Range Master RMDD3004 User manual

Downdraft Ventilators
Page 1
WARNING
READ AND SAVE THESE INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF FIRE, E ECTRIC SHOCK, OR
INJURY TO PERSONS, OBSERVE THE FO OWING:
1. Use this unit only in the manner intended by the manufacturer.
If you have questions, contact the manufacturer at the address
or telephone number in the warranty.
2. Before servicing or cleaning unit, switch power off at service
panel and loc the service disconnecting means to prevent
power from being switched on accidentally. When the service
disconnecting means cannot be loc ed, securely fasten a
prominent warning device, such as a tag, to the service panel.
3. Installation wor and electrical wiring must be done by a
qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction codes and
standards.
4. Sufficient air is needed for proper combustion and exhausting
of gases through the flue (chimney) of fuel burning equipment
to prevent bac drafting. Follow the heating equipment
manufacturer’s guideline and safety standards such as those
published by the National Fire Protection Association (NFPA),
and the American Society for Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE), and the local code au-
thorities.
5. When cutting or drilling into wall or ceiling, do not damage
electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. To reduce the ris of fire, use only metal ductwor .
8. Do not install this product with the activating switch directly
behind a burner or element. Minimum distance between the
switch and the edge of the burner should be 4 inches.
9. Loose-fitting or hanging clothing should never be worn when
operating this appliance. They may be ignited by burners/
elements on coo top.
10.Children should not be left alone or unattended in the area
where this appliance is in use.
11. This unit must be grounded.
TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE:
a) Never leave surface units unattended at high settings.
Boilovers cause smo ing and greasy spillovers that may
ignite. Heat oils slowly on low or medium settings.
b) Always turn hood ON when coo ing at high heat or when
coo ing flaming foods.
c) Clean ventilating fans frequently. Grease should not be
allowed to accumulate on fan or filter.
d) Use proper pan size. Always use coo ware appropriate
for the size of the surface element.
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE
EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE
FO OWINGa:
1. SMOTHER FLAMES with a close-fitting lid, coo ie sheet,
or metal tray, then turn off the burner. BE CAREFUL TO
PREVENT BURNS. If the flames do not go out immedi
ately, EVACUATE AND CALL THE FIRE DEPARTMENT.
2. NEVER PICK UP A FLAMING PAN - You may be burned.
3. DO NOT USE WATER, including wet dishcloths or towels
- a violent steam explosion will result.
4. Use an extinguisher ONLY if:
A. You now you have a Class ABC extinguisher, and you
already now how to operate it.
B. The fire is small and contained in the area where it
started.
C. The fire department is being called.
D. You can fight the fire with your bac to an exit.
a Based on “Kitchen Firesafety Tips” published by NFPA.
CAUTION
1. For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.
2. To avoid motor bearing damage and noisy and/or unbalanced
impellers, eep drywall spray, construction dust, etc. off power
unit.
3. Clean filters and grease-laden surfaces frequently.
4. Do not repair or replace any part of this appliance unless
specifically recommended in this manual. All other servicing
should be done by a qualified technician.
5. Please read specification label on product for further informa-
tion and requirements.
MODE WIDTH B OWER
RMDD3004 30" 500 cfm Interior
RMDD3604 36" 500 cfm Interior
RMDD4804 48" 500 cfm Interior
RMDD3004EX 30" Models 331H, 332H, 335, or 336 Exterior (purchase separately)
RMDD3604EX 36" Models 331H, 332H, 335, or 336 Exterior (purchase separately)
RMDD4804EX 48" Models 331H, 332H, 335, or 336 Exterior (purchase separately)
WARNING - To reduce the ris of burns or ignition of clothing by reaching across burners, the downdraft remote control MUST
be mounted in the countertop - at least 4" from the burners. See "INSTALL COOKTOP" section on page 8.
!
INSTA ER:
Save this manual for Electrical
Inspector and Homeowner to use.
NOTE:
Model RMDDRBK Remote Up/Down
Control sold separately.
Call 1-800-667-8721 anywhere in the US and Canada - www.rangehoods.com
at
rangehoods
com
::
.

Page 2
Downdraft Ventilators
AIR
VENT
COUNTER
TOP
BLOWER
BOX
CHIMNEY TOP
COOK TOP
GEAR
MOTOR
COVER
TYPICA INSTA ATION
120 VAC
GROUNDED
OUTLET
This downdraft blower system
is designed to be used to ex-
haust airborne contaminants
when coo ing with a variety of
gas or electric coo tops. It can
be mounted in island, penin-
sula, or conventional wall loca-
tions.
This unit can be easily installed
following these basic steps:
•Cut out the countertop
opening.
•Mount the unit in the
cabinet.
•Connect the ductwor and
electrical.
•Install the coo top.
Note: the high level of air flow of
this appliance may effect the
gas flame on some types of gas
coo tops. This is NORMAL and
will cause no harm, but can be
corrected by lowering the speed
of the blower.
P ANNING
Interior Blower Installation Exterior Blower Installation
Note: the high level of air flow of this appliance may effect the gas
flame on some types of gas coo tops. This is NORMAL and will
cause no harm, but can be corrected by lowering the speed of the
blower.
E ECTRICA
SPECIFICATIONS
120 VAC • 60 Hz • 4.0 A
TAKE MEASUREMENTS
All Units
1. Refer to the coo top installation instructions for dimensions of
coo top, countertop cut-out, and cabinet requirements. Mod-
els RMDD3004 & RMDD3004EX will fit in most 30" wide
cabinets. Models RMDD3604 & RMDD3604EX will fit in most
36" wide cabinets. Models RMDD4804 & RMDD4804EX will
fit in most 48" wide cabinets. However, it is recommended that
oversized cabinets be used for easier installation.
2. Coo top depth can vary greatly from one to another. This may
cause the fit of these two appliances to be rather tight.
Pay special attention to the areas of potential interference high-
lighted above. A countertop with (A) a raised lip and/or (B) a
bac splash may not allow enough flat countertop for a proper
installation. Note that 2" of flat countertop is required behind
coo top and that 1-3/4" is necessary between the bac edge of
the coo top and the inside of cabinet bac .
E ECTRICA
SPECIFICATIONS
120 VAC • 60 Hz • 6.0 A (max.)
3-1/4" X 10"
DUCT CONNECTOR
AIR
VENT
BLOWER
BOX
CHIMNEY TOP
COOK TOP
GEAR
MOTOR
COVER
TYPICA INSTA ATION
3-1/4" X 14"
DUCT CONNECTOR
120 VAC
GROUNDED
OUTLET
COUNTER
TOP
This downdraft blower system
is designed to be used to ex-
haust airborne contaminants
when coo ing with a variety of
gas or electric coo tops. It can
be mounted in island, penin-
sula, or conventional wall lo-
cations.
This unit can be easily installed
following these basic steps:
•Cut out the countertop
opening.
•Mount the unit in the
cabinet.
•Install Model 331H, 332H,
335, or 336 External
Blower
•Connect the ductwor
and electrical.
•Install the coo top.
2

Downdraft Ventilators
Page 3
1. The interior
downdraft blower
system is designed
for use with 3-1/4" x
10" ductwor (can be
transitioned to 6"
round). Three
different discharge
directions are
available with side-to-
side adjustment for
accurate alignment of
ductwor .
2. For best performance:
Choose the ducting
option which allows
the shortest length of
ductwor and a
minimum number of
RIGHT
DISCHARGE
DOWN DISCHARGE
LEFT
DISCHARGE
P AN THE DUCTWORK
Interior Blower Installation Exterior Blower Installation
EQUALS 8 FT. OF
STRAIGHT DUCT
6" ROUND
ELBOW
EQUALS 14 FT. OF
STRAIGHT DUCT
3. The system will operate most efficiently when the ductwor
does not exceed 40 feet of equivalent duct. The chart, above,
shows equivalent feet of elbows and transitions. The number
of feet of straight duct plus the equivalent feet of transitions
and/or elbows to be used should equal 40 feet or less.
NOTE: The equivalent feet of various roof and wall caps has
been taken into consideration. Do not include them in this
calculation.
3-1/4" X 10" TO 6" RD.
TRANSITION 3-1/4" X 10"
90O ELBOW
elbows and transitions. Chec location of floor joists, wall
studs, electrical wiring or plumbing for possible interfer-
ence.
EQUALS
2 FT. OF
STRAIGHT DUCT
1. The interior
downdraft blower
system is designed
for use with 3-1/4" x
14" ductwor (can be
transitioned to 8"
round). Three
different discharge
directions are
available with side-to-
side adjustment for
accurate alignment of
ductwor .
2. For best performance:
Choose the ducting
option which allows
the shortest length of
ductwor and a
minimum number of
RIGHT
DISCHARGE
DOWN DISCHARGE
LEFT
DISCHARGE
EQUALS 11 FT. OF
STRAIGHT DUCT
8" ROUND ELBOW
EQUALS 19 FT. OF
STRAIGHT DUCT
3. The system will operate most efficiently when the ductwor
does not exceed 40 feet of equivalent duct. The chart, above,
shows equivalent feet of elbows and transitions. The number
of feet of straight duct plus the equivalent feet of transitions
and/or elbows to be used should equal 40 feet or less.
NOTE: The equivalent feet of various roof and wall caps has
been taken into consideration. Do not include them in this
calculation.
3-1/4" X 14" TO 8" RD.
TRANSITION 3-1/4" X 14" 90O
ELBOW
elbows and transitions. Chec location of floor joists, wall
studs, electrical wiring or plumbing for possible interfer-
ence.
EQUALS
5 FT. OF
STRAIGHT
DUCT
Interior Blower Installation Exterior Blower Installation
TAKE MEASUREMENTS (CONTINUED)
SIDE VIEW
OF DOWNDRAFT SIDE VIEW
OF DOWNDRAFT

Page 4
Downdraft Ventilators
CENTER LINE
OF COUNTER
CUTOUT
CENTER LINE
OF DUCT
CUTOUT
¼" to 7¾"
5½"
(4¼" FOR
EXTERIOR
BLOWER)
10¼" x 3½"
CUTOUT
(14¼" x 3½"
FOR EXTERIOR
BLOWER)
(2½" MAX.
FOR
EXTERIOR
BLOWER)
(5" MAX.
FOR EXTERIOR
BLOWER)
CENTER LINE
OF COUNTER
CUTOUT
CENTER
LINES OF
DUCT CUTOUT
22
1
/
8
"
(19"
FOR
EXTERIOR
BLOWER)
10¼" x 3½"
CUTOUT
(14¼" x 3½"
FOR
EXTERIOR
BLOWER)
5½"
(4¼" FOR
EXTERIOR
BLOWER)
P AN THE CABINET CUTOUTS
CENTER LINE
OF COUNTER
CUTOUT
CENTER
LINES OF
DUCT
CUTOUT
16
3
/
8
"
(21½" FOR
EXTERIOR
BLOWER)
5½"
(4¼" FOR
EXTERIOR
BLOWER)
10¼" x 3½"
CUTOUT
(14¼" X 3½"
FOR
EXTERIOR
BLOWER)
BOTTOM
DISCHARGE
RIGHT SIDE
DISCHARGE
EFT SIDE
DISCHARGE
!
CAUTION:
BEFORE CUTTING HO E IN
CABINET FOR DUCTWORK,
check for interference with floor
joists, wall studs, electrical
wiring, or plumbing.
Blower Installation

Downdraft Ventilators
Page 5
P AN THE WIRING
Interior Blower Installation Exterior Blower Installation
1. The Exterior Downdraft Blower system draws 6 AMPS and
requires a 120 VAC, 60 Hz circuit.
2. The unit has a 18 in. long power cord with a 3-pronged plug.
Plan to provide a grounded outlet in a location which will allow
the unit’s power cord to reach.
IMPORTANT - OCATION OF E ECTRICA OUT ET:
If Model RMDD3004EX is being installed in a 30" wide
cabinet...
or Model RMDD3604EX is being installed in a 36"
wide cabinet...
or Model RMDD4804EX is being installed in a 48"
wide cabinet...
...the outlet cannot be located on the back wall
of cabinet.
In these cases, the width of the downdraft covers nearly the
entire width of the bac wall of the cabinet. So you must
either:
• mount the electrical box to a side wall or cabinet floor
- at least 12 inches from the bac wall.
• mount the electrical box to a wall stud behind the
cabinet - where it will not be covered by the downdraft.
Then provide a clearance hole in the bac wall of the
cabinet.
1. The Interior Downdraft Blower system draws 4 AMPS and
requires a 120 VAC, 60 Hz circuit.
2. The unit has a 18 in. long power cord with a 3-pronged plug.
Plan to provide a grounded outlet in a location which will allow
the unit’s power cord to reach.
IMPORTANT - OCATION OF E ECTRICA OUT ET:
If Model RMDD3004 is being installed in a 30" wide
cabinet...
or Model RMDD3604 is being installed in a 36" wide
cabinet...
or Model RMDD4804 is being installed in a 48" wide
cabinet...
...the outlet cannot be located on the back wall
of cabinet.
In these cases, the width of the downdraft covers nearly the
entire width of the bac wall of the cabinet. So you must
either:
• mount the electrical box to a side wall or cabinet floor
- at least 12 inches from the bac wall.
• mount the electrical box to a wall stud behind the
cabinet - where it will not be covered by the downdraft.
Then provide a clearance hole in the bac wall of the
cabinet.
PREPARE THE DOWNDRAFT
Interior/Exterior Blower Duct Connection Installation
The downdraft is shipped with duct connector pointing toward the
bottom of the unit. If you wish to change this orientation, follow the
steps below:
1. Place the downdraft on its bac on a table of flat wor surface.
2. Remove the 4 nuts and 2 clamp channels.
3. Remove 2 screws and the gear motor cover.
4. Carefully position the blower under the bottom flange of the
downdraft with the 3¼" x 10" discharge (3¼" x 14" for
exterior blower) pointed in the desired direction.
5. Connect motor plug.
6. Replace the gear motor cover and 2 sheet metal screws.
7. Replace the 2 clamp channels and start the 4 nuts, do not
tighten.
8. Slide blower left of right to desired position. Use cover plate
(supplied) to close up any open space.
9. Tighten 4 nuts to secure top of blower. Use additional screws
(supplied) through bottom flange to secure bottom in blower.
NUTS BLOWER
COVER
PLATE
CLAMP
CHANNELS
SCREWS
GEARMOTOR
COVER MOTOR
PLUG
3¼" X 10" DISCHARGE
(3¼" X 14" FOR EXTERIOR BLOWER)
ADDITIONAL
SCREWS
BOTTOM
FLANGE

Page 6
Downdraft Ventilators
CUT COUNTERTOP OPENING
All Units
1. Lay out and cut the coo top cut-out far enough FORWARD so
downdraft will fit behind it.
2. Set coo top in place and slide it as far forward as possible.
Center and square it with edges of countertop.
3. Place the plastic template against the bac flange of the
coo top and center it. Trace around template to mar the
downdraft opening.
4. Remove coo top from countertop.
5. Cut downdraft opening. Be careful not to chip edges of
countertop.

Downdraft Ventilators
Page 7
1. Cut hole in cabinet as well as holes in wall or floor as
necessary.
2. Mount the roof or wall cap and wor bac towards the cabinet,
attaching all ductwork, elbows and transitions as previ-
ously planned. Tape all ductwor connections to ma e them
secure and air tight.
3. Connect ductwork (and transition, if required) to downdraft. If
necessary, LOOSEN nuts and screws that hold the blower in
place, and slide blower left or right to meet ductwor . Re-
tighten screws and nuts.
Note: A 3¼" x 10" collar (3¼" x 14" collar for exterior blower)
is provided for installers who prefer to rivet the ductwor to the unit.
This will allow blower to be removed and replaced easily in service
situations without disturbing ductwor .
8" RD. ELBOW
& DUCTWORK
3¼" X 10"
TO 6" RD.
TRANSITION
(3¼" X 14" TO 8"
RD. TRANSITION
FOR EXTERIOR
BLOWER
Í BLOWER Î
COLLAR
SCREWS
LEVELING BRACKET -
FLANGE FACING IN
LEVELING BRACKET -
FLANGE FACING OUT
MOUNTING SCREWS
MOUNT THE UNIT
All Units
!
CAUTION:
BEFORE CUTTING HO E IN
CABINET FOR DUCTWORK,
check for interference with floor
joists, wall studs, electrical
wiring, or plumbing.
1. Set downdraft into opening. Extend leveling brackets to floor
of cabinet so downdraft sits straight. (Note: Leveling brac ets
can be removed and re-attached in other positions. Bottom
flange may have to face inward in tight cabinet installations.)
2. Secure the downdraft to the countertop as follows: Hold the
downdraft against the bac of countertop cut-out and tighten-
ing the two mounting screws (one on each end of unit) on
underside of countertop. Use a wood shim between screw and
underside of granite countertops.
3. Screw leveling brackets to bottom of cabinet. Tighten screws
holding leveling brac et to unit on each side.
INSTA DUCTWORK
Blower Installation

Page 8
Downdraft Ventilators
INSTA E ECTRICA WIRING
Interior Blower Installation
1. Mount a standard wiring box, with 3-pronged receptacle,
inside the cabinet. Ma e sure the downdraft's power cord can
easily reach it.
2. Run appropriate power cable into cabinet and connect it to
receptacle.
3. Plug the downdraft's power cord into the outlet. Ma e sure that
the power cord is routed away from the heat generated by the
coo top.
!
CAUTION: All electrical wiring should be done
by a qualified person(s) in accordance with all
applicable codes and standards.
Exterior Blower Installation
1. Mount a standard wiring box, with 3-pronged grounded recep-
tacle, inside the itchen cabinet. Ma e sure the unit's power
cord can easily reach it.
2. Run appropriate power cabinet into cabinet and connect it to
electrical box and receptacle.
3. Exterior blower may not exceed 6.0 Amp rating.
4. Run 2-wire plus ground power cable from the remote blower
to wiring box on 10" round discharge plate.
5. Connect downdraft wiring to power cable from remote blower.
Wire blac to blac , white to white, and green to green or bare
wire.
6. Replace wiring box cover.
7. Plug the downdraft's power cord into outlet. Ma e sure that the
power cord is routed away from the heat generated by the
coo top.
!
CAUTION: All electrical wiring should be done
by a qualified person(s) in accordance with all
applicable codes and standards.
INSTA COOKTOP
All Units
1. Align the coo top with the downdraft and fasten coo top in
place.
Note: Accurate alignment of coo top and downdraft is necessary
to ensure that there is no interference when air vent is raised and
lowered. There should be a gap of 1/32" - 1/16" between the bac
of the coo top and the front of the downdraft cover.
Note:
The downdraft up/down control must be mounted into the
countertop, at least 4" from the coo top.
COUNTERTOP
UP / DOWN
CONTROL
COOKTOP

Downdraft Ventilators
Page 9
REMOTE UP/DOWN CONTRO INSTA ATION
(OPTIONA )
Installation
1. Using the template at right, lay out the 3-hole pattern on the
counter top. Mar the centers of the three holes to be drilled.
2. Carefully drill the three holes through the counter top. Be
careful not to damage or chip the counter top surface when
drilling the holes.
3. Remove the control from the plastic bag. Line the control up
with the three holes and position the control so it is parallel
with the front of the counter top.
4. Remove the two nylon thumbnuts from the plastic bag and
thread onto the two studs on the control from below the
counter top. Hand tighten only.
WARNING: To reduce the risk of burns or ignition
of clothing by reaching across burners, the re-
mote control must be mounted at least 4" away
from any cook top burner.
CUT OUT
ON DOTTED INE
.250 DIA.
HO ES
.438
DIA.
HO E
2.000
2.000
.750
.750
1.000
.625 .625
5. Remove the blower, clamp channels, and gearmotor cover
from downdraft (see"Prepare the Downdraft" on page 5).
Remove the large panel to expose the downdraft's wiring.
When to use the Remote UP/DOWN Control
The Remote UP/DOWN Control should be used when your
coo top has a burner that is within 4 inches of the UP/DOWN
Button on the downdraft chimney.
The Remote UP/DOWN Control can be used for convenient UP/
DOWN operation of the downdraft chimney (even when a burner
is more than 4 inches from the UP/DOWN Button of the downdraft
chimney).
How to use the Remote UP/DOWN Control
Do not place the remote control where it will interfere with
coo ing, where hot pans could be set, or where hot liquids could
be spilled on the control.
The Remote UP/DOWN Control disables the UP/DOWN function
of the UP/DOWN Button on the downdraft chimney.
All Units
6. At the lower right hand corner of downdraft, unplug the cable
from the left side of the wiring box.
7. Remove remote cable from the plastic bag and plug into bac of
control from below counter top. Route cable through cabinet to
lower right hand corner of downdraft and through the clearance
holes in the side of downdraft and wiring box. Plug cable into circuit
board plug, as shown.
8. Stuff excess cable out of the way, secure the cable so it is not
damaged by items stored in the cabinet, and reassemble downdraft.
CABINET
FLOOR
LOWER
RIGHT
SIDE
OF
DOWNDRAFT
CUT OUT ON DOTTED INE
WIRING
BOX REMOTE
CABLE
WIRING
BOX

Page 12
Downdraft Ventilators
SERVICE PARTSWARRANTY
BROAN ONE YEAR IMITED WARRANTY
Broan warrants to the original consumer purchaser of
its products that such products will be free from defects
in materials or wor manship for a period of one year
from the date of original purchase. THERE ARE NO
OTHER WARRANTIES, EXPRESS OR IMPLIED, IN-
CLUDING, BUT NOT LIMITED TO, IMPLIED WARRAN-
TIES OR MERCHANT ABILITY OR FITNESS FOR A
PARTICULAR PURPOSE.
During this one-year period, Broan will, at its option,
repair or replace, without charge, any product or part
which is found to be defective under normal use and
service.
THIS WARRANTY DOES NOT EXTEND TO FLUO-
RESCENT LAMP STARTERS, TUBES, HALOGEN AND
INCANDESCENDT BULBS. This warranty does not
cover (a) normal maintenance and service or (b) any
products or parts which have been subject to misuse,
negligence, accident, improper maintenance or repair
(other than by Broan), faulty installation or installation
contrary to recommended installation instructions.
The duration of any implied warranty is limited to the
one-year period as specified for the express warranty.
Some states do not allow limitation on how long an
implied warranty lasts, so the above limitation may not
apply to you.
BROAN’S OBLIGATION TO REPAIR OR REPLACE, AT
BROAN’S OPTION, SHALL BE THE PURCHASER’S
SOLE AND EXCLUSIVE REMEDY UNDER THIS WAR-
RANTY. BROAN SHALL NOT BE LIABLE FOR INCI-
DENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES
ARISING OUT OF OR IN CONNECTION WITH PROD-
UCT USE OR PERFORMANCE.
Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above
limitation or exclusion may not apply to you.
This warranty gives you specific legal rights, and you
may also have other rights, which vary from state to
state. This warranty supersedes all prior warranties.
To qualify for warranty service, you must (a) notify the
company below, (b) give the model number and part
identification and (c) describe the nature of any in the
product or part. At the time of requesting warrranty
service, you must present evidence of the original
purchase date.
KEY 30N 36N 48N
NO. WIDTH WIDTH WIDTH DESCRIPTION
1 97015987 97015988 97015989 TOP COVER
2 99140195 99140195 99140195 FILTER SPRING
3 99230345 99230345 99230345 POP RIVET
4 97015970 97015971 97015972 CHIMNEY WELDMENT
5 97015874 97015874 97015874 END CAP RH
6 98009358 98009358 98009358 END CAP LR
7 97015973 97015973 97015973 MACHINED CHIMNEY SLIDE
8 98010013 98010013 98010013 MACHINED AIRBOX SLIDE
9 99160421 99160421 99160421 SCREW RHM 8-32 x .375
10 99160419 99160419 99160419 SCREW 8-32 x ..500 PHL
11 99271218 99271218 99271218 GROUND WIRE
12 99150471 99150471 99150471 SCREW 10-32 x .500 TYP CA PH
13 97015841 97015842 97015843 FILTER
14 99710032 99710032 99710032 SPACER
15 99111184 99111184 99111184 SLIDE STRIPS
16 97015974 97015975 97015976 AIRBOX WELDMENT
17 99271210 99271210 99271210 CORD SET
18 99400060 99400060 99400060 STRAIN RELIEF BUSHING
19 99271295 99271295 99271295 WIRE HARNESS
20 99271292 99271292 99271292 POT ASSEMBLY
21 99271291 99271291 99271291 CONTROL BOARD
22 97015674 97015674 97015674 CRANK ASSEMBLY
23 97015977 97015977 97015977 GEAR MOTOR BRACKET
24 99080513 99080542 99080542 GEAR MOTOR
26 98009802 98009801 98009800 FRONT AIRBOX BOTTOM
27 97015990 97015991 97015992 GEAR MOTOR COVER
INTERNAL BLOWER MODELS
97015993 97015994 97015995 GEAR MOTOR COVER
EXTERNAL BLOWER MODELS
28 98008158 98008158 98008158 AIRBOX OPENING COVER
29 98009773 98009773 98009773 AIRBOX CLAMP
30 99260488 99260488 99260488 WHIZ NUT 10-24
31 97015700 97015700 97015700 SCROLL BOX ASSEMBLY
32 98008150 98008150 98008150 SCROLL BOX COVER
33 98008157 98008157 98008157 CAPACITOR CLAMP
34 98008167 98008167 98008167 EXT - SCROLL BOX WELDMENT
35 99080362 99080362 99080362 MOTOR W/CAPACITOR
36 99020247 99020247 99020247 BLOWER WHEEL
37 99100484 99100484 99100484 MOTOR MOUNT ISOLATOR
38 99260477 99260477 99260477 WHIZ NUT 1/4-20
39 99030323 99030323 99030323 THERMOSTAT
40 97015903 97015903 97015903 ADAPTOR PLATE
41 98010005 98010005 98010005 OUTLET PLATE
42 99271304 99271304 99271304 WIRE HARNESS
43 99400042 99400042 99400042 STRAIN RELIEF BUSHING
44 99271296 99271296 99271296 UP/DOWN BUTTON HARNESS
45 99271306 99271306 99271306 THERMOSTAT WIRE HARNESS
46 98010010 98010010 98010010 THERMOSTAT MOUNTING
BRACKET

Downdraft Ventilators
Page 13
SERVICE PARTS
kitchen
accessories
::
U N L I M I T E D
rangehoods
com
::
is a division of
.
Broan at
Other manuals for RMDD3004
2
This manual suits for next models
5
Table of contents
Popular Fan manuals by other brands

Sharper Image
Sharper Image AIRBAR PORTAL owner's guide

Vortice
Vortice MF 90 Instruction booklet

Ruck Ventilatoren
Ruck Ventilatoren EM 150L E2M 01 manual

Vent-Axia
Vent-Axia T-Series Installation & user's instructions

SPX Cooling Technologies
SPX Cooling Technologies COFIMCO 03-11A user manual

RadonAway
RadonAway SF180 installation instructions