FITTING THE DECORATIVE FRAME
Chloe, Annabelle, Zara, Carmen, Carmen HIW and Juliet models;
Remove the decorative frame from it’s protective packaging. Dependant on the partic-
ular design of frame supplied, the frame is attached to the firebox either using magnets
(supplied) or hung onto the front of the firebox via brackets. Attach the frame to the fire-
box as appropriate and slide the ashpan door into place.
Heat Wave and New wave models;
The side pieces of the clip on assembly should be pushed into position first, followed
by the top bar, which should overlap the sides.
IMPORTANT NOTE: Due to the possibility of sharp edges, care should be taken
when handling the three piece frame components. The use of protective gloves is recommended.
Place the decorative firefront in front of the fire and slide the ashpan door into place. The firefront shown in these instructions may be dif-
ferent to the one supplied with the appliance.
TESTING AND COMMISSIONING
Turn on and test the gas supply up to the fire for any leaks, in accordance with current edition of BS6891.
When the appliance is first used, protective oils coating the firebox may burn off. It is advisable to ventilate the room during this period for
at least one hour.
OPERATING THE APPLIANCE
The pilot is visible through the left hand side of the matrix. Rotate the coals or pebbles for good view-
ing. Push in and turn the control knob to the SPARK position, and hold there for a few seconds.
Continue turning anti-clockwise through the spark click to the PILOT light position, ensuring the pilot
has lit. If not, return the knob clockwise, and repeat.
When the pilot lights after the spark, keep the knob depressed for approximately ten seconds. Now
release the knob and the pilot should stay alight. If the pilot is extinguished during use, wait three min-
utes before repeating the ignition procedure. To achieve the HIGH setting, push the control knob in
slightly and continue turning anti-clockwise to the high position. The main burner should light after a
few seconds. To decrease the setting to LOW, turn the control knob clockwise to the low setting.
To turn to the PILOT position from the HIGH or LOW positions, press the control knob in, and return to the pilot position and release. To turn
the fire OFF, keep the knob pressed in, return to the off position and release.
SPARK FAILURE
The gap between the spark electrode and the pilot should be 3.5 - 4.5mm to produce a good spark. There should be no need to adjust this.
If under any circumstances the electric spark fails, the pilot may be lit manually by proceeding with the ignition sequence as previously
described, and after turning the control knob through the spark position, the knob should be held in and the pilot lit with a taper.
SETTING PRESSURE
Remove the screw from the pressure test point, which will be be situated on the
main injector pipe Attach a U gauge. Light the fire on the HIGH setting.
The setting pressure should be in accordance with the figures stated on page 2 of
these instructions. The fire is factory set to achieve these pressures, and any sig-
nificant variation could indicate a supply problem.
If the pressure is too high, the gas supply meter may be set incorrectly. This should
be checked with the fire running and if necessary reset by the gas supplier. If the
pressure is too low, then check the meter governor pressure with the appliance
running. If this is incorrect it will need to be reset by the gas supplier.
If the setting pressure is too low, but the meter pressure is acceptable, then a prob-
lem in the supply pipework is to be suspected. This will be dirt and debris, kinked
or inadequate size pipes, restriction in a fitting or solder flashing across a joint.
FLUE SPILLAGE MONITORING SYSTEM
This fire is fitted with a flue spillage safety device (ODS). If the fire shuts down during use for no apparent reason then several things may be
suspected. If a door or window has been opened creating a draught, then pilot disturbance is the problem, and removal of the draught should
resolve this. The gas pressure reaching the fire must also be checked (again, recall your installer to check and rectify any problem). The ther-
mocouple connection into the back of the gas control valve may also have worked loose during installation, simply get the installer to tight-
en. If pilot disturbance is not the cause, then the ODS safety system may be in operation. Switch the appliance OFF, check the flue and carry
out any remedial work required. Relight the fire and carry out a spillage test.
DO NOT allow the appliance to be used if it continues to fail a spillage test. The aeration hole of the pilot must be carefully cleaned out on
each annual service to ensure continued function of the ODS.
The spillage monitoring system shall not be adjusted, modified, or put out of operation by the installer. Any spare parts fitted MUST be of a
type supplied for the purpose by the appliance manufacturer. If the fire is not spilling, then further guidance should be sought, using the
Troubleshooting section as a guide.
9
10.0
11.0
11.1
11.2
12.0
12.1
© 2009 Pure Glow Limited