Table 3.
Suppl voltage AC: 18 V÷ 22 V, 50Hz, 4.3A max.
DC: 20 V÷ 30 V,
Transformer 80VA (eg. AWT 250, AWT 868)
PSU module power P 49W
Output voltage 11,0 V÷13,8 V DC – buffer operation
10,0 V÷13,8 V DC – battery assisted operation
Output voltage setting, escalation and keeping
time
120ms/50ms/15ms @Inom., Uac=min.
Voltage setting range 11,0 V÷15,0 V
Voltage adjustment range ± 1%
Ripple voltage 60mV p-p max.
Output current 3,5 A max.
Current consumption b PSU module
s stems 17 mA max. – battery assisted operation
Batter charging current 250mA / 700mA (±5%) – configured with J1 jumper
SCP short-circuit protection
200% ÷ 250% of supply power – limitation of current and/or
fuse failure in the battery circuit (fuse-element replacement
required)
OLP overload protection
110% ÷ 150% (@25ºC÷65ºC) of power supply – current
limitation with the PTC automatic fuse, manual restart (the
fault requires the disconnection of the DC output circuit)
SCP short-circuit protection in the batter
circuit and reverse polarit protection
5A- current limitation, F fuse (failure requires replacement of
the fuse-element)
Excessive discharge protection UVP U<10,0 V (± 5%) – disconnection of (-BAT) battery
Technical outputs:
- BS output indicating failure of AC power
suppl
- AW technical output indicating operation
status of power suppl .
- OC type, 50mA max. normal status: level hi-Z, failure: level
L (0V), 20s time lag.
- OC type, 50mA max. normal status: level L (0V),
failure: level H (hiZ), (automatically recovered after returning
correct operation)
Optical indication:
- AC diode indicating the AC suppl status
- LB diode indicating the batter charging
process
- AUX diode indicating DC suppl status at the
power-suppl output
- red, normal status, permanently illuminated,
- red, illuminated with light with intensity depending on battery
charging current
- green, normal status, permanently illuminated,
Fuse F1 F 5A
Operation conditions
II environmental class, -10°C ÷40°C, convectional air flow
around the power supply for the convectional cooling shall be
provided
Table 4.
Casing dimensions 87 x 55 x 93 (WxHxD)
Fixation Fixing dowels x 4 (PCB fi=4,2 mm)
Connectors Ф0,41÷1,63 (AWG 26-14)
BAT batter outputs Connectors 6,3F-2,5
Net/gross weight 0,16kg/0,21kg
2. Installation.
2.1 Requirements.
The buffer PSU module is dedicated for installation by the qualified electrician, holding relevant permits
and licenses (applicable and required for the specific country) for connecting (interference with) the 230V/AC and
low-voltage systems. The unit should be mounted in the non-open premises, in accordance with the II-nd
environmental class, with the normal relative humidity (RH=90% maximum, without condensing) and temperature
within the range -10°C to +40°C. The should be operated in the position ensuring that the air may freely flow
through ventilation openings in a convectional way.