Protege PRT-RDM2 User manual

DOOR CONTACT CONNECTION
The Protégé Reader Expander allows the connection of
up to 4 contacts for monitoring and controlling access
control doors. Each zone on the reader expander can be
used for the door function that is automatically assigned
and as a normal zone input on the system. The following
example shows the connection of a normally closed door
position monitoring contact to monitor the open, closed,
forced and alarm conditions of the door.
DOOR LOCK CONNECTION
The Protégé Reader expander provides a connection for 2
electric strike locks with full monitoring of the lock circuit
for tamper and over current/fuse blown conditions. The
door lock monitoring can be disabled if it is not required.
ZONE INPUT
The Protégé Mini Reader Expander can monitor the state of
up to 6 zone inputs such as magnetic contacts, motion
detectors and temperature sensors. The Controller
supports normally opened and normally closed
configurations with or without EOL resistors on a per zone
configuration setting, the diagram below shows how to wire
a zone with EOL resistors enabled.
SPECIFICATION
Power Supply
DC Input Voltage 12VDC
(10.5VDC Min, 14.0VDC Max)
Operating Current 80mA (Typical)
Communication
RS-485 Module Network
Outputs
Lock Outputs 2 FORM C Relay Outputs
PGM Outputs 6 (50mA Max) Open Collector
Inputs
Zone 8 (500ms to 40sec Input Speed)
Tamper 1 (Normally Closed)
Trouble Zone 16
Dimensions
PCB Dimensions 92mm X 210mm
3.6" X 8.3"
*Specifications are subject to change without notice, please
visit www.integratedcontroltechnology.com for the updated
information.
Unit C, 6 Ascension Place, Mairangi Bay, P.O. Box 302-340
North Harbour, Auckland, New Zealand.
Phone: +64 (9) 476 7124 yFax: +64 (9) 476 7128
www.integratedcontroltechnology.com
Mini 2 Reader Expander
Quick Start Guide
PRT-RDM2
INTRODUCTION
The Protégé Reader Expander extends the number of card
reader inputs on the system by 2, number of zone inputs
by 8 (4 zones used for door monitoring and control and
up to eight can be used for extended functionality) and
the number of PGM outputs by 8 (includes 2 monitored
lock control outputs).
•4 Wiegand Reader Mode for 2 Entry/Exit Doors Per
Reader Expander
•Secure Encrypted RS-485 Module Communications
•8 Zone Inputs
•2 Lock FORM C Relay PGM Outputs
•6 Open Collector PGM Outputs (Reader Control
Outputs)
•Smart Reader Missing/Tamper Monitoring
•Online and Remote upgradeable firmware
For a full installation manual or more information on the
Protégé Reader Expander and other Integrated Control
Technology products please login to our website
www.integratedcontroltechnology.com

ENCRYPTED MODULE NETWORK
The Protégé Mini Reader Expander incorporates
encrypted RS-485 communications technology.
Connection of the communications should be performed
according to the diagram shown below. It is important
that the N+ Network Communications Power be supplied
from an independent battery backed power supply unit
or a networked module capable of supplying the required
power to all of the network powered devices on the
RS485 network.
Always connect the Reader Expanders NA and NB
terminals to the NA and NB terminals of the
communication network. The N+ and N- must go to a
12V power supply source as shown above and connected
at ONLY one +12V power source.
The EOL (End Of Line) jumper setting MUST
be set in the ON position for the FIRST and
LAST module on the RS485 network. EOL is
ON when the jumper is closest to the EOL
text.
CONFIGURATION SWITCH
The addressing of the Protégé Reader Expander allows up
to 128 devices to be connected to the Protégé System
Controller. The 'CONFIG' configuration DIP switch allows
each reader expander to have a unique address.
The switch positions 1 to 7 select the device address from 1
to 128. When setting an address the reader expander must
be powered down and restarted for the new address to
take affect. When changing the address the reader
expander will automatically default the internal
configuration and require a network update. See the
Protégé System reference manual for information on
performing a module update.
The device address is determined by adding the value of
each switch that is selected in the ON position and then
adding 1 to this value. In the example below the address
079 results in (64+8+4+2) + 1 = 079. Setting all address
switches to OFF results in the default address of 001.
CABINET TAMPER SWITCH
The tamper input switch should be mounted into the steel
bracket provided and connected to the tamper connection
terminals as shown in the diagram below. The tamper input
opens and closes trouble zone RDxxx:01 on the reader
expander.
READER CONNECTION
The Protégé Reader Expander allows the connection of 4
Wiegand reading devices and the ability to control 2 doors
(Entry or Exit Only) or 1 door (Entry and Exit). The
following diagrams show the connection of standard
Wiegand Reader (Entry Unit) and a Multiplexed reader
(Exit Reader).
When operating the reader expander in multiple reader
mode the Protégé Reader Expander allows the connection
of 4 Wiegand reading devices controlling two doors each
with Entry/Exit readers.