manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. SyxthSense
  6. •
  7. Thermostat
  8. •
  9. SyxthSense TAE-DI4 User manual

SyxthSense TAE-DI4 User manual

Online store: www.syxthsense.com
Enquiries: T: 0870 20 80 100 F: 0870 20 80 200 PS TH6.12 - 1/4
TAE-DI4 Electronic Room
Thermostats with Display
The TAE DI4 -C (Fig. 1) is a room electronic thermostat suitable
for a reliable and accurate temperature regulation in commercial
and industrial premises as well as for home installation. The digital
display gives the readout of the room temperature, thus allowing
an accurate regulation of the temperature in the environment to be
controlled. The manual selector (a) selects the heating or cooling
mode, according to the type of the plant wired to the thermostat.
Features
•230V~ (TAE-DI4-MC) or 24V~/= (TAE-DI4-2C) power supply
•Knob limitation feature through mechanical pins
•Room temperature display
•Heating / Cooling switch
•Fixing with distance between holes 60mm
•Compliant with directives EEC 89/336, 73/23 and 93/68 CE
Product sheet TH6.12
Thermostat type TAE-DI4
Model Types Model Description
TAE-DI4-MC
TAE-DI4-2C Electronic Room Thermostat with Display
Electronic Room Thermostat with Display (24Vac)
Technical Data Power supply TAE-DI4-MC 230V~ -15% +10% 50Hz
TAE-DI4-2C 24V~/= -15% +10% 50Hz
Power absorption 7VA
Regulation range 6°C...30°C
Sensor type PTC 2k ohm @ 25°C internal
Remote sensor
(optional) Cod. STL PTS A150
Accuracy Thermostat ±1°C
Display ±1°C (0°C...30°C range)
Resolution Knob 1°C
Display 0.1°C
Hysteresis 0,5°C
Contact rating 5 (1) A @ 250V~ SPDT
Protection class IP30
Operating
temperature 0°C...40°C
Storage temperature -10°C...+50°C
Humidity limits 20%...80% rH (non condensing)
Enclosure Material: ABS V0 self-extinguishing
Colour: Signal white (RAL 9003)
Size 85W x 85H x 31D mm
Weight ~150 gr.
SyxthSense Ltd
PS TH6.12 - 2/4
OPERATION If the device is in ‘Heating’ mode and the measured room temperature is below the value set with the
knob the thermostat turns the relay on and, at the same time, turns the flame symbol on the display.
If instead the device is in ‘Cooling’ mode and the measured room temperature is upper the value set
with the knob the thermostat turns the relay on and, at the same time, turns the fan symbol on the
display.
SET-POINT KNOB Through the set-point knob (b) the user can set the desired temperature.
INSTALLATION For installation of TAE DI4 -C follow these steps:
1. Remove the knob by tilting it, eventually with the help of a screwdriver placed in the slot.
2. Remove plastic cover by moving to the inner side, through the use of a tool (Fig. 4), the two plastic
teeth (f) located on the left side (Fig. 3) of the thermostat.
3. Fix the thermostat base plate to the wall through the two screw holes with distance between axes
of 60mm.
4. Make electrical wirings according to the diagram of Fig. 5, 7 or 8. 5. Close the thermostat by
carefully positioning the cover so that the slide switch matches the relevant hole and then by
slightly pressing the cover in order to make the four plastic teeth snapping.
KNOB ROTATION
LIMITATION It is possible to limit the rotation range for the set-point knob by following these steps:
1. Remove the knob by tilting it, eventually with the help of a screwdriver placed in the slot.
2. Pick up the plastic pins (c) parked at one side of the knob area and set them (d) as in the example
of Fig. 2. In this example the rotation range (e) is reduced as in the shown angle.
SELECTION REMOTE
SENSOR In order to connect to TAE DI4 -C a remote sensor (g) alternative to the internal one, follow diagram in
Fig. 8 and remove the jumper on the thermostat board, which is located in the bottom right side of the
thermostat, underneath the set-point knob (Fig. 6).
Fig. 4: Cover opening through screwdriver
F
ig
.
3
:
Plastic teeth position
f
f
Fig. 7: TAE DI4-C electrical wiring example for cooling
function with a heater
HEATER
PUMP
Fig. 7: TAE DI4-C electrical wiring example for cooling
function with a chiller device.
CHILLER
FAN
Fig. 8: TAE DI14-C Wiring Diagram
g
Fig. 2:
Mechanical pins positioning.
Fig. 1:
TAE DI4-C External aspect
d
c
e
a
b
d
Fig. 6: Jumper position for internal/remote sensor.
SyxthSense Ltd
PS TH6.12 - 3/4
WARNING:
To adjust properly room temperature, install the thermostat far from heat sources, draughts or
particularly cold walls (thermal bridges). When the remote sensor is used in conjunction with
the thermostat, then this note is to be applied to the remote sensor itself.
For remote version all wirings must be made using wires with 1.5mm2minimum section and
no longer than 25m. Do not use same duct for signal wires and mains.
The appliance must be wired to the electric mains through a switch capable of disconnecting
all poles compliant to the current safety standards and with a contact separation of at least
3mm in all poles.
Installation and electrical wirings of this appliance must be made by qualified technicians and
in compliance with the current standards.
Before wiring the appliance be sure to turn the mains power off.
Notes: In the view of a constant development of their
products, the manufacturer reserves the right for changing
technical data and features without prior notice. The
consumer is guaranteed against any lack of conformity for
24 months from the time of delivery, according to the
European Directive 1999/44/EC. The full text of guarantee
is available on request from the seller.
SyxthSense Ltd
© 2003 SyxthSense Ltd. All rights reserved - 07/2004
PS TH6.12 - 4/4
Online store: www.syxthsense.com
Enquiries: T: 0870 20 80 100 F: 0870 20 80 200

Other SyxthSense Thermostat manuals

SyxthSense DTP-A80-BC Dimensions

SyxthSense

SyxthSense DTP-A80-BC Dimensions

SyxthSense NEW WAVE DTP Series User manual

SyxthSense

SyxthSense NEW WAVE DTP Series User manual

SyxthSense Tempora TCP-GIO-BI03 User manual

SyxthSense

SyxthSense Tempora TCP-GIO-BI03 User manual

SyxthSense SST-A24-302 User manual

SyxthSense

SyxthSense SST-A24-302 User manual

SyxthSense DCPA80BC User manual

SyxthSense

SyxthSense DCPA80BC User manual

SyxthSense DAEA80 User manual

SyxthSense

SyxthSense DAEA80 User manual

Popular Thermostat manuals by other brands

Lauda RE 212 J operating instructions

Lauda

Lauda RE 212 J operating instructions

hager kallysto WUC70 User instructions

hager

hager kallysto WUC70 User instructions

Danfoss 060L2150 installation guide

Danfoss

Danfoss 060L2150 installation guide

Watts Vision BT-D03 RF quick start guide

Watts

Watts Vision BT-D03 RF quick start guide

ENGO CONTROLS E901WIFI Full manual

ENGO CONTROLS

ENGO CONTROLS E901WIFI Full manual

Aube Technologies TH134/U Installation and user guide

Aube Technologies

Aube Technologies TH134/U Installation and user guide

LVI MILO ROCK manual

LVI

LVI MILO ROCK manual

Gira 0394 Series installation instructions

Gira

Gira 0394 Series installation instructions

OJ Electronics MICROLINE OTN2 user manual

OJ Electronics

OJ Electronics MICROLINE OTN2 user manual

Honeywell CM61RF Specification sheet

Honeywell

Honeywell CM61RF Specification sheet

Honeywell PROGRAMMABLE THERMOSTAT RTH6350 Quick installation guide

Honeywell

Honeywell PROGRAMMABLE THERMOSTAT RTH6350 Quick installation guide

Honeywell HEAT PUMP THERMOSTAT T8411R installation instructions

Honeywell

Honeywell HEAT PUMP THERMOSTAT T8411R installation instructions

Myson REMOTE ROOM THERMOSTAT CONTROL installation instructions

Myson

Myson REMOTE ROOM THERMOSTAT CONTROL installation instructions

Antares T.225.00 manual

Antares

Antares T.225.00 manual

White Rodgers 1E30(W) installation instructions

White Rodgers

White Rodgers 1E30(W) installation instructions

Honeywell DT92 manual

Honeywell

Honeywell DT92 manual

Honeywell RTH7600 Series Quick installation guide

Honeywell

Honeywell RTH7600 Series Quick installation guide

Vortice CB LCD W Ariasalus Instruction booklet

Vortice

Vortice CB LCD W Ariasalus Instruction booklet

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.