Prostat OEM PSP4271C User manual

User Manual
Commercial Smart Wi-Fi Thermostat
PSP4271C Up to 4-heat / 2-cool with Humidity Control
OPTIONAL Wi-Fi and Local API with module
Read all instructions before proceeding.
Store this manual for future reference
© Copyright 2021 All Rights Reserved. Made in China
PSP4271C User Manual.indd 1PSP4271C User Manual.indd 1 6/9/21 10:37 AM6/9/21 10:37 AM

2
User Manual
FCC Compliance Statement
This equipment has been tested and found to comply with the limits for an intentional radiator, pursuant to Part 15, subpart C of the FCC
rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment
generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause
harmful interference in radio communications. However, there is no guarantee that the interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that of the receiver.
• Consult the dealer or an experienced radio or TV technician for help.
Notice: Only peripherals complying with FCC limits may be attached to this equipment. Operation with noncompliant peripherals or
peripherals not recommended by ProStat+™, is likely to result in interference to radio and TV reception. Changes or modifications to the
product, not expressly approved by ProStat+could void the user’s authority to operate the equipment.
FCC - INDOOR Mobile Radio Information:
To comply with FCC/IC RF exposure limits for general population / uncontrolled exposure, the antenna(s) used for this transmitter must be
installed to provide a separation distance of at least 20 cm from all persons and must not be co-located or operating in conjunction with
any other antenna or transmitter.
This Device complies with Industry Canada License-exempt RSS standard(s). Operation is subject to the following two conditions: 1) this
device may not cause interference, and 2) this device must accept any interference, including interference that may cause undesired
operation of the device.
Follow the Installation Instructions before proceeding. Set the thermostat
mode to “OFF” prior to changing settings in setup or restoring Factory
Defaults.
CAUTIO
N
PSP4271C User Manual.indd 2PSP4271C User Manual.indd 2 6/9/21 10:37 AM6/9/21 10:37 AM

3User Manual
This thermostat has the ability to receive updates to its firmware. Periodically firmware updates are released by the manufacturer to add
features and/or performance enhancements. This manual was produced reflecting the most current firmware/feature set at the time
of publication, firmware rev. 1.0. Firmware releases after rev. 1.0 may not be adequately depicted in this manual. Please refer to the
appropriate website or contact your place of purchase to learn about changes to the thermostat after firmware release 1.0.
Under Industry Canada regulations, this radio transmitter may only operate using an antenna of a type and maximum (or
lesser) gain approved for the transmitter by Industry Canada. To reduce potential radio interference to other users, the
antenna type and its gain should be so chosen that the equivalent isotropically radiated power (e.i.r.p.) is not more than
that necessary for successful communication.
Cet appareil est conforme avec Industrie Canada, exempts de licence standard RSS(s). Son fonctionnement est soumis aux deux conditions
suivantes: 1) ce dispositif ne doit pas causer d’interférences, et 2) ce dispositif doit accepter toute interférence, y compris les interférences
qui peuvent causer un mauvais fonctionnement de l’appareil.
En vertu des règlements d’Industrie Canada, cet émetteur de radio ne peut fonctionner en utilisant une antenne d’un type et maximale
(ou moins) Gain approuvé pour l’émetteur par Industrie Canada. Pour réduire les interférences radio potentielles aux autres utilisateurs, le
type d’antenne et son gain doivent être choisis afin que la puissance isotrope rayonnée équivalente (PIRE) ne est pas plus de ce qui est
nécessaire pour une communication réussie.
We, ProStat+, declare under our sole responsibility that the device to which this declaration relates: Complies with Part 15 of the FCC
Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
Innovation, Science and Economic Development Canada
ICES-003 Compliance Label: CAN ICES-3 (B)/NM8-3(B)
PSP4271C User Manual.indd 3PSP4271C User Manual.indd 3 6/9/21 10:37 AM6/9/21 10:37 AM

4
User Manual
Features .......................................................................5
Terms ...........................................................................6
1 About Your Thermostat
Front Panel ...................................................................7
Display .........................................................................9
2 Basic Operation
Setting the Clock and Day...........................................12
Heat or Cool Mode ......................................................12
Selecting your Desired Temperature............................13
Auto-Changeover Mode ..............................................13
Using the Override Button ...........................................13
Viewing the Temperature Sensors...............................14
3 Setup Step Table...................................................15
How to Change Settings in the Setup Screens.............17
Programming a Daily Schedule ...................................18
Backlight ....................................................................20
4 Advanced Features & Operation
Emergency Heat .........................................................20
Wi-Fi Module .............................................................21
Factory Defaults..........................................................22
Follow Installation Instructions carefully. Disconnect Power to the Heater/Air Conditioner
before removing the old thermostat and installing the new thermostat.
CAUTION
IMPORTANT
Contents
PSP4271C User Manual.indd 4PSP4271C User Manual.indd 4 6/9/21 10:37 AM6/9/21 10:37 AM

5User Manual
3 Setup Step Table...................................................15
How to Change Settings in the Setup Screens.............17
Programming a Daily Schedule ...................................18
Backlight ....................................................................20
4 Advanced Features & Operation
Emergency Heat .........................................................20
Wi-Fi Module .............................................................21
Factory Defaults..........................................................22
• Choose 7-Day, 5/1/1 day or 1-Day Programming
• 365-Day Holiday Programming (when connected
to ProStat+ Web Portal)
• Smart Fan runs continuous during Occupied;
Auto during Unoccupied
• Adjustable deadbands for all stages of heating
and cooling
• Adjustable staging timers for all stages of heating
and cooling
• Adjustable staging turnoffs: deadband or keep
active until setpoint
Congratulations and thank you for purchasing your new ProStat+Smart Wi-Fi thermostat.
This guide is intended to help you install and setup the basic features of your thermostat.
Features
• Smart recovery auto-adjusts Occ 1 start time
• Random Start ensures staggered equip. starts
• Dry Contact for FDD alerts, condensate
alarm, etc.
• Setpoint Limiting
• Outdoor sensor ready with Hi/Low readouts
for the day
• Choice of English, Spanish or French
for Scrolling Display
• CA Title 24 Compliant
• OEM-Branded Equipment Badges Included
PSP4271C User Manual.indd 5PSP4271C User Manual.indd 5 6/9/21 10:37 AM6/9/21 10:37 AM

6
User Manual
Terms
Auto-Changeover: A mode in which the thermostat will turn on the heating or cooling based on room
temperature demand.
Cool Setpoint: The warmest temperature that the space should rise to before cooling is turned on (without
regard to deadband).
Deadband: The number of degrees the thermostat will wait, once a setpoint has been reached, before energizing
heating or cooling.
Differential: The forced temperature difference between the heat setpoint and the cool setpoint.
Heat Setpoint: The coolest temperature that the space should drop to before heating is turned on
(without regard to deadband).
Icon: The word or symbol that appears on the thermostat display.
Mode: The current operating condition of the thermostat (i.e. Off, Heat, Cool, Auto, Program On).
Override: During programmed unoccupied periods, pressing the Override button will force the thermostat into
occupied settings. During programmed occupied periods, pressing the Override button will force the thermostat into
unoccpied settings.
Temperature Swing: Same as Deadband.
Time Period Programming: A program that allows the thermostat to automatically adjust the heat setpoint
and/or the cool setpoint based on the time of the day.
PSP4271C User Manual.indd 6PSP4271C User Manual.indd 6 6/9/21 10:37 AM6/9/21 10:37 AM

7User Manual
1Backlit, Scrolling LCD Display
2OVERRIDE Button
3Warmer & Cooler Buttons
4Heat or Cool Indicator
Heat = Red, Cool = Green
5Setup Buttons behind door
1 About Your Thermostat
Table for button presses
that are required for
entering various menus
1
2
34 5
Front Display
TO ENTER MENUS BUTTON PRESS
Setup Steps Press SETUP button
Time Schedule Press SET CLOCK button
Emergency Heat Press EMERGCY HEAT button
Lockout Buttons MODE, Up & Down for 2 seconds
Calibration Press SETUP for 10 seconds
Wireless Setup Press ACCESSRY SETUP button
PSP4271C User Manual.indd 7PSP4271C User Manual.indd 7 6/9/21 10:37 AM6/9/21 10:37 AM

8
User Manual
Button Callouts Inside Doors
PSP4271C User Manual.indd 8PSP4271C User Manual.indd 8 6/9/21 10:37 AM6/9/21 10:37 AM

9User Manual
2
1
6
4
3
3
5
Display
Features
3RD 4TH
1 The scrolling display will be used to help you easily navigate the setup screens in the thermostat.
2 Clock with Day of the Week
Indicates the current time and day. This clock is also used to program the time period schedules.
3 Mode Indicators Selects the operational mode of the equipment.
HEAT - Indicates the heating mode.
COOL - Indicates the air conditioning mode.
HEAT & COOL - Indicates the system will automatically change-over between heat and cool modes as
the temperature varies.
Neither Heat or Cool - Indicates heating and cooling is turned off.
4 Program ON icon
Indicates that Time Period Programming is running or is enabled to be set.
5Room Temperature Display
Indicates the current room temperature and displays the outdoor temperature when selected.
6 Outdoor icon
Indicates the temperature displayed is from the optional outdoor sensor or the ProStat+Web Portal.
PSP4271C User Manual.indd 9PSP4271C User Manual.indd 9 6/9/21 10:37 AM6/9/21 10:37 AM

10
User Manual
3RD 4TH
7Desired Set Temperature
Indicates desired room temperature(s). Also displays the highest and lowest temperatures
for the day.
8 Wi-Fi icons
One dot indicates the thermostat recognizes the wireless module. The “full” icon indicates the
thermostat is currently connected to the Local access point, via the optional Wi-Fi Module.
9 Setup Step icon
Indicates the step number when the thermostat is in the setup mode.
10 2nd, 3rd and 4th Stage icons
Indicates what stage of cooling or heating is currently energized.
11 icon
Indicates the keypad has been locked.
7
7
8
10
10 11
9
Display
Features
PSP4271C User Manual.indd 10PSP4271C User Manual.indd 10 6/9/21 10:37 AM6/9/21 10:37 AM

11 User Manual
3RD 4TH
12 AuxHeat icon
Indicates 2nd stage electric strip heat is being used when the thermostat is programmed for Heat
Pump operation.
13 Lo icon
Indicates the lowest recorded outdoor temperature for the day.*
14 Hi icon
Indicates the highest recorded outdoor temperature for the day.*
15 Fan On icon
Indicates constant, continuous fan operation. When Fan On is not lit - indicates the fan will only
operate when necessary to heat or to cool.
* Hi and Lo Temperatures for the day reset at midnight and require an outdoor sensor or
ProStat+ Skyport connectivity.
14
12
15
13
Display
Features
PSP4271C User Manual.indd 11PSP4271C User Manual.indd 11 6/9/21 10:37 AM6/9/21 10:37 AM

12
User Manual
2 Basic Operation
During Setup and Programming:
Press the WARMER or COOLER buttons to modify the selection. Press the MODE button to advance and confirm through
the setup steps.
Setting the Clock and Day*
*Not available when connected to a ProStat+Account
Press the SET CLOCK button. Adjust the clock using the WARMER or COOLER buttons. Press MODE to advance to the day
setting. Adjust the day using the WARMER or COOLER buttons. Press the SET CLOCK button to confirm settings.
TIP: To adjust the time by hours press and hold the FAN button while pressing the WARMER or COOLER buttons.
Selecting the Heat or Cool Mode
Select mode by pressing the MODE button.
Heating Only - Only the heating operation will be controlled by the thermostat in this mode.
Cooling Only - Only the cooling operation will be controlled by the thermostat in this mode.
Heating or Cooling (Auto-Changeover) - AUTO will automatically select heat or cool based on room temperature demand.
Neither Heat or Cool (OFF) - OFF indicates heating and cooling is turned off.
Tip : When changing MODE, the new mode will temporarily be shown on the scrolling display
WARMER
COOLER
MODE
Set
Clock
WARMER
COOLER
MODE
Set
Clock
PSP4271C User Manual.indd 12PSP4271C User Manual.indd 12 6/9/21 10:37 AM6/9/21 10:37 AM

13 User Manual
Selecting Your Desired Temperature (adjusting the setpoints)
Using the Override Button
Unoccupied Operation - During programmed, unoccupied periods, pressing the
OVERRIDE button will force the thermostat into Occupied 1 settings for 30 minutes.
Each press of the OVERRIDE button will add another 30 minutes of time up to 4 hours.
Auto-Changeover Mode
Pressing the WARMER or COOLER buttons in Auto mode will adjust both the heat and cool setpoints simultaneously. To adjust
the heat and cool setpoints individually, choose HEAT mode to adjust the heat setpoint, and COOL mode to adjust the cool
setpoint, then return to AUTO mode.
Adjust the desired set
temperature with these buttons
Heat or Cool Mode
Pressing the WARMER or COOLER buttons in Heat or Cool mode will adjust only the heat or cool set temperature.
Turning on the Time Period Program
Pressing the MODE button should cycle through OFF, then the available modes (setup step #2) then Program ON. Note that
this sequence may be restricted due to step #2 in Setup. The thermostat can be configured to be non-programmable which
will keep Program ON from appearing in the MODE sequence. The thermostat can also be configured to force the program to
always be running so the MODE button will have no effect.
Using the Fan Button
Fan On indicates constant fan operation. Fan On is not allowed when the thermostat is in the
OFF mode. Pressing the FAN button toggles this feature on or off. Fan auto will allow the fan to
run only when there is a heat or cool demand.
NOTE: OVERRIDE may
only be used when the
thermostat is set to
PROGRAM ON.
OUTDOOR
ACCSRY
HUMIDITY
OVERRIDE
FAN
ON|AU
TO
PSP4271C User Manual.indd 13PSP4271C User Manual.indd 13 6/9/21 10:37 AM6/9/21 10:37 AM

14
User Manual
If the maximum time has been set, the next press of the OVERRIDE button will reset the timer and return the thermostat
to the correct time period program for the day.
Occupied Operation - During programmed, occupied periods, pressing the OVERRIDE button will force the thermostat
into an unoccupied period for the rest of the day. During this forced unoccupied period the OVERRIDE button will operate
as described above
Viewing the Temperature Sensors
OUTDOOR – Press the Accessory Status button. If an Outdoor sensor is connected,
the reading along with the high and low temperatures for the day will be displayed. The high and low
temperatures reset at 12:00 am. If connected to a ProStat+ Skyport account, the temperatures for your
zipcode will be shown unless a wired sensor is connected.
ACCESSORY
STATUS
PSP4271C User Manual.indd 14PSP4271C User Manual.indd 14 6/9/21 10:37 AM6/9/21 10:37 AM

15 User Manual
FD = Factory Default Setting
Installer
Setup Steps
(see Installer
Manual for
more details)
3 Setup Step Table
1 Prog Mode Non, 1 Day, 5/1/1 Day, 7 Day 7 Day
2 Available Modes Heat/Cool/Auto/Off, Heat/Cool/
Heat/Cool/Off, Heat/Off, Cool/Off Auto/Off
3 Backlight On, Off Off
4 Backlight Level Off thru 7 levels of brightness Level 5
5 Night Dimmer On/Off Off
6 Night Dimmer Brightness Off thru 7 levels of brightness 2 (20%)
7 Night Dimmer Start Time 12A-12A 8:00P
8 Night Dimmer Stop Time 12A-12A 6:00A
9 Current Service Filter Runtime Hours 0-1999 Hours 0
10 Current Service Filter Calendar Days 0-720 Days 0
11 Current Override Hours 0-1999 Hours 0
12 Current UV Lamp Calendar Days 0-720 Days 0
13 Set Service Filter Runtime Hours 0-1950 hours 0
14 Set Service Filter Calendar Days 0-720 Days 0
15 Set UV Lamp Calendar Days 0-720 Days 0
16 Language English, Espanol, Francais English
17 Scrolling Method “L-R Slow, L-R Fast, Word “Whole Words
L-R Slow, Word L-R Fast, Center Fast”
Whole Word L Slow, Whole
Word R Slow, Whl Wrd Center
Fast, Whl Wrd Center Slow”
18 Setpoint Limits 0 - 3 0
19 Max Heat Setpoint 35 - 99 Degrees 74
20 Min Cool Setpoint 35 - 99 Degrees 70
21 Cycles Per Hour No Limit, 2, 3, 4, 5, 6 6
22 Compressor Minimum Off Min. 0, 3, 5 Minutes 5
23 Min. Heat/Cool Setpoint Difference 0 - 6 Degrees 2
24 Number of Heat Stages 0 - 3 2
Step# Description Pg# Range FD
PSP4271C User Manual.indd 15PSP4271C User Manual.indd 15 6/9/21 10:37 AM6/9/21 10:37 AM

16
User Manual
25 Number of Cool Stages 0 - 2 1
26 Number Of Compressor Stages 1, 2 1
27 Number of Aux Stages 0, 1, 2 0
28 1st Stage Deadband 1 - 6 Degrees 2
29 2nd Stage Deadband 0 - 10 Degrees 2
30 3rd Stage Deadband 0 - 10 Degrees 2
31 4th Stage Deadband 0 - 10 Degrees 2
32 Minutes Between 1st and 2nd Stage 0 - 60 Minutes 2
33 Minutes Between 2nd and 3rd Stage 0 - 60 Minutes 2
34 Minutes Between 3rd and 4th Stage 0 - 60 Minutes 2
35 2nd StageTurnoff Point Deadband, Setpoint Deadband
36 3rd StageTurnoff Point Deadband, Setpoint Deadband
37 4th Stage Turnoff Point Deadband, Setpoint Deadband
38 Fan Off Delay 0 - 120 Seconds 0
39 F/C Fahrenheit (F), Celsius (C) F
40 Comfort Recovery On, Off Off
41 Dry Contact Polarity Open, Closed Open
42 Dry Contact Use Condensate Pan, Occupied
FDD, Holiday, Doorswitch
43 Skyport On, Off On
44 Local API On, Off Off
45 ADR On, Off On
46 ADR Action Observe Setpoint Offset, Observe
Observe Static Setpoints Setpoints
Offsets
47 Event Max Cool Setpoint 65 - 99 90
48 Event Min Heat Setpoint 50 - 99 50
49 Static Cool Setpoint 65 - 99 82
50 Static Heat Setpoint 35 - 99 60
51 Cool Setpoint Offset 1 to 10 4
52 Heat Setpoint Offset -1 to -10 -4
53 Press Fan To Clear All Messages
Step# Description Pg# Range FD
Installer
Setup Steps
(see Installer
Manual for
more details)
PSP4271C User Manual.indd 16PSP4271C User Manual.indd 16 6/9/21 10:37 AM6/9/21 10:37 AM

17
User Manual
Installer
Setup Steps
(see Installer
Manual for
more details)
Time Period Programming
Selecting Your Time Period Schedule (setup step 1) : Press the Setup button
This thermostat may be configured to be programmable or non programmable.
7 Day Program - Allows all seven days to be programmed independently.
Non Program - No advanced time period programming available.
1 Day Program - Allows one 24 hour day to be programmed. This same schedule will be repeated every day the
program is set to run.
5/1/1 Day Program - Allows weekdays, Saturday, and Sunday to be programmed independently.
Selecting Your Available Modes (setup step 2)
Auto-Changeover - Allows the thermostat to turn on heating or cooling based on room temperature demand.
Also allows the manual selection of HEAT only or COOL only and OFF.
Heat and Cool - Allows the thermostat to turn on heating or cooling depending on which one has been manually
selected. Auto-Changeover is not available when this is selected.
Heat Only - Allows the thermostat to only turn on HEAT or OFF modes.
Cool Only - Allows the thermostat to only turn on COOL or OFF modes. continued next page
How to Change Settings in the Setup Screens
To enter Setup screens, press the SETUP button, then press
MODE. Use the WARMER or COOLER buttons to adjust the value
of your selection. Press MODE to advance to the next setup step.
Press SETUP again to leave the setup screens.
WARMER
COOLER
MODE
Set
Clock
WARMER
COOLER
MODE
Set
Clock
PSP4271C User Manual.indd 17PSP4271C User Manual.indd 17 6/9/21 10:37 AM6/9/21 10:37 AM

18 User Manual
Programming a Daily Time Period Schedule
To enable (RUN) or turn ON the Time Period Schedule press the Program button momentarily.
To turn Off the Time Period Schedule press this button again.
To alter the Time Period Schedule settings; press & hold this button for 5 seconds until the SET PROGRAM prompt appears.
Modify the settings with the Warmer and Cooler buttons. Use the MODE button to advance through the steps. Press the
Program button again to leave the setup screens.
WARMER
COOLER
MODE
ADJUST NEXT
OFF
|
RUN
HOLD
TO SET
Once the Set Program prompt appears the Mode button will step you through the settings as follows:
Set the Unoccupied Mode – Press the Warmer or Cooler buttons to choose the mode for the Unoccupied period.
The thermostat is in Unoccupied when the Time Period Schedule is running and there is not an active Occupied period.
The choices are: Off, Heat only, Cool only and AUTO changeover.
Adjust the Unoccupied Cool Setpoint – Press the Warmer or Cooler buttons to adjust the Cooling setpoint for times
when the thermostat is in Unoccupied.
Adjust the Unoccupied Heat Setpoint – Press the Warmer or Cooler buttons to adjust the Heating setpoint for times
when the thermostat is in Unoccupied.
Select the number of Occupied time periods – Press the Warmer or Cooler buttons to choose the maximum number
(up to 3 maximum) of Occupied time periods in a day.
PSP4271C User Manual.indd 18PSP4271C User Manual.indd 18 6/9/21 10:37 AM6/9/21 10:37 AM

19
User Manual
Select the Mode for the Occupied period – Press the Warmer or Cooler buttons to choose the mode for the occupied
period. The choices are: Off, Heat only, Cool only and AUTO changeover.
Adjust the Occupied Cool Setpoint – Press the Warmer or Cooler buttons to adjust the Cooling setpoint for comfort.
Adjust the Occupied Heat Setpoint – Press the Warmer or Cooler buttons to adjust the Heating setpoint for comfort.
The following steps determine when the Occupied period(s) will be active.
Enable Occupied 1 – Press the Warmer or Cooler buttons to enable (On) or to disable (Off) Occupied 1 on Monday.
Adjust the Start Time for Occupied 1 – Press the Warmer or Cooler buttons to adjust the start time for
Occupied 1 on Monday.
Adjust the Stop Time for Occupied 1 – Press the Warmer or Cooler buttons to adjust the stop time for
Occupied 1 on Monday.
Upon pressing Mode after the above step; you will be prompted to Save and Exit or Copy this Occupied schedule
to another day.
- To save and exit – Press the Program button.
- To Copy Monday’s settings/schedule to Tuesday – Press Up and then Mode. Press Mode again to copy the Monday
settings/schedule to subsequent days.
-To Program Another Day – Press Down and then press the Mode button to select the day to program.
Repeat the above steps for each day you would like to program.
PSP4271C User Manual.indd 19PSP4271C User Manual.indd 19 6/9/21 10:37 AM6/9/21 10:37 AM

20 User Manual
Emergency Heat
Only available if you have a Heat Pump installed. To initiate the Emergency Heat feature, press the EMERGCY
HEAT button. During Emergency Heat operation the thermostat will turn on the fan and auxiliary stages of
heat when there is a demand for heat. The 1st stage of heating and all stages of cooling will be unavailable.
To exit Emergency Heat, press the EMERGCY HEAT button.
4 Advanced Features & Operation
Backlight (Setup Steps 3-8): Press Setup and then Mode over and over to advance to step #3
Backlight (Setup Step 3)
Off - Backlight turns on only with a button press and turns off after 8 seconds.
On - Backlight is on continuously.
Backlight Intensity Level (Setup Step 4) - The backlight can be adjusted between Off and seven levels of brightness
Night Dimmer (setup step 5) - Selecting On allows for automatic dimming of the display at night.
Night Dimmer Brightness (setup step 6) - Off through seven levels of brightness
Night Dimmer Start Time (setup step 7)
Night Dimmer Stop Time (setup step 8)
EMERGCY
HEAT
PSP4271C User Manual.indd 20PSP4271C User Manual.indd 20 6/9/21 10:37 AM6/9/21 10:37 AM
Table of contents
Other Prostat Thermostat manuals

Prostat
Prostat PRS6110 User manual

Prostat
Prostat OEM Series User guide

Prostat
Prostat PRS6320 User guide

Prostat
Prostat OEM Series User manual

Prostat
Prostat OEM Series Instruction Manual

Prostat
Prostat PRS6390 User manual

Prostat
Prostat PRS4110 User manual

Prostat
Prostat PRS3110 User manual

Prostat
Prostat OEM PSP1100 User manual

Prostat
Prostat PRS6420 User guide