Pulsar PS-1HCE Specification sheet

Rev. 2.0
04/2022
Operaon and Installaon Manual
Pulsar® Precision System
Model PS-1HCE

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022
2
Table of Contents
1 SafetyPrecauons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.1 SafetyConvenons ......................................................4
1.2 Safety Statements for the Pulsar® PS .......................................4
2 Introducon .........................................................6
2.1 OverviewofOperaon ...................................................6
2.2 Process Flow Diagram ...................................................6
3 Pulsar®PrecisionFeederOverview ......................................8
3.1 Components List ........................................................8
4 Pre-installaonInstrucons ............................................9
4.1 Prepare the Site ........................................................9
4.1.1 Site Requirements ................................................9
4.2 GatherEquipmentforFeederInstallaon ...................................9
4.2.1 Pulsar® Precision Components ......................................9
4.2.2 EssenalEquipmentSuppliedbyOthers .............................10
4.2.3 COTS Tools .....................................................10
4.2.4 PPE ...........................................................10
4.3 Pre-InstallaonChecklist ................................................10
5 InstallaonInstrucons...............................................11
5.1 Install the Booster Pump- Venturi Loop ....................................11
5.2 Install the Flow Switch ..................................................12
5.3 Feeder Setup- Connect the Discharge Tubing Line ...........................12
5.4 Feeder Setup- Connect the Inlet Tubing Line................................12
5.5 Mount the Control Box..................................................12
5.6 Wire the Booster Pump to the Control Box .................................13
5.7 Connect the Flow Switch Cable ...........................................13
5.8 Prime the System ......................................................13
5.9 Connect the Control Box to the Feeder ....................................13
6 Post-InstallaonInstrucons...........................................14
6.1 System Startup ........................................................14
6.1.1 FeederPreparaon ..............................................14
6.1.2 ControlBoxPreparaon ..........................................15
6.1.3 System Power Up ................................................16
7 OperaonInstrucons................................................17
7.1 Fill the Hopper ........................................................18
7.2 Fill the Hopper (Dustless Procedure) ......................................18
8 PreventaveMaintenance ............................................19
8.1 PreventaveMaintenanceSchedule.......................................19
8.2 Cleaning Procedures....................................................20
8.2.1 Equipment Needed ..............................................20
8.2.2 CleantheGridBasket(OnlineCleaningInstrucons) ...................21
8.2.3 Comprehensive(Oine)CleaningInstrucons........................22

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022 3
9 TroubleshoongGuide ...............................................23
10 Appendix...........................................................24
10.1 RequirementsandSpecicaons .........................................24
10.1.1 RequirementsforProductInstallaonandOperaon ..................24
10.1.2 ProductSpecicaons ............................................24
10.1.3 OponalFeedRateCapability......................................25
10.2 ElectricalSchemacs ...................................................26
10.3 Replacement Parts List and Views.........................................29
10.4 Pulsar® Precision Duo...................................................33
11 LimitedWarranty ....................................................34
List of Figures
Figure1. Pulsar®PrecisionwithAcidPlusFeederInstallaon ....................6
Figure2. Pulsar®PrecisionDUOInstallaon ..................................7
Figure3. FrontViewofPulsar®PrecisionFeeder ..............................8
Figure4. Completethe1½"pipingrun .....................................11
Figure5. Flowswitchinstallinhorizontalpipe ...............................12
Figure6. Flowswitchinstallinvercalpipe..................................12
Figure7. DischargeTubingConnecon......................................12
Figure8. Dual-VoltageSelector............................................13
Figure9. DIPSwitchLocaonandFeedCycleSengs .........................15
Figure10. FeederControlBox .............................................16
Figure12. BucketFunnelRemoval .........................................18
Figure11. BucketFunnelInstallaon .......................................18
Figure13. 115VACControlBoxWiringSchemac.............................26
Figure14. 230VACControlBoxWiringSchemac.............................27
Figure15. FeederJunconBoxWiringSchemac .............................28
Figure16. HopperandBaseExteriorComponentsView........................29
Figure17. HopperInteriorComponentsView ................................30
Figure18. BaseInteriorComponentsView ..................................31
Figure19. BoosterPumpandVenturiAssembly ..............................32
List of Tables
Table1. Pre-installaonChecklist ..........................................10
Table2. Post-InstallaonChecklist.........................................14
Table3. MonthlyMaintenance ............................................19
Table4. SemiannualMaintenance .........................................20
Table5. SiteRequirement ................................................24
Table6. AccessoryRequirements ..........................................24
Table7. OperaonalSpecicaons.........................................24
Table8. ChemicalFeedRateSpecicaons ..................................24
Tables9-10. FeedSolenoidOn/OTimevsAvailableChlorineDeliveryRate ......25

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022
4
1 SafetyPrecauons
Danger, Warning, Cauon, and Note statements are used throughout this manual to emphasize important safety informaon. The statements
are dened below.
1.1 SafetyConvenons
Danger: Indicates a hazardous situaon which, if not avoided, will result in death or severe
injury.
Warning:Indicates a potenally hazardous situaon which, if not avoided, can result in
personal injury.
Cauon: Indicates a potenally hazardous situaon which, if not avoided, can result in minor
personal injury or equipment damage.
Note: Informaon that may assist in compleng a task correctly or for maintaining the
machine in good operang condion.
1.2 Safety Statements for the Pulsar® PS
Warning:For your protecon, carefully and completely read the informaon provided in this
manual before aempng to assemble, install, operate, or maintain this product.
Retain these instrucons for future reference. Failure to follow the instrucons or
informaon in this manual may result in injury and damage to the product and may
aect warranty coverage.
Danger: Fireorexplosion could result from contaminaon, or use of any other chlorinang
compound!
Danger: Calcium hypochlorite is hazardous. Please refer to the Safety Data Sheet for
addional informaon and precauons regarding the proper handling of Pulsar® Plus
Briquees. If any part of this prole is unclear to you, please stop immediately and
contact Solenis at (800) 478-5727.
Danger: This system contains liquid under pressure and calcium hypochlorite soluon can
be discharged unexpectedly. Operate and service all components and aached
piping that contain liquid cauously unl you are certain that the system has been
depressurized and drained. Failure to do so may result in death or serious injury.
Danger: Use suitable personal protecve equipment (PPE) at all mes to avoid physical
contact with calcium hypochlorite soluon or vapor. Failure to do so may result
in death or serious injury. Please refer to the Safety Data Sheet for addional
informaon and precauons regarding the proper handling of calcium hypochlorite.

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022 5
Danger: Do not allow Pulsar® Plus Briquees to come into contact with any foreign maer
or chemicals. Calcium hypochlorite is chemically reacve with many substances
including, but not limited to water, water treatment products, pool treatment
products, acids, organics, nitrogen-containing compounds, dry powder re
exnguishers (containing mono-ammonium phosphate), oxidizers, and corrosive,
ammable, and combusble materials. Contaminaon or improper use of Pulsar®
Plus Briquees may cause a violent reacon that produces heat, an explosion, a
re, and the release of toxic gases, and result in death or serious injury. Please refer
to the Safety Data Sheet for addional informaon and precauons regarding the
proper handling of calcium hypochlorite.
Danger: All wiring connecons, fusing, grounding, inspecon, and maintenance of wiring
must be performed by a licensed electrician in accordance with the Naonal Electric
Code (NEC), Occupaonal Safety and Health Act (OSHA) in the United States, and all
local electrical codes. Failure to properly install and wire this product can result in
property damage, serious injury, or death, and may aect warranty coverage.
Warning:Clean up, without delay, any leakage or spillage of Pulsar® Plus Briquees or
calcium hypochlorite soluon. Please refer to the Safety Data Sheet for addional
informaon and precauons regarding the proper disposal of calcium hypochlorite.
Failure to do so may result in death or serious injury.
Warning:Always operate system with electrical component enclosures in place. Failure to do
so may result in injury.
Warning:Always operate system components with safety guards in place. Failure to do so may
result in injury.
Warning:Observe and follow all locaon-specic safety procedures. Failure to do so may result
in injury.
Warning:Alwaysbecarefulwhenaddingmuriacacidtowater; this combinaon creates an
exothermic reacon, which gives o heat. Failure to take care may result in serious
injury.
Cauon: Use only replacement parts idened in 10.3 Replacement Parts List and Views on
page 29. Do not paint over or remove unit nameplates, labels, or tags so that
proper replacement parts may be idened.
The system is designed with specic motor characteriscs. Changing motor types will
change the operang characteriscs of the system, which may cause injury and may
void the warranty of this chlorinator.
Cauon: Use of any briquees or other chemicals other than the Pulsar® Plus Briquees
designed for use with this chlorinator is hazardous, possibly causing re and/or
explosion and will void this warranty.

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022
6
2 Introducon
The patented Pulsar® Precision feeder creates a consistent soluon of calcium hypochlorite used for water disinfecon.
2.1 OverviewofOperaon
The Pulsar® Precision feeder operates as follows:
1. Pulsar® Plus Briquees are placed in a basket and suspended over the soluon reservoir.
2. The control box is plugged into a chemical controller output and powered on.
3. When the chemical controller requires chlorine, the feed solenoid valve opens allowing water from the pool return to enter the inlet water
manifold at the proper supply ow rate.
4. Low-velocity, high-volume water enters the reservoir and covers the boom of the basket.
5. Pulsar® Plus Briquees erode into the reservoir and create a consistent 0.7% available chlorine soluon with 84 °F [28.8 °C] inlet water
temperature.
6. The chlorinated soluon lls the reservoir, liing the oat switch connected to the discharge valve unl the valve opens.
7. The discharge valve and outlet tubing are connected to a venturi. The vacuum generated by the venturi sucon drains the reservoir tank
and sends the concentrated soluon into the pool return.
2.2 Process Flow Diagram
Figure1. Pulsar® Precision with Acid Plus Feeder Installaon

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022 7
Figure2. Pulsar® Precision DUO Installaon

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022
8
3 Pulsar® Precision Feeder Overview
Figure3. Front View of Pulsar® Precision Feeder
A4
B2
A5
A6
A1
B1
A2
A3
A
B
3.1 Components List
The Pulsar® Precision Feeder includes these components:
A Hopper, which includes:
A1 Hopper lid, hinge pin, and retainer
A2 HCE grid basket
A3 HCE bowl
A4 Juncon Box
A5 Front cover
A6 Feeder control box
A7 ESV (emergency shuto valve)(picture not shown)
A8 ESV nut wrench (picture not shown)
A9 Grid basket removal tool (picture not shown)
B Base, which includes:
B1 Le and right covers
B2 Discharge valve assembly
B3 Level switch (picture not shown)
B4 Bucket funnel (picture not shown)
C Booster pump and venturi installaon kit (picture not shown)

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022 9
4 Pre-installaonInstrucons
4.1 Prepare the Site
Before installing equipment, ensure that:
1. The site has all electrical connecons installed. All electrical lines should be secured to meet site safety procedures and to prevent tripping
over electrical lines.
Danger: All wiring connecons, fusing, grounding, inspecon, and maintenance of wiring
must be performed by a licensed electrician in accordance with the Naonal Electric
Code (NEC), Occupaonal Safety and Health Act (OSHA) in the United States, and all
local electrical codes. Failure to properly install and wire this product can result in
property damage, injury, or death, and may aect warranty coverage.
2. Site meets criteria noted in Site Requirements on page 9.
4.1.1 SiteRequirements
The feeder must t in the selected room with enough clearance for maneuvering and servicing the equipment.
– Recommended clearance for feeder installaon is 48" L x 48" W x 76" H [121.9 cm x 121.9 cm x 193.0 cm]
– Minimum clearance for feeder installaon is 36" L x 36" W x 64" H [91.4 cm x 91.4 cm x 162.6 cm].
The room must have proper venlaon.
The room must be climate-controlled between 40 °F – 90 °F [4 °C – 32 °C].
Required electrical service as follows:
– 100 - 240 V AC / 15 - 20 A dedicated outlet.
– 50 - 60 Hz single-phase only.
– 50 Hz systems require a locally-sourced booster pump (see booster pump secon, page 13, for more informaon.
Determine the inlet and outlet locaon of the booster pump and venturi loop.
– It is preferable to install this loop across the heater bypass valve to maximize the pressure dierenal of the system to enhance
performance.
– The booster pump sucon should always be downstream of the pool lter(s) to ensure the use of clean, ltered water to protect the
solenoid valves. Refer to Figure 1 on page 6 for proper locaon of piping connecons.
– The booster pump and venturi should be located to minimize the use of 90° elbows on the venturi outlet.
The following cable lengths need to be considered for placement of the control box and feeder:
– The combined control box and feeder cable is 20 [6 m] when connected; the feeder will need to be within 20 [6 m] of the control
box.
– The ORP control cable is 20 [6 m]; the control box will need to be within 20 [6 m] of the ORP controller.
– The ow switch cable is 33 [10 m]; the distance between the control box and ow switch should be considered.
4.2 GatherEquipmentforFeederInstallaon
Assemble these products in preparaon for installaon:
Pulsar® Precision components
Essenal equipment supplied by others
Commercial o-the-shelf (COTS) tools
Personal Protecve Equipment (PPE)
4.2.1 Pulsar®PrecisionComponents
See the Components List on page 8.

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022
10
4.2.2 EssenalEquipmentSuppliedbyOthers
1 ½" Sch 40 pipe
Two (2) 1 ½" ball valves
1 ½" Sch 40 elbows, 45° and 90°
1/2" [1.27 cm] exible tubing
PVC primer and glue
Saddle clamps for connecon to 1 ½" PVC pipe from pool return (oponal)
Plumber's tape
4.2.3 COTSTools
Drill
1 ¾" hole saw and 1 ½" NPT tap (oponal)
11/16" drill bit and 1/2" NPT tap
Saddle clamps (oponal)
Pipe wrenches or gas pliers
Tubing cuers
Saw (to cut PVC pipe)
4.2.4 PPE
Safety glasses
Rubber gloves
Apron
4.3 Pre-InstallaonChecklist
Table1. Pre-installaonChecklist
ItemNo Check Completed?
1 Is a licensed electrician available to perform necessary electrical wiring of the booster pump?
2Does the site meet all criteria noted in Secon 4.1.1, Site Requirements on page 9?
3 Have inlet and outlet locaons on the pool return post lter been idened?
4Are all Pulsar® Precision components on hand?
5 Is all essenal equipment supplied by others on hand?
6Are all COTS tools and other equipment on hand?
7 Is all PPE on hand?

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022 11
5 InstallaonInstrucons
5.1 Install the Booster Pump- Venturi Loop
Downstream of your pool lter(s), connect the booster pump sucon and
venturi outlet 1 ½" piping: See Figure 4.
Cauon: Shut o the pool pump and isolate the pool return piping locaon
used for the installaon to prevent excessive water leakage.
Note: Refer to the Figure 1 on page 6 for proper locaon of system
piping connecons.
1. Drill and tap two 1 ½" NPT holes that will be used for the booster
pump inlet and venturi outlet, respecvely.
Note: Saddle clamps or tee’s can be used as an alternave for a cleaner
installaon.
2. Since not all pipes run full, for horizontal pipe, drill the holes on the
side or boom.
3. Cut the 12" x 1 ½" PVC threaded nipple provided in the installaon kit
in half.
4. Apply plumber's tape to the threads of the two nipples and thread the
nipples into the 1 ½" tapped holes.
5. Add silicon seal bead around the thread connecon to help make a
waterproof seal.
6. Take the 1 ½" ball valves and glue them onto the 1 ½" nipples. These
are the isolaon valves to the inlet and outlet of the booster pump
and venturi.
7. Glue the 2” x 1 ½" reducer bushings to the pump union tailpieces and
connect to the booster pump sucon and discharge.
8. Apply plumber's tape to the venturi threads and thread the 1 ½" unions to both ends of the venturi.
9. Thread the 3/4" x 1/2" reducer coupling onto the venturi sucon.
10. Complete the 1 ½" piping run from the inlet nipple to the booster pump sucon.
11. Connect the discharge of the booster pump with the 1 ½" to 1/2" reducer bushing and the 1 ½" venturi ensuring the venturi is oriented in
the direcon of ow.
12. Complete the 1 ½" piping run from the outlet of the venturi to the outlet nipple on the pool return using as few 90° elbows as praccable.
The use of 45° elbows in place of 90° elbows are preferred to minimize backpressure on the venturi outlet.
Figure4. Complete the 1 ½" piping run
cut 1-1/2" PVC pipe
(installer provides)
1-1/2" thread x slip
PVC union
cut 1-1/2" PVC pipe
(installer provides)
1-1/2" Slip
PVC Ball Valve
(installer provides)
flow to
feeder
flow from
feeder
flow to
pool
1-1/2" slip x 1/2" FNPT TEE
(installer provides)
1-1/2" Slip PVC Ball Valve
(installer provides)
flow
from
pool

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022
12
5.2 Install the Flow Switch
Install the ow switch upstream of the booster pump sucon in horizontal or vercal pipe
with upward ow direcon:
1. Drill and tap a 1/2" NPT hole just upstream of the booster pump sucon.
2. In horizontal pipe, the tapped hole should be on the side parallel to the ground or a
lile lower to ensure the posive presence of ow. See Figure 5.
3. In the vercal pipe, the tapped hole should be in the upward direcon of the ow.
See Figure 6.
Cauon: Do not install the ow switch on top of the pipe or in vercal piping with ow
going down. This may cause false “no ow” readings in pipes that don’t always
run full.
4. Use sucient plumber's tape on the ow switch threads to ensure a good seal.
5.3 Feeder Setup- Connect the Discharge Tubing Line
To connect the discharge tubing line of the feeder to the venturi sucon:
1. Remove the hopper (top half) of the feeder and place it on the oor.
2. Remove the le and right base covers to expose the discharge piping check valve
and tubing connector.
3. Esmate how much tubing needed to make the connecon between the feeder and
venturi and cut the appropriate tubing length using tubing cuers.
4. Manipulang the feeder base for easier access, connect the ½" OD polyethylene
tubing to the tubing connector.
5. Wind the other end of the tubing through the hole in the base so that it comes out of
the back of the base. See Figure 7.
6. Connect the tubing to the tubing connector on the venturi sucon.
7. Use a wrench, if necessary, to secure the tubing onto the tubing connectors.
5.4 Feeder Setup- Connect the Inlet Tubing Line
To connect the inlet tubing line of the feeder to the inlet manifold:
1. Replace the hopper back onto the feeder base.
2. Install the 1/2" ball valve, strainer, ow meter and male threaded tubing connector
at the booster pump discharge prior to the venturi. (Install ball valve prior to strainer
and ow meter).
3. Install the ½” female threaded tubing connector on the ½” male threads at the back of the feeder hopper
4. Esmate how much tubing is needed to make the connecon between the feeder and venturi and cut the appropriate tubing length using
tubing cuers.
5. Using the appropriate tubing connectors, connect the feeder inlet to the booster pump discharge.
5.5 Mount the Control Box
Open the control box cover to access the mounng holes of the control box.
1. The control box mounng holes are located on the outside of the waterght gasket.
2. Select the proper bolt size and material for compability to box and wall construcon.
Figure5. Flow switch install in horizontal pipe
Figure6. Flow switch install in vercal pipe
Figure7. Discharge Tubing Connecon

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022 13
5.6 Wire the Booster Pump to the Control Box
Using a cered electrician, connect the booster pump to the control box using 12 AWG
or bigger wire.
Warning:Risk of dangerous or fatal electrical shock. Be sure that power to the motor
circuit is o before working on wiring, wiring connecons, or the motor. Re-
install the motor end cover and all other wiring covers before turning on the
power.
Note: The pump must be permanently connected to the control box. Be sure no other
lights or equipment are on the same circuit.
Note: Be sure no other lights or equipment are on the same circuit as the control box.
Note: Use Ground Fault Circuit Interrupter (GFCI) as a master on-o switch.
1. Refer to Appendix secon 10.2.1 and 10.2.2 for control box wiring help.
2. Remove the booster pump motor end cover to expose the pumps dual-voltage
selector, Figure 8.
3. If you have 230 V motor supply voltage, conrm that the plug is set for 230 V. The
arrow on the plug will point to the 230 V posion, which is the default posion of the pump (the plug only connects with one prong in this
posion).
4. If you have 115 V supply, pull the plug straight up and place it on the two brass prongs so that the arrow points to the 115 V posion.
5. Open the control box cover and wire the booster pump to the control box using the wiring diagram, Figure 13.
6. Replace the booster pump motor end cover to complete the booster pump wiring.
5.7 Connect the Flow Switch Cable
Connect the orange ow switch cable to the ow switch:
1. Route the ow switch cable so that it is not a tripping hazard.
2. The M12 connector on the cable goes in one direcon. Screw in the connector so that it fully engages with the ow switch.
5.8 Prime the System
1. Allow pool water to enter the 1 ½" and 1/2" piping and tubing to conrm overall water ghtness.
2. Open the 1 ½" inlet ball valve and allow water to enter the booster pump checking for leaks.
3. Slowly crack open the booster pump discharge union, allowing water to ow out conrming that the booster pump is fully primed.
4. Reconnect and ghten the discharge union.
5. Open the 1 ½" outlet ball valve fully priming the enre booster pump / venturi loop.
6. Open the 1/2" gray inlet and outlet feeder ball valves, allowing water to reach the feeder.
7. Check for leaks at the booster pump and venturi loop and feeder and ow switch. Redo any leaking connecons.
5.9 Connect the Control Box to the Feeder
1. Connect the feeder control cable on the control box (second from the le) to the main cable coming out of the back of the feeder hopper.
2. Orient the notch of both connectors so they can be pushed in together. The 4 pin connectors from the control box and the feeder are keyed
so they t together in only one orientaon.
3. Once mated, turn the locking ring clockwise unl hand ght. (The connectors are sealed to IP68 when mated correctly.)
Figure8. Dual-Voltage Selector

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022
14
6 Post-InstallaonInstrucons
Before rst me startup of the feeder, check:
Table2. Post-InstallaonChecklist
Item
No
Check Completed?
1. Is there any residual debris (plasc shavings, screws, and so on) inside the soluon tank?
2. Has the booster pump been fully primed?
3. Are all electrical lines secure and not a tripping hazard?
4. Are all exposed electrical and instrument lines protected and do they meet eld condions?
5. Does the booster pump motor plug line up to the correct voltage supply?
6. Is the control box cover closed and screws securely ghtened?
7. Are all ngs and unions ghtened to prevent leaks?
8. Are ow direconal arrows pointed in the correct direcon of ow on the venturi, solenoid valves, and
check valves?
9. Is grid basket placed in HCE bowl correctly so that it cannot spin around?
10. Is the control box feeder cable connected to the feeder cable and is the locking ring turned clockwise to
seal the two connectors together?
6.1 System Startup
Note: Before starng up the equipment, ensure that the Post-Installaon checklist has been
completed.
6.1.1 FeederPreparaon
Aer compleng the post-installaon checklist:
1. Put on the appropriate PPE: long sleeved clothing, rubber gloves, apron, dust mask, and safety glasses.
Danger: Use suitable personal protecve equipment (PPE) at all mes to avoid physical
contact with calcium hypochlorite liquid or vapor. Failure to do so may result in death
or serious injury. Please refer to the Safety Data Sheet for addional informaon and
precauons regarding the proper handling of calcium hypochlorite.
2. Open the hopper lid.
3. If not already installed, place grid basket in to the hopper. Conrm that only one grid basket is installed in the hopper and placed in the
correct orientaon where the basket spout is on the bowl outlet. (Basket should not be able to rotate when placed correctly).
4. Use a scoop to add approximately 3 inches of Pulsar® Plus Briquees to the basket.
5. Close the hopper lid.

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022 15
6.1.2 ControlBoxPreparaon
Danger: Ensure the control box is not plugged into power prior to removing the top cover,
adjusng DIP switches, and wiring in the booster pump. Failure to do so may result in
death or serious injury from electrical shock.
1. Prior to powering up the control box, verify the output seng and economy mode by removing the top cover and idenfying the DIP
switch sengs in accordance with the Feed Cycle Sengs table in step 4, below.
2. The DIP switches are located near the top le of the controller and the feed cycle sengs are on the top right. See Figure 9, below.
3. There are 4 DIP switches. Switches 1, 2, 3 control the feed solenoid On/O me and switch 4 turns the economy mode On/O.
AC POWER CORD
14/3 10' SJTW EU COLOR CODE
PROVIDED BY MELLC
PROVIDED BY IWC
FLOW SWITCH JACK
PROVIDED BY MELLC
18/7 20' CABLE UL CSA CE SJTWO
LEVEL SWT
KEY
1
COM
12
HD1
TB8
HI LIMIT SWT
FLOW SWITCH
+24 VDC
3
COM
FEED SOL
1
-24 VDC
12
TB7 TB6
COM
COM
WASH SOL
TB4 TB3
SW1
ON
C4
104
PIC16F883
2003
OJE-124
U4
RY3
U1
107 104104
RY2
OJE-124 R10
470
TEST OFF
HD2
1
4
3
2
C1
CLP1
C2
U2
LM2950
1 AMP
FU1
C3
CLP2
120/240 VAC
ORP IN
COM
1
GND
HOT
23
TB2
LINE IN NEUTRAL
PUMP COM
1
TB1
2
LINE IN 120/240 VAC
LINE GND
PUMP GND
3 4
PUMP HOT
65
22/38
FEED CYCLES
ON
OFF
ON
+PS1
MPM-20-24
10K10K
R6 R5
FOD81 4
1
N
DIP S WITCH
ECONO MODE
ON
-
O F FS W 4
SW3
SW2
SW1
11/49 16/446/54
ON
OFF
OFF
OFF
OFF
OFF
L
OFF
OFF
ON
ON/OFF
RY1
G4A
32/28 38/22
27/33
ON
OFF
OFF
ON
ON
OFF ON
OFF
ON
44/16
ON
ON
ON
PUMP OUT
3 2 10
To 115-430-03 Feeder Terninal Block Wiring Asembly
INLINE CONNECTOR
BLA CK WIRE 0 COMMON
RED WIRE 2 FEED DIN +
ORANGE WIRE 3 WATER DIN +
BROWN WIRE 1 HI LIMT SW
WIRE LEGEND:
Figure9. DIP Switch Locaon and Feed Cycle Sengs
4. The below Feed Cycle Sengs table shows On/O feed mes in seconds based on the combinaon of DIP switch sengs. The higher on
mes yield higher chlorine output.
ON/OFF FEEDCYCLES
DIPSWITCH 6/54 11/49 16/44 22/38 27/33 32/28 38/22 44/16
SW1 OFF ON OFF ON OFF ON OFF ON
SW2 OFF OFF ON ON OFF OFF ON ON
SW3 OFF OFF OFF OFF ON ON ON ON
5. Set your desired output and economy mode seng in accordance with the above Feed Cycle Sengs table.
a. For example, SW1 on, SW2 o, SW3 on yields 32 sec On and 28 sec O for the feed solenoid – Approximately 75% chlorine output of
the feeder.
b. If SW4 is o, the booster pump will be always on. If SW4 is on, the booster pump will run in economy mode and stop 20 sec aer the
last feed or wash cycle (or 5 min if the pump just started up).
c. The DIP switches can be toggled at any me with the controller powered o.
Note: If using an ORP or chemical controller for dosing, start with the dip switches congured
to the highest output. This is SW1, SW2, and SW3 on.
6. Close the top cover of the controller to resume start up.
DIP Switch
Feed Cycle Sengs
AC POWER CORD
14/3 10' SJTW EU COLOR CODE
PROVIDED BY MELLC
PROVIDED BY IWC
FLOW SWITCH JACK
PROVIDED BY MELLC
18/7 20' CABLE UL CSA CE SJTWO
LEVEL SWT
KEY
1
COM
12
HD1
TB8
HI LIMIT SWT
FLOW SWITCH
+24 VDC
3
COM
FEED SOL
1
-24 VDC
12
TB7 TB6
COM
COM
WASH SOL
TB4 TB3
SW1
ON
C4
104
PIC16F883
2003
OJE-124
U4
RY3
U1
107 104104
RY2
OJE-124 R10
470
TEST OFF
HD2
1
4
3
2
C1
CLP1
C2
U2
LM2950
1 AMP
FU1
C3
CLP2
120/240 VAC
ORP IN
COM
1
GND
HOT
23
TB2
LINE IN NEUTRAL
PUMP COM
1
TB1
2
LINE IN 120/240 VAC
LINE GND
PUMP GND
3 4
PUMP HOT
65
22/38
FEED CYCLES
ON
OFF
ON
+PS1
MPM-20-24
10K10K
R6 R5
FOD 814
1
N
DIP SWITCH
ECONO MODE
ON
-
O F FS W 4
SW3
SW2
SW1
11/49 16/446/54
ON
OFF
OFF
OFF
OFF
OFF
L
OFF
OFF
ON
ON/OFF
RY1
G4A
32/28 38/22
27/33
ON
OFF
OFF
ON
ON
OFF ON
OFF
ON
44/16
ON
ON
ON
PUMP OUT
3 2 10
To 115-430-03 Feeder Terninal Block Wiring Asembly
INLINE CONNECTOR
BLACK WIRE 0 COMMON
RED WIRE 2 FEED DIN +
ORANGE WIRE 3 WATER DIN +
BROWN WIRE 1 HI LIMT SW
WIRE LEGEND:

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022
16
6.1.3 SystemPowerUp
Figure10. Feeder Control Box
INDICATORLIGHTS
Flow(SolidGreen) Feed(SolidGreen) Wash(SolidGreen) Alert(FlashingRed)
Flow switch senses ow in pool
recirculaon piping
Feed solenoid valve is acve Wash solenoid valve is acve High level switch is triggered
(Overow condion)
BUTTONS
Power Mode
Toggle feeder from standby (o) to ready to feed (On) Toggle from Manual (mer mode) to ORP (ORP mode)
Note: ORP light ashes green when chlorine signal is present
To power up the system:
1. Connect the control box to a dedicated AC power source in accordance with the site requirements secon 4.1.1.
2. Aer a 30 sec boot-up period, the box will power up with the indicator lights turning on. Conrm the following indicator lights are on:
Power : red/o.....A red OFF indicator light means the box is powered and on standby.
Mode : green/ORP or MANUAL.....Indicates the last operang mode the control box was in.
Flow : green…..Indicates there is ow in the pool recirculaon piping. If there is no light, there is either no ow in the piping, the
orange ow switch cable is not correctly connected to the ow switch, or the ow switch is bad.
FEED, WASH, ALERT…..O when the power is on O.
3. Slowly open the inlet ball valve to allow water to ow through the manifold.
4. Press the control box power buon to energize the system.
5. Put the control box on manual mode to energize the feed solenoid valve and send water into the hopper.
6. Check for leaks from lines, valves, and connecons. If necessary, ghten parts.
7. Put the control box back on ORP mode.
8. Connect the control box ORP plug to an ORP (chemical controller) chlorine demand output.
9. Use the ORP controller to send a chlorine feed signal to conrm operaon of the Pulsar® Precision control box.
10. When the chlorine signal is removed, verify that the controller goes into four wash cycles of 15 sec On and 15 sec O.
11. Once all operang condions are veried, press the power buon on the control box to put it back into standby.

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022 17
7 OperaonInstrucons
Note: Before starng up the equipment, ensure that the Post-Installaon checklist has been
completed.
To operate the Pulsar® Precision Feeder:
1. Put on the appropriate PPE: long sleeved clothing, rubber gloves, apron, dust mask, and safety glasses.
Danger: Use suitable personal protecve equipment (PPE) at all mes to avoid physical
contact with calcium hypochlorite liquid or vapor. Failure to do so may result in death
or serious injury. Please refer to the Safety Data Sheet for addional informaon and
precauons regarding the proper handling of calcium hypochlorite.
2. Ensure that the inlet and outlet ball valves on the booster pump discharge and venturi sucon lines are closed.
3. Open the hopper lid.
4. Ensure that the hopper is at least 50% full with Pulsar® Plus Briquees.
5. Close the hopper lid.
6. Fully open the feeder outlet 1/2" ball valve on the venturi sucon.
7. Slowly open the feeder inlet ½” ball valve unl the ow meter reads 3.0 gpm.
8. Power on the control box and select the appropriate feed mode.
9. If on ORP, once chlorine demand signal is received, the booster pump will turn on and the feeder will start its feed cycle based on the
dened DIP-switch seng.
10. Once chlorine demand signal terminates, the feeder will go into its wash 15 sec On/O cycle (4) mes for a full 2 minute cycle (indicator
light stays on for the enre wash cycle).
11. If more water goes into the feeder than is able to be removed by the venturi, the alert indicator light turns on indicang a high level
condion. This condion will shut both solenoid valves and allow the booster pump to connue to run to let the venturi remove the water
from the base.
If the pump was o due to economy mode, it will turn on in order to let the venturi remove water from the base.
The ESV (Emergency Shuto Valve) provides mechanical stop in case the electronic high level switch malfuncons.
12. If Economy mode is selected, the booster pump will shut o aer a period of me when no chlorine is demanded by the ORP and the wash
cycle has completed.

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022
18
7.1 Fill the Hopper
1. Put on the appropriate PPE: long sleeved clothing, rubber gloves, apron, dust mask, and safety glasses.
Danger: Use suitable personal protecve equipment (PPE) at all mes to avoid physical
contact with calcium hypochlorite liquid or vapor. Failure to do so may result in death
or serious injury. Please refer to the Safety Data Sheet for addional informaon and
precauons regarding the proper handling of calcium hypochlorite.
Danger: Fireorexplosion could result from contaminaon, or use of any other chlorinang
compound!
Cauon: Use of any briquees or other chemicals other than the Pulsar® Plus Briquees
designed for use with this chlorinator is hazardous, possibly causing re and/or
explosion and will void this warranty.
2. Open the hopper lid.
3. Use a scoop to ll the hopper with Pulsar® Plus Briquees.
Cauon: Do not dump Pulsar® Plus Briquees into the basket. Dumping will cause dust from
calcium hypochlorite and can damage basket from force of load.
Cauon: Use of any briquees or other chemicals other than the Pulsar® Plus Briquees
designed for use with this chlorinator shall void this warranty.
4. Close the hopper lid.
7.2 Fill the Hopper (Dustless Procedure)
Danger: Use suitable personal protecve equipment (PPE) at all mes to avoid physical
contact with calcium hypochlorite liquid or vapor. Failure to do so may result in death
or serious injury. Please refer to the Safety Data Sheet for addional informaon and
precauons regarding the proper handling of calcium hypochlorite.
1. Put on the appropriate PPE: long sleeved clothing, rubber gloves, apron, dust mask, and
safety glasses.
2. Remove the red tamper prevenon tab on the lid of the briquee bucket. The lock release buon is visible.
3. Firmly press the lock release up, then turn the lid counter-clockwise to remove the lid from the bucket.
4. Place the bucket funnel on the bucket opening and turn it clockwise unl the bucket funnel is rmly seated on the bucket. Listen for the
ratcheng sound of the locking mechanism to conrm that the funnel is properly installed.
5. In one smooth moon, invert the bucket into the hopper opening while aligning the tabs of the bucket funnel into the slots of the hopper
opening. See Figure 11.
6. Turn the bucket and funnel clockwise to secure the bucket onto the hopper. The Pulsar®
Plus Briquees will deposit into the hopper.
Note: Ensure that the bucket is empty before removing it from the hopper.
To remove the bucket from the hopper:
1. Turn the bucket counter-clockwise to disengage the tabs on the bucket funnel from the
hopper.
2. Li the bucket and funnel up to remove them from the hopper.
3. To remove the bucket funnel from the bucket, rmly press up on the two funnel locking
buons, then turn the bucket funnel counter-clockwise. See Figure 12.
Figure11. Bucket Funnel Installaon
Figure12. Bucket Funnel Removal

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022 19
8 PreventaveMaintenance
8.1 PreventaveMaintenanceSchedule
Roune maintenance of the Pulsar® Precision Feeder is minimized when proper pool water balance is maintained. Maintain pool water
chemistry as follows:
TotalAlkalinity 60 – 80 ppm
CalciumHardness 200 – 1800 ppm
PH 7.2 - 7.6
LSI –0.3 - +0.5
Note: Adherence to these recommendaons at all mes will ensure the most eecve and
economical performance of the feeder
Note: The use of Carbon Dioxide gas (CO2) to lower pH will raise the Total Alkalinity
signicantly. High total alkalinity (over 80 ppm) will increase scale and solids buildup in
feeder.
Complete each of the following tasks during the rst week of each month.
Table3. MonthlyMaintenance
AconNeeded MaintenanceProcess TimetoComplete
Change/clean basket See Clean the Grid Basket (Online Cleaning Instrucons) on page 21.
Inspect inlet and
outlet plumbing
ngs
Verify that there are no leaks at any of the inlet and outlet ½" feeder ngs and 1 ½" booster
pump and venturi piping and ngs, including the booster pump itself.
1. Close all isolaon ball valves and re-plumb / replace any leaking piping and ngs.
2. If leaking is observed at the pump motor, the pump sha seal and impeller will have to be
replaced. Refer to the booster pump manual troubleshoong guide and repair parts list for
addional informaon.
2 min
Inspect booster
pump
1. Visually check for leaks on and around the pump, including the sucon and discharge piping
and ngs.
2. Close inlet and outlet 1 ½" ball valves and ghten or replace any leaking ngs.
3. If leaking observed at the pump motor, the pump sha seal and impeller is likely burned.
4. Refer to pump manual in the Appendix, page 24, for replacement parts and instrucons.
5 min
Inspect inlet line
strainer assembly
1. With pressure in the line, visually inspect the strainer basket for leaks. Replace the enre
basket assembly if leaking.
2. Close inlet ball valve.
3. Remove strainer basket and visually inspect for cracks and debris.
4. Remove strainer screen and wash it out prior to replacing it back into the basket.
5. If screen appears damaged or has a hole in it, replace with a new screen.
6. Re-install the strainer basket back into the strainer body.
10 - 15 min

Pulsar® Precision Operaon and Installaon Manual (Model PS-1HCE) Rev 2.0 04/2022
20
Inspect discharge
check valve
1. Close the outlet ball valve.
2. Open the lower le and right base covers and unscrew the check valve unions to remove
the check valve body.
3. Disassemble the check valve and inspect for calcium build up and debris. Clean if necessary.
4. Visually check the seal for corrosion. If the seal is corroded, replace the check valve.
5. Re-assemble the check valve body ensuring to put the seal on the side of the ball.
6. Replace the check valve body back onto the unions, ensure arrow points away from feeder.
10 min
Inspect reservoir
tank
Visually inspect the soluon reservoir and ensure that there is no calcium buildup or debris on
the high level switch or the discharge valve (DV) assembly including the DV oat, and arm.
Buildup on the level switch will prevent posive nocaon of a high level event. Verify
switch operaon by liing up the switch and conrming the alert indicator light turns on.
Build up on the DV oat or arm can interfere with feeder discharge operaon. Refer to
cleaning instrucons on page 20 if needed.
5 min
Inspect 45° cut Bowl
drain pipe
Visually inspect the HCE bowl drain pipe and ensure that there is no calcium buildup or
debris on around the edges clogging the uid path. Break o scale if necessary.
Replace 45° cut drain
pipe
Remove the ¾”, 45° cut, schedule 40 pipe from the hopper bowl and replace it with a spare,
clean discharge pipe. Use cleaning steps from page 20 to prepare the pipe for the next
maintenance interval.
2 min
Complete the following tasks during the rst week of January and the rst week of July.
Note: Maintenance that prevents the discharge line from clogging is crical to feeder
operaon.
Table4. SemiannualMaintenance
AconNeeded MaintenanceProcess TimetoComplete
Inspect the Venturi 1. Close the inlet and outlet 1 ½" ball valves to the booster pump sucon and venturi outlet
2. Close the inlet and outlet 1/2" ball valves to the feeder.
3. Disconnect the feeder discharge tubing from the venturi.
4. Remove the venturi via the 1 ½" unions and visually inspect and verify it is not clogged
with scale build up.
5. If scale buildup is found, refer to cleaning instrucons on page 20.
2 - 5 min
Inspect the
solenoid valves
During feed or wash cycle, if the solenoid valves are hot to the touch, consider replacing the
valve. If the solenoid makes a raling noise when energized, consider replacing the valve.
2 min
8.2 Cleaning Procedures
8.2.1 EquipmentNeeded
PPE
– Rubber gloves
– Apron
– Safety glasses
– Long sleeved clothing
Two 5-gallon buckets for online cleaning
Three 5-gallon buckets for oine cleaning
Table of contents
Popular Swimming Pool Filter manuals by other brands

MURSATT
MURSATT CUBBY GEN-R-8 Installation & operation manual

Aqua PRO
Aqua PRO 59719-XXXX owner's manual

Clear Water
Clear Water MineralPURE RC-50 user manual

Oasis Aquatics
Oasis Aquatics Oasis SE Series Installation and operation manual

Hayward
Hayward Aqua Rite® Pro owner's manual

BIO-LAB CANADA
BIO-LAB CANADA Pool Pilot Digital 60 Installation and operation manual

Procopi
Procopi RTM Premium 610-A Installation and operating instructions

Bestway
Bestway Flowclear 58400 owner's manual

Jandy
Jandy CL Series Installation and operation manual

STA-RITE
STA-RITE PLM100 owner's manual

Davey
Davey CrystalClear DCC2540 Installation and operating instructions

Watermaid
Watermaid WM40 User handbook