Honeywell Gamewell Flex 402 User manual

Flex 402 Two-Zone FACP CS-2402 09/01/06 Page 1 of 2
Description
The Gamewell Flex 402 Fire Alarm
Control Panel brings the latest in mi-
croprocessor technology to conven-
tional fire controls. The Flex 402 is
compatible with the new i³ ™smoke
detectors from System Sensor, and
providesadvancedfeaturesincluding
driftcompensation,maintenancealert,
andfreezewarning.Automaticsynchro-
nizationofaudio/visualdevices is pro-
vided,selectable forthreemanufactur-
ers’ protocols. The NAC protocol in-
cludes the ability, using a single pair of wires, to silence audible devices while
strobes continue to flash.
The Flex 402 is also compatible with conventional input devices such as two-
andfour-wire smoke detectors,pullstations, waterflowdevices,tamper switches
andothernormally-opencontactdevices.
Operation
The activation of a compatible smoke detector or any normally-open fire alarm
initiatingdevicewill:activateaudibleandvisualsignalingdevices, illuminate an
indicatingLED,sound the piezo sounder at the FACP,activatethe FACPalarm
relay,and operate an optionalmodulewhichnotifies a remote station or initiates
anauxiliary control function.
i³™Technology Features
• Drift compensation automatically adjusts detector sensitivity and increases
resistance to false alarms caused by dust accumulation.
• The maintenance alert LEDs (per zone) warn of excessive dirt accumulation,
preventing false alarms.
• Detector sensitivity is automatically measured. The twice-yearly test require-
ments of NFPA 72 (7-3.2.1) are met without using a ladder or test meter.
• The wireless handheld sensitivity meter eliminates the need for voltmeters,
magnets, or a physical connection to the detector. The reader displays sensi-
tivity in terms of percent-per-foot obscuration and provides text status indica-
tion.
• The supervisory LED (per zone) provides a warning if a detector senses tem-
peratures approaching freezing.
• Special test protocol and LED indication allow a quick test of all detectors —
without a ladder.
• Electronic heat-sensing element provides thermal detection in addition to pho-
toelectronic smoke detection.
Features
• Two Style B(Class B) InitiatingDevice
Circuits (IDCs).
• OneStyleY(ClassB)NotificationAppliance
Circuit (NAC).
• 24 VDC.
•NACsynchronizationfeatures:
– ProvidessynchronizationofstandardANSI
audiblesignalsasrequiredbyNFPA72
(3-8.4.1.2.3).
– ProvidessynchronizationofADAcompliant
strobesperNFPA72(4-4.4.1).
– SelectableforSystemSensor,Wheelock,
andGentexprotocols.
– SelectiveSilencefeatureallowsmanual
silencingofhornswhilestrobescontinueto
flashonthesameNAC.
• SilentorAudibleWalkTestoperationmode
commandedfromthefrontkeypad,with
automaticreturntonormalafteronehourof
inactivity.
• Alarmverificationselectableperzone.
• Eachzonemaybeprogrammedfor
supervisoryorfire;eachzonehasseparate
red and yellow LEDs.
• Disableswitchesprovidedforeachzone.
•NACsprogrammablefor:SilenceInhibit,Auto
Silence,StrobeSynchronization,Selective
Silence(horn/strobemute),Temporalor
Steadysignal,Silenceableor
Nonsilenceable.
• Form-CAlarmandTroublerelays.
• 3.0ampstotalusablecurrent.
• Optionaldresspanel(P/NDP-FLEX).
• Piezosounderforalarm,trouble,supervisory,
andmaintenance.
•Controlbuttons:ACK(Acknowledge),Alarm
Silence,Reset,Walktest,
ZoneEnable/Disable(oneperzone).
•LEDindicators:FireAlarm(oneperzone),
Supervisory(oneperzone),Trouble(one
perzone),Maintenance(oneperzone),
AC Power, NAC Disable, Zone Disable,
NACFault,SystemTrouble,PowerTrouble,
Walktest,AlarmSilence,EarthFault(on
circuitboard),BatteryFault(oncircuitboard),
ChargerFault(oncircuitboard).
Listings
Listingsandapprovalsbelowapplytothe
basicFlex402panel.Insomecases,certain
modulesmaynotbelistedbycertain
approvalagencies,orlistingmaybein
process.Consultfactoryforlatestlisting
status.
• ULListed:fileS521.
• CSFMapproved:file7165-1288-180.
• MEAapproved:file366-04-E.
Flex 402
Two-Zone Fire Alarm Control Panel
g2402ph1.jpg
Flex 402 Two-Zone FACP CS-2402 09/01/06
Page 2 of 2
Specifications and wiring information are provided for information only and are
believed to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation.
For more information, contact Gamewell-FCI.
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Specifications
AC power, TB8
120 VAC, 50/60 Hz, 2.3 A.
Wire size: minimum 14 AWG (2.0 mm²)
with 600 V insulation.
Battery (sealed lead-acid only), J8
Maximum charging circuit: normal flat
charge 27.6 VDC @ 0.8 A.
Maximum battery charger capacity:
18 AH battery. Two 7 AH batteries can
be housed in the FACP cabinet. Larger
batteries require a separate battery
box such as the BB-17F.
Initiating device circuits, TB3
Alarm zones 1&2. Power-limited circuitry.
Operation: all zones Style B (Class B).
Normal operating voltage: nominal 22
VDC. Alarm current: 15 mA minimum.
Standby current: 4 mA.
Short circuit current: 40 mA maximum.
Maximum loop resistance: 100 ohms.
End-of-line resistor: 4.7K ohm, 1/2
watt (P/N 71252).
Notification appliance circuits, TB2
One NAC on Flex 402. Power-limited
circuitry.
Normal operating voltage: nominal 24
VDC.
Maximum signaling current: 2.5 A total
with standard transform.
End-of-line resistor: 4.7K ohm, 1/2
watt (P/N 71252).
Form-C relays
Trouble relay TB5 (fail-safe). Alarm
relay TB6.
Contact ratings: 2.0 A @ 30 VAC
(resistive).
Auxiliary outputs
Resettable power, TB1
Power-limiting circuitry.
Operating voltage: nominal 24 VDC.
Maximum available current: 500 mA,
appropriate for powering four-wire
smoke detectors. Note: Total current
for resettable power and one NAC
must not exceed 3 A for the Flex 402.
Cabinet dimensions
Door: 15.342" (38.97 cm) high x 14.677"
(37.28 cm) wide x 0.375" (0.95 cm)
deep. Backbox: 15.0" (38.10 cm) high
x 14.5" (36.83 cm) wide x 3.0" (7.62 cm)
deep.
Backbox Mounting
The cabinet can be surface-mounted. The door is removable during installa-
tion by opening and lifting it off the hinges. The cabinet mounts using two
key slots at the top of the backbox and two additional 0.250" diameter holes
at the bottom.
Ordering Information
F402 Two-zone conventional FACP.
BB-17F Battery box, required to house two batteries greater than 7
AH, to a maximum of 18 AH.
DP-FLEX Dress panel.
TR-1-R Trim ring for semi-flush mounting.
52194 Flex 402 Installation and Maintenance Manual.
i³™ is a trademark and Gamewell® is a registered trademark of Honeywell International Inc.

This manual suits for next models

1

Other Honeywell Control Panel manuals

Honeywell Notifier AFP-3030 User manual

Honeywell

Honeywell Notifier AFP-3030 User manual

Honeywell TotalZone TZ-4 Operation manual

Honeywell

Honeywell TotalZone TZ-4 Operation manual

Honeywell MM3-MASTERTROL MM-3 Technical manual

Honeywell

Honeywell MM3-MASTERTROL MM-3 Technical manual

Honeywell nfs2-3030 Owner's manual

Honeywell

Honeywell nfs2-3030 Owner's manual

Honeywell SILENT KNIGHT 6700 User manual

Honeywell

Honeywell SILENT KNIGHT 6700 User manual

Honeywell Notifier ST.PL4+ User manual

Honeywell

Honeywell Notifier ST.PL4+ User manual

Honeywell THOR VM1 User manual

Honeywell

Honeywell THOR VM1 User manual

Honeywell Farenhyt Series Technical manual

Honeywell

Honeywell Farenhyt Series Technical manual

Honeywell GX-Series Assembly instructions

Honeywell

Honeywell GX-Series Assembly instructions

Honeywell nfs2-3030 User manual

Honeywell

Honeywell nfs2-3030 User manual

Honeywell Galaxy Dimension series User guide

Honeywell

Honeywell Galaxy Dimension series User guide

Honeywell Galaxy Dimension GD-48 User manual

Honeywell

Honeywell Galaxy Dimension GD-48 User manual

Honeywell H-S81-HS User manual

Honeywell

Honeywell H-S81-HS User manual

Honeywell HPZC10 Series User manual

Honeywell

Honeywell HPZC10 Series User manual

Honeywell Notifier ID50 Instruction sheet

Honeywell

Honeywell Notifier ID50 Instruction sheet

Honeywell Silent Knight 5860 Technical manual

Honeywell

Honeywell Silent Knight 5860 Technical manual

Honeywell Flex Instruction manual

Honeywell

Honeywell Flex Instruction manual

Honeywell Fire-Lite Alarms ES-50X User manual

Honeywell

Honeywell Fire-Lite Alarms ES-50X User manual

Honeywell Fire-Lite Alarms MS-9200 User manual

Honeywell

Honeywell Fire-Lite Alarms MS-9200 User manual

Honeywell NOTIFIER ID2000 Series Guide

Honeywell

Honeywell NOTIFIER ID2000 Series Guide

Honeywell MS-10UD Series User manual

Honeywell

Honeywell MS-10UD Series User manual

Honeywell 13270-01LB User manual

Honeywell

Honeywell 13270-01LB User manual

Honeywell Lyric LCP300-L User manual

Honeywell

Honeywell Lyric LCP300-L User manual

Honeywell IFP-300 Technical specifications

Honeywell

Honeywell IFP-300 Technical specifications

Popular Control Panel manuals by other brands

Pego ECP200 Expert d7.5 Use and maintenance manual

Pego

Pego ECP200 Expert d7.5 Use and maintenance manual

Econ OP320 Operation manual

Econ

Econ OP320 Operation manual

H3C MPU-LSQM2SUPA0 manual

H3C

H3C MPU-LSQM2SUPA0 manual

ICP DAS USA TPD-280-H quick start

ICP DAS USA

ICP DAS USA TPD-280-H quick start

HDL HDL-MPT2.46 datasheet

HDL

HDL HDL-MPT2.46 datasheet

ABB Eurofire EN54 User and Engineers Instructions

ABB

ABB Eurofire EN54 User and Engineers Instructions

Newport Azure user manual

Newport

Newport Azure user manual

SJE Rhombus NEMA 4X Installation Instructions and Operation/Troubleshooting Manual

SJE Rhombus

SJE Rhombus NEMA 4X Installation Instructions and Operation/Troubleshooting Manual

SOMFY animeo Solo Series installation guide

SOMFY

SOMFY animeo Solo Series installation guide

technoswitch ORYX200 Series Installation & operation manual

technoswitch

technoswitch ORYX200 Series Installation & operation manual

Soundoff Signal Nergy BluePrint ENGCP18001 manual

Soundoff Signal

Soundoff Signal Nergy BluePrint ENGCP18001 manual

Satel PERFECTA-T programming

Satel

Satel PERFECTA-T programming

Vaillant VAZ CPC installation instructions

Vaillant

Vaillant VAZ CPC installation instructions

Mitsubishi Electric PANEL_RS2 installation manual

Mitsubishi Electric

Mitsubishi Electric PANEL_RS2 installation manual

CAME ZL22N installation manual

CAME

CAME ZL22N installation manual

AKO PROPlus manual

AKO

AKO PROPlus manual

Simplex 4007-9201BA manual

Simplex

Simplex 4007-9201BA manual

Panasonic AY-RP500 installation manual

Panasonic

Panasonic AY-RP500 installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.