DOOR CONTACT CONNECTION
The Protégé Reader Expander allows the connection of
up to 4 contacts for monitoring and controlling access
control doors. Each zone on the reader expander can be
used for the door function that is automatically assigned
and as a normal zone input on the system. The following
example shows the connection of a normally closed door
position monitoring contact to monitor the open, closed,
forced and alarm conditions of the door.
DOOR LOCK CONNECTION
The Protégé Reader expander provides a connection for 2
electric strike locks with full monitoring of the lock circuit
for tamper and over current/fuse blown conditions. The
door lock monitoring can be disabled if it is not required.
ZONE INPUT
The Protégé Mini Reader Expander can monitor the state of
up to 6 zone inputs such as magnetic contacts, motion
detectors and temperature sensors. The Controller
supports normally opened and normally closed
configurations with or without EOL resistors on a per zone
configuration setting, the diagram below shows how to wire
a zone with EOL resistors enabled.
SPECIFICATION
Power Supply
DC Input Voltage 12VDC
(10.5VDC Min, 14.0VDC Max)
Operating Current 80mA (Typical)
Communication
RS-485 Module Network
Outputs
Lock Outputs 2 FORM C Relay Outputs
PGM Outputs 6 (50mA Max) Open Collector
Inputs
Zone 8 (500ms to 40sec Input Speed)
Tamper 1 (Normally Closed)
Trouble Zone 16
Dimensions
PCB Dimensions 92mm X 210mm
3.6" X 8.3"
*Specifications are subject to change without notice, please
visit www.integratedcontroltechnology.com for the updated
information.
Unit C, 6 Ascension Place, Mairangi Bay, P.O. Box 302-340
North Harbour, Auckland, New Zealand.
Phone: +64 (9) 476 7124 yFax: +64 (9) 476 7128
www.integratedcontroltechnology.com
Mini 2 Reader Expander
Quick Start Guide
PRT-RDM2
INTRODUCTION
The Protégé Reader Expander extends the number of card
reader inputs on the system by 2, number of zone inputs
by 8 (4 zones used for door monitoring and control and
up to eight can be used for extended functionality) and
the number of PGM outputs by 8 (includes 2 monitored
lock control outputs).
•4 Wiegand Reader Mode for 2 Entry/Exit Doors Per
Reader Expander
•Secure Encrypted RS-485 Module Communications
•8 Zone Inputs
•2 Lock FORM C Relay PGM Outputs
•6 Open Collector PGM Outputs (Reader Control
Outputs)
•Smart Reader Missing/Tamper Monitoring
•Online and Remote upgradeable firmware
For a full installation manual or more information on the
Protégé Reader Expander and other Integrated Control
Technology products please login to our website
www.integratedcontroltechnology.com
ENCRYPTED MODULE NETWORK
The Protégé Mini Reader Expander incorporates
encrypted RS-485 communications technology.
Connection of the communications should be performed
according to the diagram shown below. It is important
that the N+ Network Communications Power be supplied
from an independent battery backed power supply unit
or a networked module capable of supplying the required
power to all of the network powered devices on the
RS485 network.
Always connect the Reader Expanders NA and NB
terminals to the NA and NB terminals of the
communication network. The N+ and N- must go to a
12V power supply source as shown above and connected
at ONLY one +12V power source.
The EOL (End Of Line) jumper setting MUST
be set in the ON position for the FIRST and
LAST module on the RS485 network. EOL is
ON when the jumper is closest to the EOL
text.
CONFIGURATION SWITCH
The addressing of the Protégé Reader Expander allows up
to 128 devices to be connected to the Protégé System
Controller. The 'CONFIG' configuration DIP switch allows
each reader expander to have a unique address.
The switch positions 1 to 7 select the device address from 1
to 128. When setting an address the reader expander must
be powered down and restarted for the new address to
take affect. When changing the address the reader
expander will automatically default the internal
configuration and require a network update. See the
Protégé System reference manual for information on
performing a module update.
The device address is determined by adding the value of
each switch that is selected in the ON position and then
adding 1 to this value. In the example below the address
079 results in (64+8+4+2) + 1 = 079. Setting all address
switches to OFF results in the default address of 001.
CABINET TAMPER SWITCH
The tamper input switch should be mounted into the steel
bracket provided and connected to the tamper connection
terminals as shown in the diagram below. The tamper input
opens and closes trouble zone RDxxx:01 on the reader
expander.
READER CONNECTION
The Protégé Reader Expander allows the connection of 4
Wiegand reading devices and the ability to control 2 doors
(Entry or Exit Only) or 1 door (Entry and Exit). The
following diagrams show the connection of standard
Wiegand Reader (Entry Unit) and a Multiplexed reader
(Exit Reader).
When operating the reader expander in multiple reader
mode the Protégé Reader Expander allows the connection
of 4 Wiegand reading devices controlling two doors each
with Entry/Exit readers.

Popular Card Reader manuals by other brands

Matrics RDR-RUG-100 user manual

Matrics

Matrics RDR-RUG-100 user manual

Tyco KT-MUL-MT-KP manual

Tyco

Tyco KT-MUL-MT-KP manual

Diehl Metering IZAR OH BT 2 user guide

Diehl Metering

Diehl Metering IZAR OH BT 2 user guide

StarTech.com 35FCREAD20 Spec sheet

StarTech.com

StarTech.com 35FCREAD20 Spec sheet

Viking PRX-2 product manual

Viking

Viking PRX-2 product manual

Panasonic AJ-PG50 operating instructions

Panasonic

Panasonic AJ-PG50 operating instructions

Hama 00124144 operating instructions

Hama

Hama 00124144 operating instructions

Omron V680-CA1D user manual

Omron

Omron V680-CA1D user manual

Aluratek AUHR200 product reference card

Aluratek

Aluratek AUHR200 product reference card

CDVI KRYPTO K1BT Quick start installation guide

CDVI

CDVI KRYPTO K1BT Quick start installation guide

HID multiCLASS RMK40 installation guide

HID

HID multiCLASS RMK40 installation guide

HID iCLASS R10 installation guide

HID

HID iCLASS R10 installation guide

SPLITTY SPLITTY user manual

SPLITTY

SPLITTY SPLITTY user manual

Abocom UR2060 Specifications

Abocom

Abocom UR2060 Specifications

Honeywell IF2B user guide

Honeywell

Honeywell IF2B user guide

HID iCLASS RK40 Installation

HID

HID iCLASS RK40 Installation

Farpointe Data MCR-30 quick start guide

Farpointe Data

Farpointe Data MCR-30 quick start guide

impinj SPEEDWAY IPJ-R1000 user guide

impinj

impinj SPEEDWAY IPJ-R1000 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.