation process shall be carried out prior to
returning the compressor to the suppliers. Only electric heating to the compressor
body shall be employed to accelerate this process. When oil is drained from a
system, it shall be carried out safely.
TROUBLESHOOTING
Trouble Cause Solution
Appliance
does not work
• Power is off
• Water tank is full
• The ambient temperature is too
low or too high
• Switch the power on
• Drain internal water tank
• Recommend to use the
machine in at the temperature
range of 7-35oC (44-95oF)
The
dehumidifying
function
doesn’t work
• Filters are too dirty
• Is the intake duct or discharge
duct obstructed?
• Clean the air lter.
• Remove the obstruction from
the discharge duct or intake
duct.
Poor air
discharge
• Air lter is dirty
• Air intake is obstructed.
• Clean the air lter.
• Check for obstructions.
Noisy
operation • Unit is not level • Check the unit is stood level
on a at even surface.

15
TECHNICAL SPECIFICATION
PELL0309 PELL0310
Main voltage 220-240V ~ 50Hz
Rated input power 480W 750W
Power standby mode 0W
Dehumidifying capacity 30L/24hr 40L/24hr
Air ow 250m³/h
Sound power level ≤47dB(A)
Refrigerant/charge R290/100g R290/130g
Fan speeds 2
Recommended room oor area 25-30m² 30-40m²
Dimensions 360x360x610mm
Weight 16kg Net / 17kg Gross 17kg Net / 18kg Gross

16
INFORMATION ON WASTE DISPOSAL FOR CONSUMERS OF
ELECTRICAL & ELECTRONIC EQUIPMENT.
When this product has reached the end of its life it must be treated as Waste Electrical & Electronic
Equipment (WEEE). Any WEEE marked products must not be mixed with general household waste,
but kept separate for the treatment, recovery and recycling of the materials used. Contact your local
authority for details of recycling schemes in your area.
Man Rev 1.0
Made in China
PR2 9PP PO Box 13362 Dublin 2
This manual suits for next models
1
Table of contents
Other Pro-Elec Dehumidifier manuals