RDS PS 8000 Instruction Manual

PS 8000
APOLLO / DELTA 34
SPRAYER CONTROLLER
Operation
RDS Part.No.:
Doc. Issue:
Software Issue:
S/DC/500-10-221
4b : 10/8/01
PS515-002 rev..27 (Apollo)
PS521-000 rev.10(Delta)
1

Electromagnetic Compatibility (EMC)
This product complies with Council Directive 89/336/EEC when
installed and used in accordance with the relevant instructions.
IMPORTANT, READ THIS BEFORE USING THE APOLLO
The Apollo installation is a part of the Precision Farming System
("the System"). It is very important that you follow the described
calibration procedures before operating the Apollo instrument.
Calibration and operation of the Apollo must be in accordance with
these instructions. Use of the System is subject to the following
disclaimer;
1. So far as is legally permissible RDS Technology ("RDS"), or its
distributors, shall not be liable, whatever the cause, for any
increased costs, loss of profits, business, contracts, income, or
anticipate savings or for any special, indirect or inconsequential
damage whatsover (death orpersonal injury excluded).
2. The capabilities and functions of the Precision Farming System
("the System") are limited as set out in the specification of the
System, details of which are contained in the Help files and
product literature and which must be read before using the
System.
3. Without prejudice to the generality of the above it is hereby
acknowledged that the System is not designed nor intended to a)
originate variable treatment plans or b) achieve or avoid any
application rate outside application parameters, which in both
cases shall be the responsibility of the operator.
4. The standard terms and conditions of RDS (except clause 7), a
copy of which is available on request, apply to the supply and
operation of this System.
Service and Technical Support
PLEASE CONTACT YOUR NEAREST DISTRIBUTOR
If unknown then fax: 44 (0) 1453 733311 for further information.
Our policy is one of continuous improvement and the information in
this document is subject to change without notice.
Check that the software reference matches that displayed by the
instrument.
© Copyright RDS Technology Ltd 2001
\UK221-4b.DTP
2

Section 1 Overview
1.1 The RDSPrecision Farming System (Apollo 8000) 4........................
1.2 Installationand Inter-operabilitywithother systems(Apollo8000) 4.............
1.3 ControlSoftware(Apollo8000) 4.....................................
1.4 Control Channels and "Tanks"(Apollo8000) 5............................
1.5 Sprayer Control Modes (Apollo 8000 / Delta 34) 5.........................
1.6 The Operating screens (Apollo 8000 / Delta 34) 7.........................
1.6.1 Menu keys - 7
1.6.2 The MAIN screen page (Single implement operation) - 7
1.6.3 Status Indicators - 8
1.6.4 The MAIN screen page (Multi-tank operation) - 9
1.6.5 The INFOscreen page - 10
1.6.6 The LOG screen page - 10
1.6.7 The SETUP screen page - 11
1.6.8 Data Entry - 11
1.6.9 Units - 12
Section 2 Operation (Apollo 8000 / Delta 34)
2.1 Startup 13......................................................
2.2 Selecting the Tank / Product 13.......................................
2.2.1 Editing Product Names - 13
2.3 Nozzle Settings - the "Nozzle Wizard" 14.................................
2.3.1 Setting the Target Speed - 15
2.3.2 Using the Nozzle Wizard - 15
2.3.3 Editing a Preset Nozzle Type - 15
2.3.4 Programming the Product Density - 16
2.4 AutomaticRateControl 17...........................................
2.4.1 Setting the Target Rate - 17
2.4.2 Overriding the Target rate - 17
2.5 ManualRateControl 17.............................................
2.6 MAINScreen DisplayOptions 18......................................
2.7 TankContents 18.................................................
2.7.1 Tank Filling (Manual) - 19
2.7.2 Tank Filling (Automatic) - 19
2.8 Part / Total Accumulation and RPM Display 20.............................
2.8.1 Reset Totals - 20
2.9 Forward Speed and Flow Rate Alarm 21.................................
2.9.1 Spray Performance Indicator - 21
2.9.2 Setting the Alarm Thresholds - 21
Section 3 Logging Options (Not available on "Delta 34" Model)
3.1 HardwareSetup 22................................................
3.2 Variable Rate Treatment (VRT) 23......................................
3.2.1 Running a Variable-rate Treatment Plan - 23
3.2.2 Overriding the VRT Application Rate - 24
3.2.3 Stopping a VRT Job - 24
3.2.4 Tagging - 25
3.2.5 Extended Data Functions - 25
3.2.6 Display Vehicle Track (MAP) - 26
3.2.7 Display GPSStatus - 26
3.3. DynamicdataLogging 27...........................................
3.4 Field Data Logging 28..............................................
3.5 Review, Reset or Download a Job Summary 29...........................
CONTENTS
3

1 - Overview
Overview
This manual covers the operation of the Pro-Series 8000 when configured as an Apollo
8000 Variable-Rate Spray Controller. Separate manuals are supplied for other
applications. The "Delta 34" instrument has identical sprayer control functions and
capabilities with the exception of Data Logging. This menu is not available.
1.1 The RDS Precision Farming System (Apollo only)
The RDS PS 8000 is a fully DGPS compatible, multi-function cab computer for a wide
range of applications and is the central component of RDS Precision Farming
hardware (figure 1).
1.2 Installation and Inter-operability with other systems (Apollo
only)
An RDS control system comprises several component kits. This modular approach
means that a suitable control system can be specified for a very wide range of
implements. When re-configured with the appropriate control software the PS 8000
head unit can be simplytransferred between different implements.
The PS 8000 can also output variable-rate instructions to other control systems
including Vicon, Bogballe and Amatron systems, as well as acting on variable-rate
instructions received from Fieldstar, Soyl Opti, Agrocom ACT and Hydro-N Sensor
systems.
1.3 Control Software (Apollo only)
Your instrument is pre-loaded with "Apollo Sprayer Control"software only.
With the purchase of a "secondary software module" - an electronic chip loaded into
the back of the instrument, the Pro-Series can be instantly switched to perform
another function e.g. from a Sprayer Controller to a Data Logger for route navigation
and soil mapping tasks. This is done from "Instrument Select" in the "USER
OPTIONS"menu.
There are software modules for yield monitoring/mapping, route/soil mapping,
variable-rate sprayer control, variable-rate belt spreader control, variable-rate disc
spreader control,and variable-rate seed drilling.
For information on connecting and configuring RDS PF hardware e.g. the Data Card
Module, Secondary Software Module, DGPS Receiver, cables etc, and data transfer
to your PC, please refer to the "Precision Farming Supplement".
1
Figure 1
The Pro-Series 8000 is the
central component of RDS
Precision Farming hardware
4

1 - Overview
1.4 Control Channels and 'Tanks'
The PS 8000 is an extremely versatile control system able to simultaneously control
via 4 different "control channels". Each "channel" is a full control system comprising a
control valve or actuator,and a feedback sensor e.g.
- a sprayer flow control valve and a flow sensor,
- a linear actuator with position (rate) feedback,
- a proportional hydraulic control valve and a flow rate sensor
A 'tank' is the default description for the implement tank or hopper (you can
programme your own description accordingly).
Normally there is one control channel per "tank". Occasionally, two control channels
are controlling the output of one "tank" e.g. a fertiliser spreader with two actuators
controlling left and right sides.
Single implement operation (Delta 34)
By default, only 'Tank 1' is enabled. Only one control channel is required for most
sprayer control systems .
Except for the boom setup, each 'tank' can be configured for different sprayers, so
you can simply transfer the head unit to another sprayer fitted with an RDS
distribution system. On changing sprayers, the appropriate 'tank' is enabled from the
"Machine Options" screen in the calibration menu. You must re-configure the boom
setupasrequired.
Multiple implement operation (Apollo only)
You can simultaneously control more than one implement e.g. front and rear-
mounted spreaders, and all 4 channels can be utilised depending on the total
number ofvalve/actuators/motors in operation.
Additional 'Tanks' are enabled from the 'Machine Options' screen in the calibration
menu. The MAIN menu key is then used to cycle between the separate tank display
screens and also a screen displaying application rates for all enabled 'tanks'.
NOTES: All "Tanks" must be distributing across the same basic width / boom setup.
This manual predominantly covers single tank operation, however, where applicable,
a symbol indicates information pertaining to multi-tank operation.
1.5 Sprayer Control Modes
The PS 8000 has three control modes. The Delta 34 has only two;
Manual Control Mode (Apollo / Delta 34)
This gives simple manual control of application rate.
On the Apollo only, field data ("job summaries") can be logged and are stored in the
instrument memory. Up to 75 summaries can be stored.
5

1 - Overview
Automatic Control Mode (Apollo / Delta 34)
This gives fully automatic rate control. Flow / pressure is automatically regulated as
forward speed varies, to ensure that the actual application rate constantly matches a
preset target rate. The application rate can be manually nudged up and down from
the target rate as required for spot application in specific areas. Programmable
alarms warn of high and low flow rates.
On the Apollo only, field data ("job summaries") can be logged and are stored in the
instrument memory. Up to 75 summaries can be stored. If you have a GPS receiver
and RDS Data Card Module connected, as well as creating a job summary, you can
also log the vehicle route and application data to a "dynamic log" file on the PCMCIA
card. The job summary data is also appended to this file, which can be viewed in
PLOT/PLAN.
VRT (Variable-rate treatment) Control Mode (Apollo only)
This enables the system to be controlled via treatment instructions prepared using
RDS PLOT/PLAN or similarly capable Precision Farming software programs, in
conjunction with DGPS position data. To enable fully automatic variable-rate
treatment for Precision Farming applications, the Pro-Series 8000 requires a suitable
DGPS receiver and the RDS PCMCIA Card Module to implement treatment plans
generated in RDS PLOT/PLAN.
A work record file is automatically created on the card module to log data confirming
the actual treatment. The job summary data is also appended to this file, which can
be viewed in PLOT/PLAN.
Please refer to the 'Precision Farming Supplement' Pt No. S/DC/500-10-202 for details
of DGPSinstallation, setup and data transfer with the Data Card Module.
6

1 - Overview
1.6 The Operating Screens (Apollo / Delta 34)
1.6.1 Menu keys
All instrument functions are accessed bynine menu keys adjacent to the LCD display.
The four menu keys to the right of the screen (figure 2) access the primary screen
pages (those viewed during normal operation). There are three primary screens
MAIN, INFO and LOG (Apollo only)for normal operating functions, and a SETUP
screenforcalibration functions.
The five sub-menu keys below the screen control the various display functions and
settings for each of the primary screen pages. Text or icons are displayed adjacent to
the sub-menu keys to denote their function.
1.6.2 The MAIN screen page (Single implement operation)
The instrument will always default to the MAIN screen on startup. The MAIN screen
displays the following information (figure 3).
Figure 2
The functions are con-
trolled via the menu
keys next to the dis-
play
Figure 3
The information displayed
on the MAIN screen
SprayPerformance
Indicator
Forwardspeed
Instantaneous
Applicationrate
Volumeremaining
in tank
OR
Area sprayed
OR
Flow Rate
OR
Pressure (when pressure-
sensor configured for "INFO
ONLY" or "REGULATION")
Tank / Product
Select Spray mode
Select Flow, Area, or Tank
volume (Pressure) display
Return to Target Rate
Target Rate
Boom section
ON/OFF indicator
Adjust application rate
(AUTO or MAN spray mode)
In/Out of work
(Areaaccumulation)GPSLogging Card
Module
StatusIndicators
7

1 - Overview
1.6.3 Status Indicators
The row of icons at the top of the page show the following;
(i) if logging is in progress or not (Apollo only) :-
Logging stopped Logging started
(ii) if the Card Module is connected and whether a card is inserted (Apollo only):-
No Module Module but no card OK
(iii) if a GPS signal is being received (Apollo only):-
No Position Standalone (No Diff.) Full DGPS
(iv) if the area / distance is being accumulated (Apollo / Delta 34):-
No accumulation Accumulation
NOTE: The GPS icon and the Data module status icons will only appear if the GPS / Data
Module settings are selected in the "PORTS SETUP" menu (refer to the calibration
manual).
Otherwise, the status indicators will appear on all the screen pages
8

1 - Overview
1.6.4 The MAIN screen page (multi-tank operation - Apollo only)
The instrument will always default to the MAIN screen on startup. The MAIN screen
differs from that for single tank operation only in the respect of there being a separate
screen page for each tank or hopper enabled (fig. 4), and also a screen page which
shows the application rates for all tanks - the "multi-tank" page (fig.5).
The text line at the top of the screen indicates which tank/product the screen
information is referring to.
Individual tank - display and settings
Press the MAIN menu key repeatedly to cycle between the MAIN screen pages
for each tank.
You can independentlyset the target rate,application mode (AUTOor MAN) and alter
the target rate (AUTOmode) or actual application rate (MAN mode) for each tank,
Multi-tank display and settings
From the "multi-tank" page you can alter the target rate simultaneously for all tanks
set for AUTO (fig. 5) by pressing the arrow keys. All rates will change by the same
increment (default = 5%).
The target rate from each tank is displayed by the graphic. If the
application rate from an individual tank has been adjusted above or below the target
rate, then that target rate will be flashing on the "multi-tank" page. Note that in this
example, tanks 3 and 4 do not show a target rate because they are set to MAN
mode.
Pressing the key will reset all tank rates to their respective pre-programmed
targetrates.
Figure 4
The MAIN screen page with
multiple "tanks" enabled
Figure 5
The multi-tank"MAIN screen
Current Tank / Product Selected
9

1.6.5 The INFO screen page
Additional work measurement functions are displayed on this page.If onlyone tank is
enabled,the screen will displayonlythe product selected and not the tank number as
shown in figure 6.
NOTE: If more than one tank is enabled there is a separate screen page for each tank (as for
the MAIN screen). Press the INFO menu key repeatedly to cycle between each
page.
1.6.6 The LOG screen page (Apollo only)
This page controls data logging (Field Summary data), and P.F. functions (when the
Data Card Module is connected and enabled) and data transfer (e.g. printing a job
summary).
1 - Overview
Figure 6
The INFO screen In/Out of work indication
(Areaaccumulation)
Amountsprayed
AreaAccumulated
RPM indicator
e.g.for Fan,PTO,
orEnginedepending
on the installation
Tank / Product
Reset PART or
NORMAL Totals
Select Tank-filling options
Select PART or
NORMAL Total
display
Select and review / clear / print
summary data for stored jobs
Start/endlogging
Figure 7
The LOG screen
Select GPS Status
screen
Check Alarm
Condition
10

1.6.7 The SETUP screen page
The key selects the SETUP menu for calibration factors and calibration settings
specific to particular products being sprayed and nozzle types fitted.
You should not need to enter menus 1, 2 and 3 in normal use. These settings are
generally made only on initial installation. The menus can be protected with a
personalised PIN number to prevent unauthorized access. Calibration settings that
need to be changed during normal use are shown on figure 8.
1.6.8 Data Entry
Alpha-numeric values are entered via the right-hand keypad. You must press the key
from 2 to 5 times to select the required letter. (Some keys have additional special
characters not shown on the keylegend).
The key will either toggle between lower and upper case characters or when
preceeding a numerical entry, will set a MINUS value.
The key will toggle between 0 and a SPACE.
The key will BACKSPACE the screen cursor if you need to re-enter a character.
The key is the RETURN key and is normally pressed to confirm the data entry
intomemory.
1 - Overview
Figure 8
The information displayed
on the SETUP screen
PINprotected
Time/Date
Contrast/Brightness
Units
Language
Print Cal. Data
Portsconfiguration
Fwd Speed
calibration
RegulationMode
Select / Calibrate Product
Set simulated speed
Select nozzle type
LoggingInterval
Tag Names
Function Names / Values
GPS Antenna Offsets
GPS Home Location
11

1.6.9 Units
Information can be displayed in Metric or Imperial units by selecting the desired
option via the SETUP menu. Please refer to the Calibration manual.
The units are:-
Function Units
Metric UKImperial
ForwardSpeed km/hr miles/hr
Applicationrate litres/ha gallons/acre
Flowrate litres/min gallons/min
Part/TotalArea hectares acres
Tankvolume,
Part/Total volumeapplied litres gallons
Spraypressure bar lbs/in2
1 - Overview
12

Operation (Apollo / Delta 34)
2.1 Startup
Press the key. The startup screen, which shows the software version, will display
for about 8 seconds then the MAINscreen is displayed.
2.2 Selecting the Tank / Product
1 Press the key and then press the key (figure 9a).
The 'PRODUCT SELECTION' screen only lists tanks that have been enabled via the
calibration menu.
NOTE1: By default, the tanks labelled "Tank 1" to "Tank 4" however, these descriptions may be
edited via the "MACHINE OPTIONS" page in the calibration menu.
2 Select the tank using the left / right arrow key, then using the up / down arrow key,
move the screen cursor opposite the product for that tank (figure 9b). For any tank,
you can programme and calibrate up to 8 different products "A" to "H".
NOTE2: By default, the products are labelled "A" for tank 1, "B" for tank 2, "C for tank 3 and "D
for tank 4. You can edit the product description by pressing the key while the
"PRODUCT SELECTION"screen is displayed (section 2.2.1).
3 Press the MAINkey to return to the "MAIN" screen page.
2.2.1 Editing Product Names
The 8 default product descriptions are 'Spray A' to 'Spray H'.
From the 'PRODUCT SELECTION' screen, press the key to select the
'PRODUCT NAMES' screen.
Select the product name using the arrow keys, and edit the name using the alpha-
numerickeypad.
2 - Operation
2
Figure 9
Selecting the PRODUCT
SELECTION screen
13

2 - Operation
2.3 Nozzle settings - the "Nozzle Wizard"
The "Nozzle Wizard" will assist you to choose the appropriate nozzles for a chosen
application rate and forward speed.
The "Nozzle Wizard"displays the following;
The Nozzle Wizard page shows you how a selected nozzle will perform in order to
achieve the Target Application Rate at a programmed Target Speed.
The centre of the "bow tie" display indicates the target speed for optimum nozzle
performance.The operating range of the nozzle is based on the target speed.
There are 8 pre-programmed, ISO standard nozzle types A to H ;
Type Colour
A Orange
B Green
C Yellow
D Blue
E Red
F Brown
G Grey
H White
Figure 10
Selecting the "Nozzle
Wizard"
Target Rate
Nozzle Type
PressureRange
Nozzle operating range
Speed Range
Nozzle Flow Rate
Select Tank
Figure 11
The "Nozzle Wizard"
Edit Nozzle
Data Jug Test
Wizard Select
Nozzle type
14

2 - Operation
NOTE: If you have more than one "tank" enabled, on selecting "Nozzle Setup", the instrument
will first prompt you to select the channel to which the nozzle setup will apply (fig. 12)
before displaying the "Nozzle Wizard" screen.
Alternatively you can press the key in the Nozzle Wizard to select the tank to
which the Nozzle Wizard refers.
2.3.1 Selecting the Target Speed
1 From the SETUP page, press .
2 Key-in the speed and press to start the speed simulation. The display will revert
to the MAIN screen and the icon will start flashing.
Speed simulation can only be started with the sprayer stationary. To stop speed
simulation, press the key or move the vehicle a short distance.
2.3.2 Using the Nozzle Wizard
1 Set your Target Speed as above.
2 Key-in the target application rate either on the MAIN page or on the "Nozzle Wizard"
and press .
3 Cycle through the nozzles with the key until a nozzle is reached closest to the
desired spraying pressure and press .
4 Fit the appropriate nozzles to the sprayer.
2.3.3 Editing the preset Nozzle type
If the nozzles fitted do not correspond to any of the 8 preset types, then you must
select one of the nozzle types A to H and edit the calibration data according to the
nozzle manufacturersdata.
Press the on the Nozzle Wizard to edit nozzle data.
Figure 12
Selecting the "Tank" in the
Nozzle Wizard
15

2 - Operation
2.3.4 Programming the Product Density
You must programme the correct density when spraying fertilisers. The system will
then automatically compensate in order to maintain the correct application rate and
sprayperformance.
Whenever the programmed density for the selected product is anything other than
1.00 the instrument will display the icon on the main screen.
1 Press to select the "SETUP" screen.
2 Press to select the "PRODUCT SELECTION" screen (fig 9).
3 Select the "DENSITY line, key-in the correct density and then press .
4 Use the "ESC" key or press to return to the "SETUP" screen, (or press the
MAIN key to return to the operation screen).
2.3.5 NozzleCalibration
Refer to section 3 of the calibration manual.
16

2 - Operation
2.4 Automatic Rate Control
Select 'AUTO' from the 'MAIN' screen. The flow rate will be automatically adjusted as
forward speed varies, to ensure that the application rate constantly matches the
preset target rate.
2.4.1 Setting the Target Application Rate
From the "MAIN" screen simply key-in the desired target rate and press .
2.4.2 Overriding the Target Application Rate
Press to override the target rate.
The preset target rate can be overidden in ±5% steps while spraying, e.g. over
localised weed infestation or other crop conditions.
While overidden,the target rate indicator will flash.
Press toreturn tothetarget rate.
NOTE :The instrument will automatically alarm if the flow rate/forward speed goes above or
below the limits programmed via the 'SETUP' menu.
When the alarm threshold is reached first of all the screen will change to show the
alarm screen and the message "FLOW LOW" or "FLOW HIGH" is displayed The
instrument will beep continuously. Press any of the lower 'OK' keys to cancel the
alarm screen and return to the 'MAIN' operating screen. An alarm bell icon in the
upper right hand corner of the screen will continue to flash and the instrument will
beep every5 seconds to remind you of the alarm condition.
NOTE: If the instrument flashes the alarm bell icon as above, at any time you can re-identify
the cause of the alarm by pressing the key on the INFOscreen.
2.5 Manual Rate Control
You do not normally need to select this mode, however in the event you experience a
problem with automatic control (if for example the forward speed sensor had stopped
working),you can still control the application rate manually.
Select 'MAN' from the 'MAIN' screen. To maintain the required application rate, you
must maintain a constant forward speed. You can also log and store field data ("job
summaries") as you go, and print them out or download them to a PC or printer when
convenient.
Press to adjust the application rate.
NOTE : The speed range indicator functions as normal, however there is no forward speed or
flow rate alarm in manual mode.
17

2 - Operation
2.6 "MAIN" screen display options
In addition to the Application rate and Forward Speed display, on the appropriate
MAINscreen page for each machine enabled,you can select between,
Volume remaining in tank ( litres or gallons)
Accumulated area ( hectares or acres)
Flow rate ( litres/minor gallons/minute)
Pressure ( bar or psi - only on systems fitted with a pressure sensor)
2.7 Tank Contents
The Apollo 8000 automatically calculates the volume of liquid remaining in the
appropriate tank. The calculation is based on the full tank volume which is
programmed via the "INFO" screen. You can also programme an alarm threshold so
that the instrument will warn you when the tank volume is getting low.
When the alarm threshold is reached (e.g.200 litres),first of all the screen will change
to show the alarm screen and the message 'TANK # LOW'. The instrument will beep
continuously. Press any of the lower 'OK' keys to cancel the alarm screen and return
to the 'MAIN' operating screen. An alarm bell icon in the upper right hand corner of
the screen will continue to flash and the instrument will beep every 5 seconds to
remind you of the alarm condition.
NOTE: If the instrument flashes the alarm bell icon as above, at any time you can re-identify
the cause of the alarm by pressing the key on the INFOscreen.
The screen will change to show the alarm screen and the message 'TANK # EMPTY''
once the tank contents register reaches zero. Again, press any of the lower 'OK' keys
to cancel the alarm screen to return to the 'MAIN' operating screen, and the alarm will
continue as above.
The tank contents register must be reset manually after re-filling the tank unless your
system includes the optional Tank Inflow Sensor and Flow Shutoff Valve. When fitted
this enables the instrument to automatically monitor re-filling and cut off the inflow
when the tank is full.
Figure 13
Selecting the display option
on the MAIN screen
18

2 - Operation
2.7.1 Tank filling (Manual)
1 Select the "INFO" screen and press to access the TANK FILL screen (fig. 14).
The screen will display,
"MAX" - the full tank volume
"NOW" - the volumeremaining in the tank
"TO ADD" - volume to replenish
NOTE: If more than one tank is enabled, there is a separate screen page for each tank (as
for the MAIN screen). Press the INFO menu key repeatedly to cycle between each
page.
2 Fill the tank to the desired level.
3 Confirm that "MAX" corresponds to the quantityin the tank. Adjust as necessary.
NOTE: Move the screen cursor using the arrow keys and enter values via the numeric
keypad.
4 Press to reset to the full tank volume.
5 Confirm the alarm volume ( ) is OK (typically the volume needed to spray a
single bout). Adjust as necessary.
2.7.2 Tank filling (Automatic)
A Tank Inflow Sensor must be installed to measure the inflow. A Shutoff Valve must
be installed to stop the filling automatically.
1 Connect the inflow hose.
2 Select the "TANK FILL" screen as above.
3 Confirm that "MAX" corresponds to the quantity you want in the tank after filling.
Adjustas necessary.
4 Confirm that the "NOW" volume is the volume currently in the tank. Adjust as
necessary.
5 Confirm the alarm volume as above.
6 Press the key.
6
Figure 14
Resetting the Tank Volume
19

2 - Operation
The "TO ADD" volume will then count down and the screen will display "STOP
INFILL". If a Shutoff Valve is fitted, filling will cease automatically when the "TO ADD"
volume reaches zero. You can also press at any time to stop filling. An audible
alarm will sound and filling will stop.
2.8 Part / Total Accumulation and RPM display
You can record the area and volume sprayed for a particular job using the "PART"
Total function. In addition the area and volume will be recorded to the "TOTAL"
memoryregister.
1 Select the "INFO" screen to displaythe accumulated totals and the RPM display.
NOTE: If more than one tank is enabled, there is a separate screen page for each tank (as
for the MAIN screen). Press the INFO menu key repeatedly to cycle between each
page.
2 Select 'PART' todisplaythe Part Area and Part Volume accumulation,
Select "TOTAL" to displaythe Total Area and Total Volume accumulation.
2.8.1 Reset Totals
1 Select the "PART" or "TOTAL" display.
2 Press the RESET key.
3 Press to zero the totals or press ESC to return to the "INFO" screen.
20
Table of contents
Other RDS Controllers manuals