Radionics D8024 User manual

34377C 06/99 © 1999 Radionics, a division of Detection Systems, Inc.
D8024, D9024, D10024 Analog Fire Alarm Control Panels
Networking Guide

Contents
D8024, D9024, D10024 Networking Guide
34377C 06/99 Page 1© 1999 Radionics. All rights reserved.
1.0 Notice ...................................................................................................................................................................... 3
2.0 Warnings and Cautions .......................................................................................................................................... 3
3.0 FCC Notices ............................................................................................................................................................ 3
Part 15.............................................................................................................................................................................3
4.0 UL/NFPA Notices .................................................................................................................................................... 3
5.0 Network Installation................................................................................................................................................ 4
5.1 Serial Port Assignment and Function.....................................................................................................................4
5.2 System Installations..............................................................................................................................................4
6.0 Shared Zone Network ............................................................................................................................................. 5
6.1 Shared Zone Network Operation ...........................................................................................................................5
6.1.1 Alarm Conditions...........................................................................................................................................5
6.1.2 In a Fault Condition.......................................................................................................................................6
6.1.3 Repeaters and Peripherals.............................................................................................................................6
6.2 Shared Zone Network Programming......................................................................................................................6
6.2.1 Master Panel Programming, Shared Zone Network........................................................................................6
6.2.2 Slave Panel Programming, Shared Zone Network..........................................................................................8
7.0 Report and Control Network................................................................................................................................. 10
7.1 Report and Control Network Operation................................................................................................................10
7.1.1 Alarm Conditions.........................................................................................................................................10
7.1.2 System Reset from Alarm Conditions ..........................................................................................................10
7.1.3 Fault Condition............................................................................................................................................11
7.1.4 Event Log....................................................................................................................................................11
7.1.5 D9070 Controllers and D9069 Annunciators.................................................................................................11
7.2 Report and Control Network Programming..........................................................................................................12
7.2.1 Master Panel Programming, Report and Control Network ............................................................................12
7.2.2 Slave Panel Programming, Report and Control Network ..............................................................................14
8.0 Panel Programming Options................................................................................................................................ 16
9.0 Networking Schematics........................................................................................................................................ 16
9.1 Mini Network.......................................................................................................................................................16
9.2 Master/Slave.......................................................................................................................................................17
9.3 RS-485 High Integrity Network............................................................................................................................17
Figures
Figure 1: D9051 Network Connections...........................................................................................................................4
Figure 2: Shared Zone Network.....................................................................................................................................5
Figure 3: Front Panel Displays.......................................................................................................................................6
Figure 4: Main Menu......................................................................................................................................................6
Figure 5: Path through Commission Menus to Network..................................................................................................7
Figure 6: Network Menu One.........................................................................................................................................7
Figure 7: Network Menu Two.........................................................................................................................................7
Figure 8: Network Menu Three.......................................................................................................................................7
Figure 9: Network Menu Four ........................................................................................................................................7
Figure 10: Network Menu Five.......................................................................................................................................7
Figure 11: Network Menu Six.........................................................................................................................................8
Figure 12: Network Menu Seven....................................................................................................................................8
Figure 13: Network Menu Eight......................................................................................................................................8
Figure 14: Commission Menu Three..............................................................................................................................8
Figure 15: Master-to-Slave Menu One...........................................................................................................................8
Figure 16: Commission Menu One................................................................................................................................8
Figure 17: Commission Menu Three..............................................................................................................................8
Figure 18: Network Menu One.......................................................................................................................................9
Figure 19: Network Menu Two.......................................................................................................................................9
Figure 20: Network Menu Four ......................................................................................................................................9

D8024, D9024, D10024 Networking Guide
© 1999 Radionics. All rights reserved. Page 234377C 06/99
Figure 21: Network Menu Five.......................................................................................................................................9
Figure 22: Network Menu Six.........................................................................................................................................9
Figure 23: Network Menu Seven....................................................................................................................................9
Figure 24: Network Menu Eight......................................................................................................................................9
Figure 25: Commission Menu Three..............................................................................................................................9
Figure 26: Configure Menu............................................................................................................................................9
Figure 27: Memory Check Message............................................................................................................................. 10
Figure 28: Commission Menu Three............................................................................................................................ 10
Figure 29: Master Panel Fault Condition Display.......................................................................................................... 11
Figure 30: RS-485 Link Message.................................................................................................................................11
Figure 31: Master Panel Event Log Display..................................................................................................................11
Figure 32: Main Menu.................................................................................................................................................. 12
Figure 33: Path through Commission Menus to Network.............................................................................................. 12
Figure 34: Network Menu One..................................................................................................................................... 12
Figure 35: Network Menu Two.....................................................................................................................................12
Figure 36 Network Menu Three....................................................................................................................................13
Figure 37: Network Menu Four ....................................................................................................................................13
Figure 38: Network Menu Five..................................................................................................................................... 13
Figure 39: Network Menu Six....................................................................................................................................... 13
Figure 40: Remote Alarms Query Menu....................................................................................................................... 13
Figure 41: Network Menu Seven..................................................................................................................................13
Figure 42: Network Menu Eight....................................................................................................................................13
Figure 43: Commission Menu Three............................................................................................................................ 13
Figure 44: Master-to-Slave Menu One......................................................................................................................... 14
Figure 45: Commission Menu One.............................................................................................................................. 14
Figure 46: Commission Menu Three............................................................................................................................ 14
Figure 47: Network Menu One..................................................................................................................................... 14
Figure 48: Network Menu Two.....................................................................................................................................14
Figure 49: Network Menu Four ....................................................................................................................................14
Figure 50: Network Menu Five..................................................................................................................................... 15
Figure 51: Network Menu Six....................................................................................................................................... 15
Figure 52: Remote Alarms Query Menu....................................................................................................................... 15
Figure 53: Network Menu Seven..................................................................................................................................15
Figure 54: Network Menu Eight....................................................................................................................................15
Figure 55: Commission Menu Three............................................................................................................................ 15
Figure 56: Configure Menu..........................................................................................................................................15
Figure 57: Memory Check Message............................................................................................................................. 15
Figure 58: Commission Menu Three............................................................................................................................ 15
Figure 59: Mini Network............................................................................................................................................... 16
Figure 60: Master/Slave Network................................................................................................................................. 17
Figure 61: RS-485 High Integrity Network....................................................................................................................17
Tables
Table 1: Shared Zone Configuration..............................................................................................................................5
Table 2: Panel Programming Options..........................................................................................................................16

D8024, D9024, D10024 Analog Fire Alarm Control Panels
D8024, D9024, D10024 Networking Guide
34377C 06/99 Page 3© 1999 Radionics. All rights reserved.
Networking Guide
1.0 Notice
•The material and instructions covered in this manual have been carefully checked for accuracy and are presumed
to be reliable. However, the manufacturer assumes no responsibility for inaccuracies and reserves the right to
modify and revise this document without notice.
•These instructions are for connecting, programming, and operating D8024, D9024 and D10024 Fire Alarm Control
Panels (FACP) in a network controlled by a D8024, D9024 or D10024 master panel. See the D8024 Installation
Guide (P/N: 38728) and the D8024 Operator’s Guide (P/N: 35394), or the D9024, D10024 Installation Guide
(P/N: 74-07649-000) and the D9024, D10024 Operator’s Guide (P/N: 74-07661-000) for specific information on
individual D8024, D9024 and D10024 Fire Alarm Control Panel Systems.
2.0 Warnings and Cautions
These instructions contain procedures to follow in order to avoid personal injury and damage to
equipment.
3.0 FCC Notices
Part 15
•This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15
of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a
commercial installation. This equipment generates, uses and can radiate radio frequency energy, and, if not
installed in accordance with the instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by turning the equipment on and off,
the user is encouraged to try to correct the interference by one or more of the following measures:
1. Reorient or relocate the receiving antenna.
2. Increase the separation between the equipment and the receiver.
3. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
4. Consult the dealer or an experienced radio/TV technician for help.
4.0 UL/NFPA Notices
•UL listed for NFPA 72, Local.
•All references to NFPA and related requirements are based upon compliance with the 1993 edition of NFPA 72,
National Fire Alarm Code. Since installation specifications are nearly always based upon a specific edition of a
standard that has been legally adopted by the Authority Having Jurisdiction (AHJ), earlier editions of NFPA
standards will generally apply. Consult with the appropriate AHJ for confirmation.

D8024, D9024, D10024 Networking Guide
© 1999 Radionics. All rights reserved. Page 434377C 06/99
5.0 Network Installation
•All panels must be D8024, D9024 or D10024 Fire Alarm Control Panels. The network wiring is supervised. A fault
in the network wiring results in a warning message. In a fault condition on the network wiring each panel will
operate as a stand-alone unit.
•In a shared zone network, notification appliance peripherals associated with a specific zone can be
attached to any panel on the system.
Notification appliances connected to one panel that are associated with detection devices on
other panels will not activate in a network fault condition.
5.1 Serial Port Assignment and Function
•Serial network data communications take place using D9051 RS-485 Bus Modules attached to Serial Port C on the
Panel Control Module.
Figure 1: D9051 Network Connections
5.2 System Installations
•The panels are wired in series to an NFPA Class B, Style 3.5 signaling line circuit on the appropriate RS-485 bus.
The RS-485 terminals on the D9051 Module are polarity sensitive. The channels are marked A and B, and data
cables should be connected A to A and B to B. Cross wiring between channels will result in corrupted data but will
not damage equipment.
•Use shielded twisted pair wiring such as the Data Grade Cable D293, Beldon 8670 two-core twisted pair, or non-
shielded 18 gauge cable from Atlas, Guardian Sound & Security, or their equals. To avoid data corruption, route
cables so that they do not run next to other cables.
•The total length of the data cables between the two end panels must not exceed 3,935 ft. (1,199 m) per channel.

D8024, D9024, D10024 Networking Guide
34377C 06/99 Page 5© 1999 Radionics. All rights reserved.
6.0 Shared Zone Network
•This system is usually an installation in a single site or building. Multiple panels are networked together using
common zones. This configuration can have up to 99 zones with 2,520 addressable points. See Table 1.
•In the Shared Zone Network, up to four D8024, D9024 and/or D10024 panels are networked together with one
panel designated to act as the Master.
Table 1: Shared Zone Configuration
Panel Number of Zones Max. No. Addressable Points Max. No. Outputs Notification Appliances/Relays
D8024 20 252 20
D9024 40 1,512 400
D10024 40 expandable to 99 2,520 400
System
ResetTrouble
Silence
Letters
Numbers
Alarm
Silen ceManu al
Alarm ENTERYES
Keyword
NO
ALARM
TROUBLE
ALARM
TROUBLE
ALARM
TROUBLE
ALARM
TROUBLE
ALARM
TROUBLE
ALARM
TROUBLE
TROUBLE
ALARM
ALARM
TROUBLE
Numbers
Letters
Alarm
Sile nce
Trouble
Silence
System
ResetAlarm
ManualENTER
Keyword
YESNO
Letters
Numbers
TROUBLE
ALARM
TROUBLE
ALARM
TROUBLE
ALARM
ALARM
TROUBLE
Sile nce
Alarm
SystemSilence
Trouble
ResetManual
Alarm ENTER
Keyword
YESNO
Letters
Numbers
TROUBLE
ALARM
TROUBLE
ALARM
TROUBLE
ALARM
ALARM
TROUBLE
Silence
Alarm
SystemSilence
Trouble
ResetManual
Alarm ENTER
Keyword
YESNO
Figure 2: Shared Zone Network
•These systems share common zones (max. 20, 40, 80, or 99, depending on the panel types) and act as one large
system.
6.1 Shared Zone Network Operation
6.1.1 Alarm Conditions
•The location text message of the first alarm on the system will be displayed on the LCD of the master panel
and all of the sub panels on the network.
•The location text message from subsequent alarms will appear only on the master panel and on the panel of
origin. The local message will override any global message on the panel of origin.
•All sub panels will automatically scroll through the first four local alarm text messages.
•The Master panel will automatically scroll through the first four global alarm text messages, regardless of
origin.
•The zonal fire LED indications on all panels will illuminate to show all zones in alarm on the total system.
•The outputs and notification appliances will follow the programmed zonal settings. (All outputs from any panel that
are programmed to a particular zone will perform as programmed when a fire is detected in that zone, regardless of
which panel detects the fire.)
•In a shared zone network, notification appliances associated with a specific zone can be attached to any
panel on the system.
The maximum number of outputs (notification appliances/ relays) is 100 per panel.
Notification appliances connected to one panel that are associated with detection devices in
alarm on other panels will not activate in a network wiring fault condition.

D8024, D9024, D10024 Networking Guide
© 1999 Radionics. All rights reserved. Page 634377C 06/99
6.1.2 In a Fault Condition
•Alarm text messages override fault text messages.
•The master panel scrolls through the first four network faults.
•The master panel LEDs indicate all fault conditions on the network.
•Local panels scroll through the first four local faults
•Local panel LEDs indicate all zones in fault condition on that panel.
•The operator may use the control keys on any panel to respond to alarm and fault conditions.
D8024
LEDDisplayControlKeys
SystemTrouble
ALARM
TroubleSilenced
PointBypassed
SprinklerSupervisory
SounderFault
Relays Bypassed
EarthFault
CPUReset
SoundersDisabled
SoundersSilenced
ACPower
FireDrill
Alarm Silence
TroubleSilence
SystemReset
D9024,D10024
12345678
System
ResetTrouble
Silence
9 10 11 12 13 14 15 16 17 18 19 20
Letters
Numbers
Alarm
SilenceManual
Alarm ENTERYES
Keyword
NO
ALARM
TROUBLE
ControlKeys LEDDisplay
Zone LED’s
Alphanumeric
Keys
Alphanumeric
Display
Figure 3: Front Panel Displays
6.1.3 Repeaters and Peripherals
•Repeater panels will mimic the text information on the LCD of the panel to which they are connected.
6.2 Shared Zone Network Programming
•Follow the instructions in the Analog Fire Alarm Control Panels Programming Guide (P/N: 38789) to set up and
configure individual panels. To simplify the network programming procedure, the panels may be set up so that all
programming is done from the master panel. To do this, run the setup sequence, Section 7.2. of the Analog Fire
Alarm Control Panels Programming Guide, on each panel and set the Memory Lock Check, Section 7.2 “Memory
Lock Check”., to [No]. Leave the memory lock switch in the unlocked position. After completing the Master Panel
Network Programming use the procedure outlined at the beginning of Section 6.2 “Slave Panel Programming,
Shared Zone Network,” of this guide to program the slave panels.
6.2.1 Master Panel Programming, Shared Zone Network
•Press the [>] key to display the Operator’s Menu, Main Level.
Figure 4: Main Menu

D8024, D9024, D10024 Networking Guide
34377C 06/99 Page 7© 1999 Radionics. All rights reserved.
•Select option one 1) Commission, by pressing the [1] key. The display prompts, “Please key in your password”
[Active]1)Commission 2)Test3)Time[1]
4)Enable5)Disable6)Print7)View
1)CONFIGUREYES)MoreOptions[A]
2)INSPECT3)NORMALOPERATION
1)Time/Date2)ProgramIntegrity[A]
3)PowerSupplies4)Modifylevel2code
1)DayModes2)Setup options3)Network[A]
4)Devices5)TalktoSlave
Press the "1"Key
Press the "YES"Key
Press the "YES"Key
Press the "3"Key
EnterPass Code
Figure 5: Path through Commission Menus to Network
•Enter the Level Three Pass Code (9898). The display shows the first of the three Commission Menus. Press [Yes]
twice to page to Commission Menu Three. Press [3] to enter Network options.
•Unlock the memory using the Memory Lock Switch. The memory must be locked at the end of the programming
session. The panel will not allow a reset unless the memory is locked.
•Press [3]. The panel displays Network Menu One.
Figure 6: Network Menu One
•Enter the Network address for the Master Panel. This is a number from one to 20.
•In messages on the LCD, the panel software will identify the first slave panel as Slave CPU 1, the second
slave panel as Slave Panel 2 and so on.
•Avoid confusion between network addresses and panel identifications by giving the master panel a unique
identification number (i.e. 10).
•The panel displays Network Menu Two.
Figure 7: Network Menu Two
•Enter the number of slave processors (1 to 3 in a shared zone network). The panel displays Network Menu Three.
Figure 8: Network Menu Three
•Enter the address for the first slave CPU. Network Menu Three will change to prompt for the address of the next
slave CPU until the number of slave processors entered in Network Menu Two are identified. The panel then
displays Network Menu Four.
Figure 9: Network Menu Four
•Press [Yes] if the master panel is not connected to a modem. If a modem is connected to Port B or Port C of the
master panel, press [Change] to alter the statement to True and press [Enter]. The panel displays Network Menu
Five.
Figure 10: Network Menu Five

D8024, D9024, D10024 Networking Guide
© 1999 Radionics. All rights reserved. Page 834377C 06/99
•Press [Yes]. The panel displays Network Menu Six.
Figure 11: Network Menu Six
•If necessary, use the [Change] Key to set Peer to Peer to True and press [Yes]. The panel displays Network Menu
Seven.
Figure 12: Network Menu Seven
•Press [Yes]. The panel displays Network Menu Eight.
Figure 13: Network Menu Eight
•Press [Yes]. The panel displays Commission Menu Three.
1)DayModes2)Setup options3)Network[10]
4)Devices5)TalktoSlave
Figure 14: Commission Menu Three
6.2.2 Slave Panel Programming, Shared Zone Network
•Program each of the slave panels using option 3) Network on the Commission Menu Three. If the Master Panel
and the slave CPU(s) are set up as outlined in section 6.2 of this guide with the memory lock switch left in the
unlocked position, all programming may be done from the Master Panel. This section outlines that procedure.
After completing slave panel programming, run the setup program at each panel. Set the
memory lock check to Yes and lock the memory if you have completed all programming at this
time.
•The slave CPU(s) may be programmed individually using the control keys on each panel to access Commission
Menu Three. Select Option 4) Talk to Slave from Commission Menu Three. The Panel queries for the CPU
number.
Figure 15: Master-to-Slave Menu One
•In messages on the LCD, the panel software will identify the first slave panel as Slave CPU 1, the second
slave panel as Slave Panel 2 and so on.
•Enter 01 to talk to CPU1. The panel displays Commission Menu One.
Figure 16: Commission Menu One
CPU1 is now being programmed from the master panel. The menu displayed on the master
panel is Commission Menu One of Slave Panel One (CPU1). The display on both panel displays
is identical and programming may be performed from either or both panels.
•Select option 1) Commission. The panel prompts for the password. Enter the Level Three Pass Code (9898).
Press [Yes] twice to reach Commission Menu Three (on CPU1). The panel displays Commission Menu Three.
1)DayModes2)Setup options3)Network[10]
4)Devices5)TalktoSlave
Figure 17: Commission Menu Three

D8024, D9024, D10024 Networking Guide
34377C 06/99 Page 9© 1999 Radionics. All rights reserved.
•Select option 3) Network. The Panel displays Network Menu One.
Figure 18: Network Menu One
•Enter the Network address for CPU1. This is a number from one to 20.
•In messages on the LCD, the panel software will identify the first slave panel as Slave CPU 1, the second
slave panel as Slave Panel 2 and so on.
•Avoid confusion by giving each slave panel the same identifier as the panel software: e.g. assign CPU1 the network
address one (1). Enter a number and press [Enter]. The panel displays Network Menu Two.
Figure 19: Network Menu Two
•Press [0] and press [Enter]. The panel displays Network Menu Four.
Figure 20: Network Menu Four
•Press [Yes] if CPU1 is not connected to a modem. If a modem is connected to Port B or Port C of CPU1, press
Change to alter the statement to TRUE and press [Enter]. The panel displays Network Menu Five.
Figure 21: Network Menu Five
•Press [Yes]. The panel displays Network Menu Six.
Figure 22: Network Menu Six
•If necessary, use the [Change] Key to set Peer to Peer to True and press [Yes]. The panel displays Network Menu
Seven.
Figure 23: Network Menu Seven
•The Port B Protocol for the slave panels in a shared zone network must be set to 0. Press [Yes]. The panel
displays Network Menu Eight.
Figure 24: Network Menu Eight
•Press [Yes]. The panel displays Commission Menu Three.
1)DayModes2)Setup options3)Network[10]
4)Devices5)TalktoSlave
Figure 25: Commission Menu Three
•Press [No] to return to the Configure Menu.
Figure 26: Configure Menu

D8024, D9024, D10024 Networking Guide
© 1999 Radionics. All rights reserved. Page 10 34377C 06/99
•Enter 3) NORMAL OPERATION. The display shows the Memory Check Message.
Figure 27: Memory Check Message
•If the Master Panel and the slave CPU(s) are set up as outlined in section 6.2.2, press [3] for Normal Operation a
second time to return to Commission Menu One. Press [Reset]. This closes the Network process for CPU1 and
returns the display returns to Commission Menu Three for the Master Panel.
1)DayModes2)Setup options3)Network[10]
4)Devices5)TalktoSlave
Figure 28: Commission Menu Three
•Repeat the network programming procedure (see section 6.2.2 “Slave Panel Programming, Shared Zone Network”)
for each slave panel. After completing network programming for the last slave panel press [No] from Commission
Menu Three and return to Commission Menu Three for the Master Panel.
•Press [No] to return to the Configure menu. Press [3] for NORMAL OPERATION to return to the Operator’s Menu,
Main Level.
•Run the Set Up procedure as described in section 7.2. of the Analog Fire Alarm Control Panels Programming Guide
and set the Memory Lock Check (section 7.2 “Memory Lock Check”.) to [Yes] on the Master Panel and each Slave
Panel.
7.0 Report and Control Network
•The Report and Control Network links the individual panels to a master panel for reporting and control. Up to ten
D8024, D9024 and/or D10024 panels may be networked together in a Report and Control Network with one
dedicated panel designated to act as the Master.
7.1 Report and Control Network Operation
7.1.1 Alarm Conditions
•The LCDs of the Master Panel and the Panel of Origin display the location text message of the first alarm on the
system. Other panels in the network do not acknowledge the alarm condition and continue normal polling.
•The location text message from subsequent alarms appears on the Panel of Origin and the Master Panel.
•The relay outputs and notification appliances connected to the panel of origin will follow programmed zonal settings
for their individual units.
•The [Alarm Silence] key on the Panel of Origin or the Master Panel deactivates and reactivates notification
appliances. The Panel of Origin key controls notification appliances connected to that panel. The Master Panel key
controls all notification appliances in alarm on the network.
•The Master Panel will automatically scroll through the first four alarm text messages, regardless of origin.
•The LED zone indicators on the panel of origin will illuminate to show all zones in alarm on that panel.
•The [Fire Drill] (Manual Alarm) key on the Master Panel activates only the notification appliances attached to master
panel.
7.1.2 System Reset from Alarm Conditions
•The [System Reset] key on the Panel of Origin resets that panel. The [System Reset] key on the Master Panel
resets all the panels on the network.
•After the condition is cleared, the panel of origin may be reset from the Panel of Origin or from the Master Panel. If
the reset is from the panel of origin, the alarm message on the LCD display of the Master Panel and the LED alarm
indications on the Master Panel remain until the Master Panel is reset.

D8024, D9024, D10024 Networking Guide
34377C 06/99 Page 11 © 1999 Radionics. All rights reserved.
7.1.3 Fault Condition
•Alarm text messages override fault text messages.
•The text display on the Panel of Origin scrolls through the first four fault messages on that panel.
•The text display on the Master Panel scrolls through the first four network fault messages
Figure 29: Master Panel Fault Condition Display
•This display on the Master Panel indicates that CPU3 has a fault condition -an open input circuit at address 20 on
polling loop one, a manual call point.
•A fault condition results in a System Trouble LED at the panel of origin and at the Master Panel. The Master
Panel’s System Trouble LED indicates a fault condition on the network.
•The [Trouble Silence] key on the Panel of Origin silences the buzzer at that panel, but not at the Master Panel.
•The [Trouble Silence] key at the Master Panel silences Master Panel buzzer. The System Trouble and Trouble
Silenced LEDs on all panels in a fault condition remain lit.
•A fault in the RS-485 link results in a panel buzzer at the Master Panel and an LCD display indicating the CPU link
that is lost. See Figure 30.
Figure 30: RS-485 Link Message
•This display indicates that network connection is lost between CPU1 and the rest of the network. The remaining
panels continue to operate independently.
•The location text message of the first fault on the system will be displayed on the LCD of the Master and the panel
of origin.
•The [System Reset] key on the Master Panel resets all the panels on the network.
•The master panel scrolls through the first four network faults.
•Local panels scroll through the first four local faults
•Local panel LEDs indicate all zones in fault condition on that panel.
7.1.4 Event Log
•The panel of origin event log performs identically to a stand-alone installation.
•The Master Panel logs network events. The Master Panel event log display indicates the sub panel associated with
each event. See Figure 31.
Figure 31: Master Panel Event Log Display
•In Figure 31, Entry 57 occurred at 13:38 on March 12th on CPU1. The alarm was in response to a signal from the
device at address 20 of polling loop one.
7.1.5 D9070 Controllers and D9069 Annunciators
•The displays on these devices mimic the text information on the LCD of the panel to which they are connected.
The maximum number of outputs (notification appliances/relays) is 100 per panel.

D8024, D9024, D10024 Networking Guide
© 1999 Radionics. All rights reserved. Page 12 34377C 06/99
7.2 Report and Control Network Programming
•Follow the instructions in the Analog Fire Alarm Control Panels Programming Guide (P/N: 38789) to set up and
configure individual panels. To simplify the network programming procedure, the panels may be set up so that all
programming is done from the master panel. To do this, run the setup sequence (section 7.2 of the Analog Fire
Alarm Control Panels Programming Guide) on each panel and set the Memory Lock Check (section 7.2 “Memory
Lock Check”) to [No]. Leave the memory lock switch in the unlocked position. After completing the Master Panel
Network Programming, use the procedure outlined in Section 7.2.2 “Slave Panel Programming, Report and Control
Network” to program the slave panels.
7.2.1 Master Panel Programming, Report and Control Network
•Press the >key to display the Operator’s Menu, Main Level.
Figure 32: Main Menu
•Select option one 1) Commission, by pressing the 1key. The display prompts, “Please key in your password”.
[Active]1)Commission 2)Test3)Time[1]
4)Enable5)Disable6)Print7)View
1)CONFIGUREYES)MoreOptions[A]
2)INSPECT3)NORMALOPERATION
1)Time/Date2)ProgramIntegrity[A]
3)PowerSupplies4)Modifylevel2code
1)DayModes2)Setup options3)Network[A]
4)Devices5)TalktoSlave
Press the "1"Key
Press the "YES"Key
Press the "YES"Key
Press the "3"Key
EnterPass Code
Figure 33: Path through Commission Menus to Network
•Enter the Level Three Pass Code (9898). The display shows the first of the three Commission Menus. Press[ Yes]
twice to page to Commission Menu Three. Press [3] to enter Network options.
•Unlock the memory using the Memory Lock Switch. The memory must be locked at the end of the programming
session. The panel will not allow a reset unless the memory is locked.
•Press [3]. The panel displays Network Menu One.
Figure 34: Network Menu One
•Enter the Network address for the Master Panel. This is a number from one to 20.
•In messages on the LCD, the panel software will identify the first slave panel as Slave CPU 1, the second
slave panel as Slave Panel 2 and so on.
•Avoid confusion between network addresses and panel identifications by giving the master panel a unique
identification number (i.e. 10). The panel displays Network Menu Two.
Figure 35: Network Menu Two

D8024, D9024, D10024 Networking Guide
34377C 06/99 Page 13 © 1999 Radionics. All rights reserved.
•Enter the number of slave processors (1 to 9 in a report and control network). The panel displays Network Menu
Three.
Figure 36 Network Menu Three
•Enter the address for the first slave CPU. Network Menu Three will change to prompt for the address of the next
slave CPU until the number of slave processors entered in Network Menu Two are identified. The panel then
displays Network Menu Four.
Figure 37: Network Menu Four
•Press [Yes] if the master panel is not connected to a modem. If a modem is connected to Port B or Port C of the
master panel, press [Change] to alter the statement to TRUE and press [Enter]. The panel displays Network Menu
Five.
Figure 38: Network Menu Five
•If necessary, use the [Change] key to change the selection to False. Press [Yes]. The panel displays Network
Menu Six.
Figure 39: Network Menu Six
•If necessary, use the [Change Key to set Peer to Peer to False and press [Yes]. The panel displays the Remote
Alarms Query Menu.
Figure 40: Remote Alarms Query Menu
•The setting of Remote Alarms determines whether an alarm condition originating at another panel is annunciated
on this LCD display. If necessary, use the [Change] Key to set Remote Alarms to True and press [Yes]. The panel
displays Network Menu Seven.
Figure 41: Network Menu Seven
•Port B Protocol should be set to zero. Press [Yes]. The panel displays Network Menu Eight.
Figure 42: Network Menu Eight
•If necessary, use the [Change] key to select Global and press [Yes]. The panel displays Commission Menu Three.
1)DayModes2)Setup options3)Network[10]
4)Devices5)TalktoSlave
Figure 43: Commission Menu Three

D8024, D9024, D10024 Networking Guide
© 1999 Radionics. All rights reserved. Page 14 34377C 06/99
7.2.2 Slave Panel Programming, Report and Control Network
•The slave CPU(s) may be programmed individually using the control keys on each panel to access Commission
Menu Three. Press [3] for option 3) Network on the Commission Menu Three. If the Master Panel and the slave
CPU(s) are set up as outlined in section 6.2 with the memory lock switch left in the unlocked position, all
programming may be done from the Master Panel. This section outlines that procedure.
After completing slave panel programming, run the setup program at each panel. Set the
memory lock check to Yes and lock the memory if you have completed all programming at this
time.
•Select Option 4) Talk to Slave from Commission Menu Three. The Panel queries for the CPU number.
Figure 44: Master-to-Slave Menu One
•In messages on the LCD, the panel software will identify the first slave panel as Slave CPU 1, the second
slave panel as Slave Panel 2 and so on.
•Enter 01 to talk to CPU1. The panel displays Commission Menu One.
Figure 45: Commission Menu One
CPU1 is now being programmed from the Master Panel. The menu displayed on the Master
Panel is Commission Menu One of Slave Panel One (CPU1). The display on both panel displays
is identical and programming may be performed from either or both panels.
•Select option 1) Commission. The panel prompts for the password. Enter the Level Three Pass Code (9898).
•Press [Yes] twice to reach Commission Menu Three (on CPU1). The panel displays Commission Menu Three.
1)DayModes2)Setup options3)Network[10]
4)Devices5)TalktoSlave
Figure 46: Commission Menu Three
•Select option 3) Network. The Panel displays Network Menu One.
Figure 47: Network Menu One
•Enter the Network address for CPU1. This is a number from one to 20.
•In messages on the LCD, the panel software will identify the first slave panel as Slave CPU 1, the second
slave panel as Slave Panel 2 and so on.
•Avoid confusion by giving each slave panel the same identifier as the panel software: e.g. assign CPU1 the network
address one (1).
•Enter a number and press [Enter]. The panel displays Network Menu Two.
Figure 48: Network Menu Two
•Press [0] and press [Enter]. The panel displays Network Menu Four.
Figure 49: Network Menu Four

D8024, D9024, D10024 Networking Guide
34377C 06/99 Page 15 © 1999 Radionics. All rights reserved.
•Press [Yes] if CPU1 is not connected to a modem. If a modem is connected to Port B or Port C of CPU1, press
[Change] to alter the statement to True and press [Enter]. The panel displays Network Menu Five.
Figure 50: Network Menu Five
•If necessary, use the [Change] key to change the selection to False. Press [Yes]. The panel displays Network
Menu Six.
Figure 51: Network Menu Six
•If necessary, use the [Change] Key to set Peer to Peer to False and press [Yes]. The panel displays the Remote
Alarms Query Menu.
Figure 52: Remote Alarms Query Menu
•Set Remote Alarms to False on all sub panels. Press [Yes]. The panel displays Network Menu Seven.
Figure 53: Network Menu Seven
•The Port B Protocol for the slave panels in a Report and Control network must be set to 0. Press [Yes]. The panel
displays Network Menu Eight.
Figure 54: Network Menu Eight
•If necessary, use the [Change] key to select Local and Press [Yes]. The panel displays Commission Menu Three.
1)DayModes2)Setup options3)Network[10]
4)Devices5)TalktoSlave
Figure 55: Commission Menu Three
•Press [No] to return to the Configure Menu.
Figure 56: Configure Menu
•Enter 3) NORMAL OPERATION. The display shows the Memory Check Message.
Figure 57: Memory Check Message
•If the Master Panel and the slave CPU(s) are set up as outlined in section 6.2 of this manual, press [3] for Normal
Operation a second time to return to Commission Menu One. Press [Reset]. This closes the Network process for
CPU1 and returns the display returns to Commission Menu Three for the Master Panel.
Figure 58: Commission Menu Three
•Repeat the network programming procedure (see p.8, “6.2.2 Slave Panel Programming, Shared Zone Network”)
for each slave panel. After completing network programming for the last slave panel press [No] from Commission
Menu Three and return to Commission Menu Three for the Master Panel.

D8024, D9024, D10024 Networking Guide
© 1999 Radionics. All rights reserved. Page 16 34377C 06/99
•Press [No] to return to the Configure menu. Press [3] for NORMAL OPERATION to return to the Operator’s Menu,
Main Level.
•Run the Set Up procedure as described in section 7.2. of the Analog Fire Alarm Control Panels Programming Guide
and set the Memory Lock Check (section 7.2 “Memory Lock Check”) to [Yes] on the Master Panel and each Slave
Panel.
8.0 Panel Programming Options
Table 2: Panel Programming Options
Protocol Number Description Application
0Default Network Option Connection to a Master Panel
Connection to a Graphics PC
20 Fire Zone Pager
21 Fire Zone + Text Pager
30 PC Interface Two-way interface with acknowledgment
31 PC Interface One-way interface
9.0 Networking Schematics
9.1 Mini Network
*TheD9057 4-OutputRelay Modulewill beavailableinafuturerelease.
**TheD9063 8-InputModulewill beavailableinafuturerelease.
PC
Dotmatrix
printer
D9075
RS-232/RS-485
Converter***
120VAC
D9050 FrontPanelPrinter
PortB
D9051
RS-485
BusModule
PortC
D9051
RS-485
BusModule
PortC
D9051
RS-485
BusModule
D905440-Zone
LEDExpansionBoard
(Zones41-80)
D10024 Base
Slave 1
D10024 Base
Slave 2
D10024 Base
Slave 3
PortC
D9051
RS-485
BusModule
PortC
D9051
RS-485
BusModule
PortCPortC
PortD
D9051
RS-485
BusModule
D9072 4-Output
NACModule
(Addr.1-15)
24
VDC 24VAuxiliary
PowerSupply
24VDC
D9063 8-Output
InputModule**
(Addr.1-126)
D90574-Output
RelayModule*
(Addr.1-31)24VAuxiliary
PowerSupply
24VDC
D9069
FireSystem
Annunciator
D9078LED
DriverModule
D10024 Base
24VDC
RS-485 max.distance:3,937 ft (1,200 m)
24VDC
D9070
FireSystem
Controller
Compatibledevicesforuse
inthe mini-network
***TheD9075 RS-232/RS-485 Converterwill beavailableinafuturerelease.
24
VDC
Figure 59: Mini Network

© 1999 Radionics, a division of Detection Systems, Inc.
® The Radionics logo is a registered trademark of Radionics,
PO Box 80012, Salinas, CA 93912-0012, USA
All rights reserved.
Customer Service: (800) 538-5807
9.2 Master/Slave
•A dedicated Master (MCU) can control up to ten slave D8024, D9024 or D10024 FACPs.
•Each slave D8024, D9024 and D10024 slave FACPs can be configured with a maximum number of D9067 Polling
Circuit Modules.
•A Master panel can also function as a fire panel by installing polling circuit modules.
•All networks can be configured as shared zone or report and control systems.
•A single twisted pair cable is required between control panels for networking.
PC
Printer
MasterSlave 1Slave 7
D9024 Master
ControlUnit
D9061
Graphics
Software
and
Interface
D9051
RS-485
Module
PORTC
D9051
RS-485
Module
PORTC
D9051
RS-485
Module
PORTC
D9051
RS-485
Module
PORTB
Cabletype:Beldon 8760
screened twisted pairorequivalent
D9024 (1to5zones)D9024
D9051 RS-485 max.distance:3,937 ft. (1,200 m)
Figure 60: Master/Slave Network.
9.3 RS-485 High Integrity Network
Cabletype:Beldon 8760
screened twisted pairorequivalent
Max.distancebetween nodes:0.9mi.(1.5km)
PC
Printer
D9061
Graphics
Software
D9024 MasterControlUnit
D9051
RS-485
Module
PORTC
D9051
RS-485
Module
PORTB
D9073 High Integrity
RS-485 Module
24VDC Tap
Out InD9073 High Integrity
RS-485 Module
24VDC Tap
Out In
D9051
RS-485
Module
PORTC
D9073 High Integrity
RS-485 Module
24VDC Tap
Out In
D9051
RS-485
Module
PORTC
Slave Panel2
D9073 High Integrity
RS-485 Module
24VDC Tap
Out In
D9051
RS-485
Module
PORTC
Slave Panel12
D9024 1to5zones
Slave Panel1
Figure 61: RS-485 High Integrity Network