Radionics D7212 Specification sheet

D7212 Control/Communicator
Operation and Installation Manual
74-06913-000-B 2/96 © 1993-1996 Radionics

D7212 Operation & Installation Manual
Page 2
74-06913-000-B 2/96 © 1993-1996 Radionics
Notice
The material and instructions covered in this manual have been carefully checked for
accuracy and are presumed to be reliable. However, Radionics, Inc. assumes no
responsibility for inaccuracies and reserves the right to modify and revise this manual
withoutnotice.
It is our goal at Radionics to always supply accurate and reliable documentation. If a
discrepancy is found in this documentation, please mail a photocopy of the corrected
materialto:
Radionics, Inc.
c/o Technical Writing
1800AbbottStreet
P.O. Box 80012
Salinas,CA93912-0012
© 1993 Radionics, Inc., Salinas, CA, U.S.A. All rights reserved.
FCC Notices
Part 15
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC rules. These limits are designed to provide
reasonableprotectionagainstharmfulinterferencewhentheequipmentisoperatedina
commercialenvironment.
This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful
interferencetoradiocommunications.
Operation of this equipment in a residential area is likely to cause harmful interference in
which case the user will be required to correct the interference at his own expense.
Part 68
This equipment complies with Part 68 of FCC rules. A label contains, among other
information,theFCCregistrationnumberandringerequivalencenumber(REN).If
requested,this informationmust beprovided tothe telephonecompany.
TheRadionicsD7212Control/Communicatorisregisteredforconnectiontothepublic
telephone network using an RJ38X or RJ31X jack.
The ringer equivalence number (REN) is used to determine the number of devices that may
be connected to the telephone line. Excessive RENs on the telephone line may result in
the devices not ringing in response to an incoming call. In most, but not all areas, the sum
of the RENs should not exceed five (5). To be certain of the number of devices that may
be connected to the line, as determined by the RENs, contact the telephone company to
determine the maximum REN for the calling area.
IftheD7212Control/Communicatorcausesharmtothetelephonenetwork,thetelephone
company will notify you in advance. If advance notice isn’t practical, the telephone
company will notify the customer as soon as possible. Also, you will be advised of your
right to file a complaint with the FCC if you believe it is necessary.

D7212 Operation & Installation Manual
Page 3
© 1993-1996 Radionics74-06913-000-B 2/96
Part 68 (Continued)
The telephone company may make changes in its facilities, equipment, operations, or
procedures that could affect the operation of the equipment. If this happens, the telephone
company will provide advance notice in order for you to make the necessary modifications
inordertomaintainuninterruptedservice.
Iftroubleisexperiencedwith the D7212 Control/Communicator,pleasecontactRadionics
Customer Service for repair and/or warranty information. If the trouble is causing harm to
thetelephone network,the telephonecompany mayrequest thatyou removethe
equipment from the network until the problem is resolved. User repairs must not be made,
and doing so will void the user’s warranty.
This equipment cannot be used on public coin service provided by the telephone company.
Connection to Party Line service is subject to state tariffs. (Contact your state public
utilities commission for information.)
FCCRegistrationNumber: AJ9USA-18808-AL-E
RingerEquivalence: 0.1A 0.2B
Service Center in U.S.A.: Radionics, Inc.
1800AbbottStreet
P.O. Box 80012
Salinas,CA93912-0012
(800)538-5807

D7212 Operation & Installation Manual
Page 4
74-06913-000-B 2/96 © 1993-1996 Radionics
Table of Contents
Power Outputs .................................................... 22
Circuit Protection............................................ 22
Available Power ............................................. 22
Continuous Power Outputs ............................ 23
Continuous Current Draw .......................... 23
Programmable Power Outputs....................... 24
Programming ............................................. 24
Optional Relays Required.......................... 24
Terminals 6 and 7...................................... 25
Terminal 8.................................................. 25
Fire System Power Formula ...................... 25
Telephone Connections..................................... 26
Registration.................................................... 26
Notification ..................................................... 26
Location ......................................................... 26
Phone Cord Connection................................. 27
Phone LED (Red)........................................... 27
Operation Monitor LED (Green)..................... 27
Dialing Format ............................................... 27
Phone Line Monitor........................................ 27
Phone Line Test Points.................................. 28
Communication Failure.................................. 28
Ground Start .................................................. 28
Relay Installation ....................................... 28
Ground Start Jumper ................................. 29
D128 Dual Phone Line Switcher .................... 29
Operation................................................... 29
Primary Phone Lines,
Primary Phone Numbers ........................... 30
Watchdog Feature ..................................... 30
Installing the D128..................................... 30
D128 Status LEDs ..................................... 31
On-Board Points................................................. 32
Description..................................................... 32
Point Sensor Loops........................................ 32
Point Parameters ........................................... 33
Point Response Time..................................... 33
Off-Board Points................................................. 34
Point (ZONEX) Buss ...................................... 34
D8125 POPEX Module
D8127 POPIT Modules.................................. 34
Installing the D8125 POPEX Module ............. 35
Wiring the D8125 to the D7212 ................. 35
Wiring POPITs to the
Data Expansion Loop ................................ 37
Wiring Data Expansion Loops to
POPEX Modules........................................ 38
POPIT Sensor Loops................................. 38
Point Assignments..................................... 39
Introduction .......................................................... 7
Areas and Accounts......................................... 8
Communicator ................................................. 8
D1255 Alpha III Command Center ................... 8
Keyswitch......................................................... 8
Event Memory.................................................. 9
Event Log......................................................... 9
EMI/Lightning Transient Protection.................. 9
Programming ................................................... 9
Other Features............................................... 10
D7212 Control/Communicator Assembly ....... 11
Ordered Separately ................................... 11
Listings and Approvals................................... 12
Fire ............................................................ 12
Burglary ..................................................... 12
Installation .......................................................... 13
Before You Begin........................................... 13
Enclosure Options.......................................... 13
Beginning the Installation............................... 13
Mounting the Enclosure............................. 13
Premises Wiring ........................................ 14
Installing the D7212 Assembly .................. 14
Connecting Earth Ground .............................. 14
Locking the Reset Pin.................................... 15
Finishing the Installation ................................ 16
Charge the Battery as You Finish.............. 16
Install and Wire Detection Devices ............ 16
Install Modules and Relays........................ 16
Make the Telephone Connections ............. 17
Connect the On-Board Points and Command
Centers...................................................... 17
Power Up................................................... 17
Programming the Panel ................................. 17
Install the Point Chart Label........................... 17
Power Supply...................................................... 18
Primary Power ............................................... 18
Primary (AC) Power Circuit........................ 18
Installing the Transformer.......................... 18
Secondary Power........................................... 19
Secondary (DC) Power.............................. 19
Installing the Battery .................................. 19
Battery Supervision ................................... 19
Battery Charging Circuit............................. 20
Battery Discharge/Recharge Schedule
(No AC Power) .......................................... 20
Charging Status and Low Battery LEDs......... 21
Charging Status LED (Yellow)................... 21
Low Battery LED (Red).............................. 21

D7212 Operation & Installation Manual
Page 5
© 1993-1996 Radionics74-06913-000-B 2/96
D8128A OctoPOPIT Module.......................... 41
Listing ........................................................ 41
Installing the OctoPOPIT ........................... 41
Wiring OctoPOPITs to the D7212.............. 42
Line Termination........................................ 43
OctoPOPIT Sensor Loops ......................... 44
Off-board Relays ................................................ 46
D8129 OctoRelay........................................... 46
Configuring the D8129 OctoRelay ............. 46
Relay Outputs............................................ 46
Installation ................................................. 48
Wiring Connections ................................... 48
Arming Devices .................................................. 49
Description..................................................... 49
D1255 Command Centers ............................. 49
Assigning the D1255 an Address .............. 49
Installation ................................................. 50
D268/D269 Independent Zone Control
D279 Independent Zone Control.................... 51
Keyswitch....................................................... 52
Description................................................. 52
Programming ............................................. 52
Installation ................................................. 52
Keyswitch Operation.................................. 52
Programmer and Accessory Connections ....... 53
Programmer Connector (J7) .......................... 53
Expansion Port (J4) ....................................... 54
Programmer Access Reports..................... 54
Accessory Connector (J2).............................. 54
D7212 Faceplate ................................................. 55
Quick Reference Terminal Description ............ 56
Installation Guide for UL and Fire Applications57
Listings and Approvals................................... 57
Fire ............................................................ 57
Burglary ..................................................... 57
Optional Compatible Equipment .................... 58
Burglary Applications................................. 58
Fire Applications ........................................ 58
System Chart ...................................................... 60
System Wiring Diagram, Issue A ...................... 61
Current Rating Chart for
Standby Battery Calculations............................ 62
Standby Battery Requirements ......................... 63
Standby Battery Calculation for
Fire Alarm Applications ..................................... 64
Troubleshooting Guide ...................................... 66
Introduction .................................................... 66
Self Diagnostics ............................................. 66
Phone Line Trouble........................................ 68
Communications Failure ................................ 69
Problems Programming the Panel ................. 70
Problems with Points ..................................... 71
Problems with the D8125 POPEX
Data Expansion Loops................................... 74
Checking Shielded Cable............................... 75
EMI on Long Wire Runs................................. 75
Problems with Command Centers ................. 76
Battery and Power Reports............................ 77
Watchdog Reset Reports............................... 77
Runaway Reports to the Receiver ................. 77
Overloaded Power Supply ............................. 78
Command 57 Toggles Default Idle Text ........... 79
Command 59 Toggles Default Idle Text ........... 79
Specifications..................................................... 80

D7212 Operation & Installation Manual
Page 6
74-06913-000-B 2/96 © 1993-1996 Radionics
Figures and Tables
Figure 1: D7212 System Configuration ......................................................7
Figure 2: Enclosure Mounting ..................................................................13
Figure 3: Reset Pin .................................................................................... 15
Figure 4: Charging and Battery LEDs ...................................................... 21
Figure 5: Relays for Terminals 7 and 8 ....................................................24
Figure 6: RJ31X Wiring .............................................................................26
Figure 7: Telephone Connections ............................................................28
Figure 8: Ground Start Relay ....................................................................28
Figure 9: Ground Start Jumper ................................................................29
Figure 10: D128 Dual Phone Line Switcher .............................................31
Figure 11: On-board Point Sensor Loop Wiring .....................................32
Figure 12: D8125 Connections .................................................................36
Figure 13: Typical Expansion Loop/POPIT Configuration .....................38
Figure 14: D7212 Program Record Sheet ................................................39
Figure 15: POPIT Labels ...........................................................................40
Figure 16: D8128A OctoPOPITs ...............................................................42
Figure 17: D8129 OctoRelay Connections...............................................48
Figure 18: Power at Command Centers...................................................51
Figure 19: Keyswitch Wiring.....................................................................52
Figure 20: Reset Pin ..................................................................................53
Figure 21: Programmer and Accessory Connections ............................54
Table 1: Data Expansion Loop Wire Specifications ...............................37
Table 2: D8128A OctoPOPIT Switch Settings .........................................45
Table 3: D8129 Switch Settings................................................................47
Table 4: D1255 Address Settings .............................................................49
Table 5: D1255 Connections..................................................................... 50

D7212 Operation & Installation Manual
Page 7
© 1993-1996 Radionics74-06913-000-B 2/96
Introduction
Figure 1: D7212 System Configuration
Points
TheRadionicsD7212Control/Communicatorpanelprovidesupto48separatepointsof
protection.Pointprogrammingparametersdeterminethepanel’sresponsetoopenand
shorted conditions on the point’s sensor loop. Points are programmed individually with
several options to custom-fit the protection to your installation.
Points 1 to 8 are located on the D7212 circuit board (on-board points). They are standard
sensor loops. The remaining 40 off-board points are POPIT (PointofProtection Input
Transponder)points.Eachoff-board pointrequiresa POPIT module. D8127POPIT
modulesrequiretheD8125POPEXmodule.The D8128A OctoPOPIT modulecombines
eight POPITs in a single module and does not require the D8125 POPEX module.
D7212
D8128A OctoPOPIT combines
8 POPIT Points in one module.
D8125 Interface for D8127
POPITS Points 9 - 48 D8129 OctoRelay
provides alarm and
auxiliary relay output.
(Other functions available.)
Use D1255 Command Centers and/or
keyswitches to arm the D7212 by area. Each
panel can have up to 8 areas. Each area can
have its own account number or areas can be
grouped together with a common account number.
Points of protection are assigned to areas.
D128 module allows the
D7212 to monitor two phone
lines.
D9131 module connects
to a parallel printer to
print event log locally.
On-board Points
1 to 8

D7212 Operation & Installation Manual
Page 8
74-06913-000-B 2/96 © 1993-1996 Radionics
Areas and Accounts
The D7212 supports up to eight separate areas. You can assign all points to a single area
or spread them out over up to eight areas.
You arm and disarm the D7212 panel by area. You can arm and disarm several areas with
one menu function. You can also assign a passcode an authority level that allows a user
to arm an area from a remote command center in another area. Assigning each area its
ownaccount numbercreates eightseparate accounts in one D7212panel. Assigningthe
same account number to different areas, groups them together in a single account.
Area options include: exit tone and delay, separate fire and burglary outputs, and multiple
openingandclosingwindows.
Communicator
TheRadionicsD7212Control/Communicatorpanelusesabuilt-indigitalcommunicatorto
send reports to the receiver. The panel transmits reports in either the Modem II or BFSK
format. Your D6500 receiver's MPU and line cards must have software revision 6.00 (or
greater)installed toaccept ModemII reports from the D7212.Power yourreceiver down
and up to print the software revision numbers.
The D7212 connects to an RJ31X jack for phone line seizure. Connection to the RJ31X
complieswith FCCregulations for usingthe publictelephone network.You can programthe
paneltodirect reports tofourseparate phone numbers.AddingtheD128 Dual PhoneLine
Switcher module allows you to connect and supervise a second phone line.
D1255 Alpha III Command Center
TheD1255 AlphaIII CommandCenter offerscomplete systemcontrol andannunciation.
TheD1255features an illuminatedkeypad,a16-character English languagedisplay,anda
built-in speaker that offers several distinct warning tones. Switches on the D1255 assign
an address (1 to 8) to the command center. You assign addresses to areas in the
CommandCenterAssignmentssection of theprogram.
You can connect a maximum of 32 command centers to the D7212. The available power,
number of supervised command centers, and number of areas you intend to use, affect the
total number of command centers you can connect to the D7212.
The D7212 can supervise up to 8 command centers. The panel transmits a serial device
trouble report, SDI FAILURE in the Modem II format orTROUBLE ZN D in the BFSK
format, if it loses communication with a supervised command center. You can add more
command centers but only eight can be supervised. See
Command Center
in the
D7212
ProgramEntryGuide(74-06915-000)
forcompletedetailsoncommandcenteroptions.
Keyswitch
You can arm and disarm any of the eight available areas with maintained or momentary
closure devices such as keyswitches. Keyswitches connect to points. Point programming
determines which area a keyswitch controls. See
Options
in the
Point Index Parameters
moduleofthe
D7212ProgramEntryGuide
(74-06915-000)
.

D7212 Operation & Installation Manual
Page 9
© 1993-1996 Radionics74-06913-000-B 2/96
Event Memory
The D7212 uses event memory to store events for each area. You can view the events for
anarea at aD1255 Command Centerassignedto thearea.The D7212 panelclears the
events for an area from event memory and starts storing new events when you master arm
thearea.
Event Log
The D7212 stores up to 500 events and event modifiers from all areas in it's event log.
Event modifiers add information about an event to the log. Some events are always
followed by a modifier. For example, the D7212 adds at least two items to the log each
time you arm or disarm an area, the open (or close) event and an event modifier showing
the previous arming state.
All events and their modifiers are stored even if the D7212 does not send a report for them.
You can view the log at a D1255 Command Center, print it locally using the D9131 Parallel
Printer Interface and a parallel printer, or upload it to a D5300 Remote Account Manager II
(RAM II).
See
S- View Log
in the
Security System User's Guide
(71-06141-000) for a complete
listing of log events and event modifiers.
EMI/Lightning Transient Protection
The D7212 maintains the Radionics high level of quality and field dependability. Its design
significantlyreduceselectromagneticinterferenceandmalfunctiongenerallycausedby
lightning.
Programming
UseeithertheRadionicsD5200Programmer,ortheD5300Remote Account Manager II
(RAMII)toprogramtheD7212.RefertotheD7212Prog
ramEntryGuide
(74-06915-000)
forprogrammingoptions.
NCI
154

D7212 Operation & Installation Manual
Page 10
74-06913-000-B 2/96 © 1993-1996 Radionics
Other Features
The D7212 has many programmable features. A short list of some of the features follows.
Complete details on all the D7212’s features can be found in the
D7212 Program Entry
Guide
(74-06915-000)
.
• SupervisionofAC (primary power),battery(secondary power), ZONEXandSDIbuses,
CPU(CentralProcessingUnit),1printer,andtelephonelines
• Automatic system test reports
• Remoteaccess forprogramming, diagnostics,and loguploads usingthe Radionics
D5300Remote AccountManager II(RAM II)
• RAMLineMonitoransweringmachinework-around
• FireAlarmVerification
• ProgrammableAlarmOutput
• ProgrammableRelayOutputusingtheD8129OctoRelayModule
• OpeningandClosingWindows
• Skeds(scheduledevents)

D7212 Operation & Installation Manual
Page 11
© 1993-1996 Radionics74-06913-000-B 2/96
D7212 Control/Communicator Assembly
TheRadionicsD7212Control/Communicatorisshippedpre-assembledfromthefactory.
Youshould receivethe following partswith yourD7212 panel.
LiteraturePack
•
D7212InstallationReferenceGuide
(74-06913-000)
•
D7212ProgramRecordSheet
(74-06894-000)
•
ULSmokeDetectorCompatibilityTechnogram
(73-06143-000)
•
UL1023HouseholdBurglaryTechnogram
(73-06806-000)
•
PointChartLabel
(79-06916-000)
• Eight 1k ý end-of-line resistors
• Two14", 18AWG, color-codedbattery leads
•
SecuritySystemOwner’sManual(71-06633-000)
D7212Assembly:
• D7212PCboard
• Faceplateshield
• MountingSkirt
• One#6x1¦4"screw
Ordered Separately
Order the following to complete a basic 8 point D7212 installation.
• D1255orD720CommandCenter(or keyswitch)
• D1640Transformer
• D126Battery
• D161orD162PhoneCord
(ordertwo cordsif youare usingthe D128Dual PhoneSwitcher)
• D8103,D8109,orD8108AEnclosure

D7212 Operation & Installation Manual
Page 12
74-06913-000-B 2/96 © 1993-1996 Radionics
Listings and Approvals
Fire
UL
UnderwritersLaboratoriesliststheD7212 Control/CommunicatorasaSignalSystemControl
Unit for:
CentralStation,Local, Auxiliary, RemoteStation,and Household FireWarning.
CSFM
Approvedby theCalifornia StateFire Marshal.
NYC-MEA
Approved by New York City's Materials and Equipment Acceptance System.
FactoryMutual(FM)
Submitted for evaluation by Factory Mutual.
Burglary
UL
UnderwritersLaboratoriesliststheD7212Control/Communicator for:
Central Station, Local, Police Connect, Mercantile Safe and Vault, and Grade A Household
systems.
DepartmentofDefense (DOD)
TheD7212hasbeengrantedapprovalforDepartmentofDefense(DOD)installationsin
SensitiveCompartmentedInformationFacilities(SCIF).

D7212 Operation & Installation Manual
Page 13
© 1993-1996 Radionics74-06913-000-B 2/96
Installation
Before You Begin
This
Installation
section contains a general installation procedure. It refers you to other
sections of the manual for detailed instructions.
Radionicsrecommendsyou review thismanualand the
D7212ProgramEntry Guide
(74-06915-000)beforeyoubegintheinstallation todeterminethehardwareandwiring
requirements for the features you want to use.
Havethe followingadditional documents handyas youreadthrough thismanual:
•
D7212ProgramRecordTrainingSheet
(74-06895-000)
•
SecuritySystemOwner’sManual
(71-06633-000)
•
D7212OperationandInstallationManual
(74-06144-000)
Before you begin the installation of the D7212 you should be familiar with the operation of
theD5200programmerortheRAMIIremoteprogrammer.
Enclosure Options
Mountthe D7212 Control/Communicatorassemblyin any oftheRadionics enclosures
listed below. Refer to the
Installation Guide for UL and Fire Applications
in this manual to
determine if your application requires a specific enclosure.
• D8103UniversalEnclosure(gray)
• D8109FireEnclosure(red)
• D8108AAttack ResistantEnclosure (gray)
Beginning the Installation
Mounting the Enclosure
Mount the enclosure in the desired location. Be certain to use all five mounting holes. See
Figure2.
Figure 2: Mounting Enclosure
HOOK OPENINGS
LOCK-DOWN TAB
SKIRT MOUNTING HOLE
MOUNTING
SKIRT HOOK
MODULE MOUNTING
LOCATIONS
MOUNTING
SKIRT HOOK
TAMPER SWITCH
MOUNTING LOCATION
MODULE
MOUNTING
LOCATIONS
BACK OF D7212
POINT CHART LABEL

D7212 Operation & Installation Manual
Page 14
74-06913-000-B 2/96 © 1993-1996 Radionics
PremisesWiring
Run the necessary wiring throughout the premises and pull the wires into the enclosure.
EMI (Electro Magnetic Interference) may cause problems:
EMI may occur if you install
the D7212 system or run system wires near the following:
• Computernetworksystem
• Electrical lines, fluorescent fixtures or telephone cabling
• Hamradio transmittersite
• Heavymachineryandmotors
• Highvoltageelectricalequipmentortransformers
• PBX telephone system
• Public service (police, fire departments, etc.) using radio communications
• Radio station transmitter site, or other broadcast station equipment
• Weldingshop
If you think that EMI may be a problem, use shielded cable. The drain wire for the shielded
cable must have continuity from terminal 10 on the D7212 to the end of the wire run. If
continuity is not maintained, the shielded cable may aggravate potential noise problems
ratherthaneliminatethem.
Connectingthe drain wireto ground atother than terminal10 may alsoproduce problems.
If you cut the drain wire to install devices be certain to splice it together. Solder and tape
all splices.
Installing the D7212 Assembly
1. Place the D7212 assembly over the inside back of the enclosure, aligning the large
rectangular openings of the mounting skirt with the mounting hooks of the enclosure.
Slide the D7212 down so it hangs on the hooks. See Figure 2.
2. Remove the tape from the #6x1/4" screw in the mounting tab on the D7212 assembly.
The screw passes through the mounting tab and into the skirt mounting hole in the
enclosure. Tighten the screw to secure the D7212 assembly in the enclosure.
3. Connect earthgroundto thepanelbefore makinganyother connections.See
ConnectingEarthGround
below
.
Connecting Earth Ground Terminal 10
To help prevent damage from electrostatic charges or other transient electrical surges,
connect the D7212 to earth ground at terminal 10 before making any other connections. A
groundingrodorcoldwaterpipearerecommended earthgroundreferences.
Do not use telephone or electrical ground for the earth ground connection
. Use 16
AWG wire when making the connection. Do not connect any other panel terminals to earth
ground.
Locking the Reset Pin
Locking the Reset Pin disables the panel. See Figure 3. The D7212 ignores the command
centersand pointswhile disabled.CALL FORSERVICE appearsin commandcenter
displays while the pin is locked down.

D7212 Operation & Installation Manual
Page 15
© 1993-1996 Radionics74-06913-000-B 2/96
Existing reports transmitted with Reset Pin locked down:
Any reports that are in the
panel’s report buffer when you lock down the Reset Pin, will be transmitted. However, no
new reports can be created with the pin locked down.
To prevent buffered reports from being transmitted, momentarily close the Reset Pin, wait
for the buzzer to stop sounding, and then lock the pin down to prevent new reports from
beinggenerated.
Locking Reset Speeds Programming:
If you have supervised command centers or other
supervised devices connected to the Data Bus (terminals 30 and 31), locking the Reset
Pinwillspeed communicationbetweenthepanel andtheD5200.
On-board relays (terminals 6, 7, and 8) and off-board relays, deactivate when the panel is
reset. There is power at terminal 8 when the relay is deactivated. Activation interrupts
power at that terminal. The relays remain deactivated while the Reset Pin is locked in the
disableposition.
You can program the panel while it is locked in the disable position with either the D5200 or
D5300 (RAM II) programmers. If you place the reset pin in the disable position with one or
more areas disarmed, there must be an entry in the
AnswerDisarmed
program item to use RAM II.
If you place the reset pin in the
disablepositionwhenall areas are
armed, there must be an entry in the
AnswerArmed
programitem.See
RAM Parameters
in the
D7212ProgramEntryGuide
(74-06915-000).
Releasing the reset pin from the
closed position resets the panel.
The panel resets all its timers,
counters, indexes, and buffers.
Changesto some program
parametersrequirearesetbefore
theybecomeeffective:
Radionics
recommends that you reset the
panelafterchangingprogram
parameterswiththeD5200programmer.
TheD5300(RAMII)programmerpromptsyou
for a "RESET BYE" when a program change requires that the panel be reset.
Lock the Reset Pin Now
Locking the pin in the disable position allows you to power up the panel and charge the
battery as you install the detection devices and command centers. Lock the pin down now.
SDI DEVICE WIRING
Operation Monitor
Pulses When Normal
Flickers When Ringing
RED
YELLOW
GREEN
BLACK
32
POWER +
DATA BUS A
DATA BUS B
COMMON -
31
30
29
Reset Pin
Disable All Except Battery
Charging And Local Programming
GRN
RESET PIN
LOCKED (CLOSED)
RESET PIN
NORMAL (OPEN)
Figure 3: Reset Pin
NCI
142,
347, 353

D7212 Operation & Installation Manual
Page 16
74-06913-000-B 2/96 © 1993-1996 Radionics
Finishing the Installation
Earth ground and reset pin first:
Make the earth ground connection to terminal 10 and
lock the reset pin in the closed position if you haven’t already done so.
Charge the Battery as You Finish
Connect the battery and then the transformer so that the panel can charge the battery as
you finish the installation. See the
Power Supply
section for instructions.
On-board Buzzer Sounds at Power Up and Reset:
The D7212 performs a series of self
diagnostic tests of its hardware, software, and program at power up and at reset. The
buzzer on the D7212 sounds during the tests. They take about 10 seconds to complete.
If the panel fails any of the tests, the buzzer continues sounding and a system trouble
message appears at the command centers. See
Self Diagnostics
in the
Trouble Shooting
section for a description of each system trouble message.
Touch Terminal 10 first:
If the on-board buzzer sounds briefly when you touch the panel,
you're discharging any static charge you may be carrying to the panel. The panel may
generateWATCHDOGRESET and/or PARAMFAILevents.See the
TroubleShooting
section for a description of these events. Always touch terminal 10, the panel's earth
groundconnection, beforebeginningworkonthepanel.
Install and Wire Detection Devices
Install and wire detection devices and command centers at their locations throughout the
premises. DO NOT make the connections at the panel end of the wiring yet.
The
On-Board Points
section of this manual contains instructions for wiring the on-board
points to detection devices. The
Arming Devices
section contains instructions for wiring
thecommand centers.
Instructions for wiring the off-board point POPIT sensor loops are found in the instructions
packaged with the POPIT modules.
Install Modules and Relays
1.
PowerDown First:
PowerdowntheD7212byunpluggingthetransformerand
disconnectingthebattery.Radionicsrecommends that you powerdowntheD7212
when installing modules or relays, or when making wiring connections to the panel.
2. Install and wire any modules required for your installation as described in the module’s
installation instructions.
Instructions for the D8125 POPEX Module, the D8128A OctoPOPIT Module, the
D8129OctoRelay Module,theD811 ArmStatus Relay Module,and the D128Dual
PhoneLine Switcher appearinthis manual.
See
Off-board Points
forD8125 andD8128A instructions. See
Relays
forD8129 and
D811instructions. See
DualLine Transmitting
in the
TelephoneConnections
section
for instructions for the D128.
3. If you are using the power outputs at terminals 7 or 8, install a D136 relay in the
appropriatesockets. See
ProgrammablePower Outputs
in the
PowerOutputs
section
for instructions.
4. If you are using a ground start phone system, insert a D136 relay in socket K6/J5 and
set the ground start pin in the ground start position. See
Ground Start
in the
Telephone
Connections
section.

D7212 Operation & Installation Manual
Page 17
© 1993-1996 Radionics74-06913-000-B 2/96
Make the Telephone Connections
See
TelephoneConnections
.If youare connecting theD7212 toa groundstart phone
system, you need to install D136 relay, see
Install Modules and Relays
on the previous
page.
Connect the On-Board Points and Command Centers
Connecttheon-boardpointandcommandcenterwiringtothe D7212. See the
On-Board
Points
and
Arming Devices
sections for instructions.
Power Up
Reconnectthe batteryand thenplug inthe transformer.Remember thebuzzer soundsfor
10 seconds when you first power up the panel.
Leave the reset pin locked down for now.
Yellow Charging Status LED doesn’t go out:
If the yellow charging status LED doesn’t
go out within 5 minutes of powering up the panel, the battery may be deeply discharged, or
you may have connected too many powered devices to the panel. Combined continuous
current draw for terminals 3, 8, and 32, and the Accessory Connector (J2) cannot exceed
1.4A. See the
Power Outputs
section for help.
Programming the Panel
If you haven’t created a program for the panel, review the
D7212 Program Entry Guide
(74-
06915-000). Check to be certain you have all the required accessory modules installed for
the features you want to use.
Usethe D5200Programmer orthe RAMII remoteprogrammer toload your custom
programintothepanel.
Move the reset pin to the normal position. See Figure 3. The panel transmits reboot and
battery reports to the receiver.
Install the Point Chart Label
Point chart label required for fire systems with verification points:
You must install the
point chart label for fire or combined fire/burglary systems using verification points.
Use the program record sheet to gather the information you need to fill out the point chart.
Install the label on the enclosure door as shown in figure 2. To avoid smearing your entries
on the chart, use the label's peel off backing to press the label in place.

D7212 Operation & Installation Manual
Page 18
74-06913-000-B 2/96 © 1993-1996 Radionics
Power Supply
Primary Power Terminals 1 2
Primary (AC) Power Circuit
A 16.5 VAC, 40 VA internally fused transformer (Radionics model D1640) is the primary
power source for the D7212. The AC power circuit provides 1.9 Amps of rectified AC
power. The panel reserves 500 mA of this power for internal operations leaving 1.4 Amps
forpowereddevices.
Transient suppressors and spark gaps protect the circuit from power surges. This
protection relies on the ground connection at terminal 10. Make sure you connect terminal
10 to a proper ground. See
Connecting Earth Ground
in the
Installation
section
.
ACPowerFailure
The D7212 indicates an AC power failure when the power at terminals 1 and 2 is missing.
The
AC Fail Time
program item sets the number of seconds that AC must be missing
beforethe panel acknowledgesthe failure andthe number ofseconds after thepower
returnsbeforethepanelacknowledgestherestoralofpower.
You can program
AC Fail Time
from 1 to 90 seconds. The Radionics default sets
AC Fail
Time
at 10 seconds.
Installing the Transformer
Do not short the terminals of the transformer:
Shortingtheterminals opens theinternal
fuse causing permanent failure. Connect the transformer to terminals 1 and 2 of the panel
beforepluggingit intothepowersource.
Use 18 AWG (minimum) wire to connect the transformer to the panel. Wire length should
be kept as short as possible. Maximum length is 50 feet.
Connect the battery and then plug in the transformer:
Radionicsrecommends that you
always connect the battery first and then plug in the transformer. Instructions for
Installing
the Battery
appear on the next page.
Only plug the transformer into an unswitched, 120 VAC, 60 Hz power outlet. Secure the
transformer to the outlet with the screw provided.
Never sharethetransformerwith other equipment:
ForeigngroundsontheACinput
damagetheD7212powercircuit.
AC wiring can induce both noise and low level voltage into adjacent wiring. Route phone
andsensor loopwiring away fromany ACconductors, includingthe transformer wire.Route
datawiringawayfromACandphone wiring.
D8004TransformerEnclosurerequiredfor fire systems:
UsetheD8004Transformer
EnclosurefortheD1640transformerinfireandcombinedfire/burglaryapplications.

D7212 Operation & Installation Manual
Page 19
© 1993-1996 Radionics74-06913-000-B 2/96
Secondary Power Terminals 45
Secondary (DC) Power
A12V,7Ahsealedlead-acidrechargeablebattery(RadionicsD126) supplies secondary
powerfor auxiliaryand alarmoutputs, and powers the systemduring interruptionsin
primary(AC)power.
Lead Acid Batteries ONLY:
TheD7212chargingcircuit is onlycalibratedforlead-acid
batteries. Do not use gel-cell or nicad batteries.
Extra Batteries Increase Back-up Time:
Toincreasebatteryback-up time, connecta
second 12V, 7 Ah battery in parallel to the first battery to form a 12V, 14 Ah battery. Use a
D122Dual BatteryHarness toensure properand safeconnection. Youcan usethe D8132
Battery Charger Module to connect two additional batteries for a total of four. See the
D7212 Standby Battery and Current Rating Chart
in this manual for battery standby time
calculations.
Installing the Battery
Place the battery upright in the base of the enclosure. Locate the red and black leads
supplied in the literature pack. Connect the black battery lead to terminal 4, and then to the
negative (-) side of the battery. Connect the red battery lead to terminal 5, and then to the
positive (+) side of the battery.
Warning, High Current Arcs Possible:
The positive(red) batterylead and Terminal 5
can create high current arcs if shorted to other terminals or the enclosure. Use caution
when working with the positive lead and terminal 5. Always disconnect the positive (red)
lead from the battery before removing it from terminal 5.
Replacement
Radionicsrecommends batteryreplacement every3 to5 yearsunder normaluse.
Exceeding the maximum output ratings, or installing the transformer in an outlet that is
routinely switched off, causes heavy discharges. Routine heavy discharges can lead to
prematurebatteryfailure.
D8132boosts battery backup:
AddingaD8132BatteryChargerModulesupports
additional batteries of up to 36 Ah capacity if required.
Warning:
The transformers for the D7212 and any D8132 modules connected to it must be
powered from the same 120 VAC circuit. The D7212 supervises AC power by monitoring
the power from the transformer connected to terminals 1 and 2. It cannot supervise the AC
power for D8132 modules if their transformers are not plugged into the same AC circuit as
thetransformerfor the panel.
Battery Supervision
When the battery voltage drops to 13.8 VDC, the yellow Charging Status LED lights. When
the battery drops to 12.1 VDC the red Low Battery LED lights and the panel, if programmed
for power supervision, transmits a BATTERY LOW report in the Modem II transmission
format. It transmits a TROUBLE ZN 9 report in the BFSK format.
If the battery is missing or shorted, the red Low Battery LED flashes at the same rate as
thegreen OperationMonitor LED.If the panel is programmedfor powersupervision, it
transmits a BATTERY MISSING report in the Modem II transmission format, or TROUBLE
ZN 9 report in the BFSK format.

D7212 Operation & Installation Manual
Page 20
74-06913-000-B 2/96 © 1993-1996 Radionics
Battery Supervision (Continued)
When battery voltage returns to 13.7 VDC the Low Battery LED goes out. If the panel is
programmed for power supervision, it transmits aBATTERY RESTORAL report in the
Modem II transmission format or RESTORAL ZN 9 report in the BFSK format. At 13.9
VDC the Charging Status LED goes out.
Investigate low battery reports right away
: If primary (AC) power is off and the
dischargecontinues,thepanelbecomesinoperativewhen the battery voltagedropsbelow
10.2VDC.
Battery Charging Circuit
FloatCharge
The float voltage for the battery charging circuit is 13.9 VDC at a maximum current of 1.4
Amps. Deduct any continuous load for devices connected to the panel from 1.4 Amps to
find the actual current available for charging.
Load Shed Relay protects battery:
Duringan AC powerloss the batterysupplies all
power to the security system. If the battery voltage falls below 10.2 volts during an AC
power loss, a “load shed” relay isolates the battery from the panel and disables the panel.
Loadshedprotects thebatteryfrombeing damagedbydeepdischarge. WhenACpower
restores, the load shed relay resets and battery voltage is again available.
Reset or power down required for shorted battery:
Ifthe D7212determines the battery
is shorted, it uses the load shed relay to disconnect the battery. You must reset or power
down the panel after correcting the problem to reset the load shed relay and reconnect the
battery.
Reset the panel by momentarily placing the reset pin in the disable position. See Figure 3.
The red Low Battery LED continues to flash until you reset the panel.
A shorted battery condition is created either by a shorted cell inside the battery or by a
short on terminals 4 and 5. A shorted battery may generate WATCHDOG RESET reports.
Battery Discharge/Recharge Schedule (No AC Power)
DischargeCycle
AC OFF AC fail report when AC fails if panel is programmed to report AC failure at
occurrence.
13.9VDC Chargingfloatlevel
13.8VDC ChargingStatusLEDon
12.1VDC Low Battery & AC fail reports if programmed; Low Battery LED on
10.2VDC Battery load shed (processing functions continue if AC is present)
RechargeCycle
ACON Load shed relayresets, battery chargingbegins, batterytrouble and
AC restoral reports sent.
13.7VDC Battery restoral reports sent, Low Battery LED off
13.9VDC Charging Status LED off, battery float charged
Other manuals for D7212
2
Table of contents
Other Radionics Control Panel manuals
Popular Control Panel manuals by other brands

Engineering Incorporated
Engineering Incorporated PMA6000 Pilot's guide and operation manual

Siemens
Siemens SIMATIC IFP1500 V2 Quick install guide

Mircom
Mircom FX-2000 series Operation

Seav
Seav LRX 2100 quick start guide

ADT
ADT 6128B installation guide

DMP Electronics
DMP Electronics XR100 Programming guide

ADT
ADT Command Hybrid quick guide

Motorline professional
Motorline professional MC50 User& installer's manual

Zeta
Zeta Premier Quatro installation manual

Honeywell Home
Honeywell Home HZ221 TrueZONE Professional installation guide

Mircom
Mircom FA-200 Series Installation and operation manual

Citron
Citron ZigBee SC-TZ1-01 instruction manual