Red Jacket Quick-Set VSFC Submersible Turbine Pump Guide

Manual No: 577013-847 ●Revision: K
Installation, Service, & Parts Lists
The Red Jacket VSFC
Submersible Turbine Pump
Red Jacket® Quick-Set® Submersible Pump

Notice
Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of
merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in
connection with the furnishing, performance, or use of this publication.
Veeder-Root reserves the right to change system options or features, or the information contained in this publication.
This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication
may be photocopied, reproduced, or translated to another language without the prior written consent of Veeder-Root.
Contact Red Jacket Technical Support for additional troubleshooting information at 800-323-1799.
DAMAGE GOODS/LOST EQUIPMENT
Thoroughly examine all components and units as soon as they are received. If any cartons are damaged or missing, write a
complete and detailed description of the damage or shortage on the face of the freight bill. The carrier's agent must verify the
inspection and sign the description. Refuse only the damaged product, not the entire shipment.
VR must be notified of any damages and/or shortages within 30 days of receipt of the shipment, as stated in our Terms and
Conditions.
VEEDER-ROOT’S PREFERRED CARRIER
1. Fax Bill of Lading to V/R Customer Service at 800-234-5350.
2. Call V/R Customer Service at 800-873-3313 with the specific part numbers and quantities that were received damaged or
lost.
3. VR will file the claim with the carrier and replace the damaged/missing product at no charge to the customer. Customer
Service will work with production facility to have the replacement product shipped as soon as possible.
CUSTOMER’S PREFERRED CARRIER
1. Customer files claim with carrier.
2. Customer may submit a replacement purchase order. Customer Service will work with production facility to have the
replacement product shipped as soon as possible.
3. If “lost” equipment is delivered at a later date and is not needed, VR will allow a Return to Stock without a restocking fee.
4. VR will NOT be responsible for any compensation when a customer chooses their own carrier.
RETURN SHIPPING
For the parts return procedure, please follow the instructions in the “General Returned Goods Policy” pages of the “Policies and
Literature” section of the Veeder-Root North American Red Jacket Mechanical Products Price Book. Veeder-Root will not accept
any return product without a Return Goods Authorization (RGA) number clearly printed on the outside of the package.
Veeder-Root 2019 All rights reserved.

Table of Contents
iii
Introduction
Overview ...........................................................................................................................1
Red Jacket VSFC Operation Selections ...........................................................................2
Stand Alone Pump Operation...................................................................................2
Tandem Pump Operation .........................................................................................2
Required Kits ....................................................................................................................2
Safety Precautions ............................................................................................................3
Warnings and Instructions ................................................................................................4
PRELIMINARY PRECAUTIONS ..............................................................................4
REQUIREMENTS FOR USE....................................................................................5
OPERATING PRECAUTIONS .................................................................................5
Reference Manuals - As Required ....................................................................................6
Fuel Compatibilities ..........................................................................................................6
Operation with Mechanical Leak Detection .......................................................................6
Installation and Manifold Dimensions ...............................................................................7
Recommended Floating Suction Installation .....................................................................7
Dimensions for Pump Selection ........................................................................................8
Specifications ..................................................................................................................10
Installation
Attaching the UMP ..........................................................................................................12
Installing the Pump .........................................................................................................13
Pressure Transducer Installation ....................................................................................18
I.S. Barrier Installation ....................................................................................................18
Tubing Kit Installation .....................................................................................................18
Installing Pumps for Multiple Pump Operation ................................................................22
Siphon Ports ...................................................................................................................22
Service And Repair
Replacing the UMP .........................................................................................................24
Kits Required: .........................................................................................................24
Procedure: ..............................................................................................................24
Installing a Siphon Assembly ..........................................................................................27
Procedure: ..............................................................................................................27
Replacing the Check Valve Assembly ............................................................................29
Procedure: ..............................................................................................................29
Replacing the Conduit Bushing ......................................................................................31
Procedure: ..............................................................................................................31
Replacing the Pigtail .......................................................................................................32
Kits Required: .........................................................................................................32
Procedure: ..............................................................................................................32
Replacing the Packer-to-Manifold Wiring Connectors ....................................................34
Kits Required: .........................................................................................................34
Procedure: ..............................................................................................................34
Installing a Pressure Transducer ....................................................................................39
Kits Required: .........................................................................................................39
Other parts:.............................................................................................................39
Procedure: ..............................................................................................................39
Replacing the Air Purge Screw .......................................................................................40
Kits Required: .........................................................................................................40
Procedure: ..............................................................................................................40

Table of Contents
iv
Pump Tests
Verifying Relief Pressure ................................................................................................44
Checking Relief Pressure at the Pump ...........................................................................44
Equipment Required:..............................................................................................44
Procedure: ..............................................................................................................44
Testing the Line ..............................................................................................................45
Equipment Required:..............................................................................................45
Procedure: ..............................................................................................................45
Testing the tank ..............................................................................................................47
Equipment Required:..............................................................................................47
Procedure: ..............................................................................................................47
Parts Lists
Customer Service Number ..............................................................................................48
Pump Parts .....................................................................................................................48
Siphon Cartridge Kit Parts ..............................................................................................50
Check Valve Housing Kit Parts .......................................................................................50
Check Valve Kit Parts .....................................................................................................51
Conduit Bushing Kit Parts ...............................................................................................52
Die Spring Kit Parts ........................................................................................................52
O-Ring Kit Parts ..............................................................................................................53
Electrical Connector Kit Parts .........................................................................................54
Air Purge Screw Kit Parts ...............................................................................................54
Capacitor Kits .................................................................................................................55
Siphon Dummy Plug Kit Parts ........................................................................................56
Eyebolt Plug Kit Parts .....................................................................................................57
Conduit Box Plug Kit Parts .............................................................................................58
Appendix A: Hardware/Seal Kit O-Ring Gauge
Appendix B: Check Valve/Air Purge Screw Operation
Figures
Figure 1. Red Jacket Pac/Man Components And Dimensions ..............................7
Figure 2. Floating Suction Installation ....................................................................8
Figure 3. Floating Suction Adapter ........................................................................8
Figure 4. Measuring The Tank (See Table 2 For Adjustment Ranges) .................9
Figure 5. Identifying UMP Models By Their End View .........................................11
Figure 6. Packer/Manifold With Piping Attaching To UMP ...................................12
Figure 7. Verifying Pigtail Female Connector Is Seated Properly ........................12
Figure 8. Aligning The UMP Gasket ....................................................................13
Figure 9. Measuring Tank ....................................................................................14
Figure 10. Loosening Column Pipe Locking Nut ....................................................15
Figure 11. Adjusting Pump Length .........................................................................15
Figure 12. Locating Return Line Fitting On Packer ................................................16
Figure 13. Attaching Return Line Tubing To Pump ................................................16
Figure 14. Connecting UMP To Packer Wiring ......................................................17
Figure 15. VSFC Component Installation Ports .....................................................18
Figure 16. Compression Bushing ...........................................................................19
Figure 17. Installed Tubing From Kit In Compression Bushing ..............................20
Figure 18. Recommended Power Wire Entry Through The
Compression Bushing ...........................................................................20

Table of Contents
v
Figure 19. Recommended Power Wire/I.S. Barrier (Transducer)
Wire Entry Through The Compression Bushing ...................................21
Figure 20. Multiple Pumps .....................................................................................22
Figure 21. Siphon Connection ...............................................................................23
Figure 22. Extractable Lock-Down Nuts ................................................................24
Figure 23. UMP Bolts And Gasket .........................................................................25
Figure 24. Verifying Pigtail’s Female Connector Is Seated Properly .....................25
Figure 25. Locating Packer And Manifold O-Rings ................................................26
Figure 26. Siphon Ports .........................................................................................27
Figure 27. Inserting Siphon Assembly Into Manifold ..............................................28
Figure 28. Inserting Check Valve Assembly Into Manifold .....................................30
Figure 29. Extractable Lock-Down Nuts ................................................................32
Figure 30. Packer-To-Manifold Wiring Connectors ................................................35
Figure 31. Male Connector’s Indexing Pin .............................................................35
Figure 32. Male Connector Index Hole In Base Of Socket ....................................36
Figure 33. Placing Masking Tape Alignment Marker On Front Of Male Connector ..36
Figure 34. Correct Depth Of Male Connector In Packer Socket ............................37
Figure 35. Locating Female Connector Set Screw ................................................38
Figure 36. Locating Discharge Port Plug For Pressure Transducer ......................39
Figure 37. Locating Air Purge Screw .....................................................................40
Figure 38. Locating Air Purge Screw Hitch Pin ......................................................41
Figure 39. Reorienting The Air Purge Screw Hitch Pin ..........................................41
Figure 40. Hitch Pin In Position To Install Air Purge Screw ...................................41
Figure 41. Installing Air Purge Screw Hitch Pin In The Retaining Position ............42
Figure 42. Locating Pump Line Test Port ..............................................................44
Figure 43. Service Screw, Line Test Port, And Air Purge Screw Locations ...........46
Figure 44. Tank Test Port On Manifold ..................................................................47
Figure 45. Pump Parts ...........................................................................................49
Figure 46. Siphon Cartridge Kit ..............................................................................50
Figure 47. Check Valve Housing Kit ......................................................................50
Figure 48. Check Valve Kit ....................................................................................51
Figure 49. Conduit Bushing ...................................................................................52
Figure 50. Die Spring Kit ........................................................................................52
Figure 51. O-Ring Kit .............................................................................................53
Figure 52. Electrical Connector Kit ........................................................................54
Figure 53. Air Purge Screw Kit ...............................................................................54
Figure 54. Capacitor Kit .........................................................................................55
Figure 55. Siphon Dummy Plug Kit ........................................................................56
Figure 56. Eyebolt Plug Kit ....................................................................................57
Figure 57. Conduit Box Plug Kit .............................................................................58
Figure B-1. Pump On Condition ............................................................................ B-1
Figure B-2. Relief Valve Vents Excess Line Pressure ........................................... B-1
Figure B-3. Locking Down The Check Valve For Line Testing .............................. B-2
Figure B-4. Removal Of Check Valve Assembly For Service ................................ B-2
Figure B-5. Returning The Check Valve To Its Normal Operating Position ........... B-3
Figure B-6. Purging Air From Manifold .................................................................. B-4
Tables
Table 1. Maximum Specific Gravity And Maximum Viscosity ..................................6
Table 2. Distances From Top Of Lifting Screw To Inlet .........................................10
Table 3. Electrical Service Information ..................................................................10
Table 4. UMP Model Dimensions ..........................................................................10
Table 5. Approximate Pump Shut Off Pressure Range .........................................11
Table 6. UMP And Packer/Manifold Combinations ...............................................12

Table of Contents
vi
Table 7. Pump Parts List .......................................................................................48
Table 8. 410151-001 Siphon Cartridge Kit Parts List ............................................50
Table 9. Check Valve Housing Kits Parts Lists .....................................................50
Table 10. 410153-001 Check Valve Kit Parts List ...................................................51
Table 11. 410153-002 Hi Pressure Check Valve Kit Parts List ...............................51
Table 12. 410486-001 Conduit Bushing Kit Parts List .............................................52
Table 13. 410485-001 Die Spring Kit Parts List ......................................................52
Table 14. 410154-001 O-Ring Kit Parts List ............................................................53
Table 15. 410165-001 Electrical Connector Kit Parts List .......................................54
Table 16. 410484-001 Air Purge Screw Kit Parts List .............................................54
Table 17. Capacitor Kits ..........................................................................................55
Table 18. Siphon Dummy Plug Kit Parts List ..........................................................56
Table 19. 410482-001 Eyebolt Plug Kit Parts List ...................................................57
Table 20. 067-258-5 Conduit Box Plug (STD) Kit Parts List ...................................58

1
Introduction
Overview
The Red Jacket VSFC STP ensures a constant flow to each nozzle in the fuel line, regardless of the number of
nozzles in use at anytime. The Red Jacket VSFC STP fits 4-inch NPT threaded, thin-wall risers and is adjustable to
fit the requirements of most installations.
Newly designed features of The Red Jacket VSFC STP are:
• Service spill elimination
The check valve can be raised to provide a larger path to depressurize the line and return fuel to the tank.
• Vacuum monitoring applications
The vacuum sensor siphon is a monitoring-grade siphon system. It is designed specifically for use in vacuum
monitoring applications, and to integrate with V-R vacuum sensors. The two-port vacuum sensor-siphon system
incorporates a redesigned one-piece rubber check valve with an inline filter screen that reduces the clogs and
failures that can cause false alarms and downtime in vacuum monitoring applications.
• Plug-in yoke electrical connection
Current safety practice when servicing existing STPs requires turning off the circuit breaker, backing off the
bolts by up to one inch, and then manually pulling the electrical yoke connection apart. With The Red Jacket
VSFC STP you turn off the circuit breaker, then simply back off the two nuts holding the extractable in place and
the yoke electrical connection is broken as the extractable is removed. After service is complete, the electrical
circuit reconnects when the two nuts are retightened. Safe, simple, and easy.
• Extractable is easy to service
The Red Jacket VSFC STP incorporates industrial die springs that break loose the o-ring seals when the nuts
holding the extractable in place are removed. No physical effort or special equipment is required to break the
seal. In addition, all connected parts have been moved to the manifold. There is no need to remove parts,
pressure transducers, leak detectors, or siphons when service or upgrades require removing the extractable.
Utilize the lifting eyebolt to lift out the extractable unit. Removal of the extractable section of the pump must be
conducted with caution. Make certain that the extractable section remains centered within the riser pipe and
that no portion of the extractable binds during the removal process. If binding occurs during removal, stop and
determine the cause of the binding and correct the situation before proceeding with removal.
• Manifold allows for vertical or horizontal discharge
The Red Jacket VSFC STP has been designed for vertical product discharge via a 2-inch NPT threaded port,
but with adequate swinging radius to allow for the addition of an elbow to accommodate a side discharge. In
fact, the discharge is now located higher on the manifold so that a side discharge is on the same plane as the
rest of the pump.
• Built-in contractor's box
An electrical connection housing (contractor's box) is built into The Red Jacket VSFC STP's manifold and is
completely isolated from the fuel path. Unlike existing systems, there is no adjustment required to fit the yoke,
making this pump easy to install.
• Pressurized Line leak detection (PLLD) compatibility
The Red Jacket VSFC STP’s pressure transducer does double duty by supplying the product line’s pressure
measurements for both variable speed flow control and Veeder-Root’s PLLD system.

Introduction Red Jacket VSFC Operation Selections
2
Red Jacket VSFC Operation Selections
Stand Alone Pump Operation
The VSFC Controller’s microprocessors are preprogrammed from the factory for stand alone operation, i.e., one
VSFC Controller and one VSFC STP pressurize the product line.
Tandem Pump Operation
When multiple VSFC STPs are required to maintain proper flow, their VSFC Controllers can be programmed to
operate in tandem. The master VSFC Controller varies the speed of the primary pump depending on the pressure
in the line. When the primary pump can no longer maintain proper pressure, additional pump(s) come on line to
supplement the pressure and maintain proper flow. Instructions in the VSFC Installation Guide (P/N 577013-815)
explain how to setup for tandem operation.
Master-Slave Operation
The installer can designate one VSFC Controller as the master unit and the others as the slave units. The master
VSFC Controller monitors line pressure and determines when a supplemental pump is required. Additional pumps
will turn on if they have received a dispense-enable signal.
Alternating Operation
This feature allows the pumps to alternate and prevent the problem of having one tank run dry. It also ensures that
one pump does not wear excessively. For each dispensing cycle, the master VSFC Controller determines which
VSFC STP will be the primary pump. When the master controller receives the dispense-enable signal, the primary
pump starts. The master VSFC Controller monitors line pressure and determines when a supplemental pump is
required. Additional pumps will turn on even if they have not received a dispense-enable signal.
Tank-Based Operation
Individual pumps will turn on when they have received a dispense-enable signal. The master VSFC Controller
monitors line pressure and determines when a supplemental pump is required. Additional pumps will turn on even
if they have not received a dispense-enable signal.
IMPORTANT!
For VSFC stand alone installations a V-R PLLD Pressure Transducer is required in the VSFC STP. To
install this transducer, refer to the relevant section of the PLLD Site Prep guide (P/N 576013-902).
For VSFC Tandem, Master-Slave, Alternating, or Tank-based installations, a V-R PLLD Pressure
Transducer is required only in the VSFC STP that is connected to the Master VSFC Controller. To
install this transducer, refer to the relevant section of the PLLD Site Prep guide (P/N 576013-902).
For VSFC installations in sites that have a TLS-350 Console with PLLD line leak detection monitoring
the product line, a separate PLLD transducer is not required because the VSFC unit and the PLLD
system will share the same transducer that is installed in the VSFC STP.
For all VSFC STP installations you must make wiring connections in the pump (i.e., pressure
transducer, I.S. Barrier, and pump power connections) following the instructions in the VSFC
Installation Guide (P/N 577013-815).
Required Kits
• VSFC Tubing kit (P/N 410370-001)
• VSFC Controller (P/N 330020-450) for I.S. wiring - includes pressure transducer, or
• VSFC Controller (P/N 330020-451) for non-I.S. wiring - includes pressure transducer and I.S. Barrier.
NOTICE

Introduction Safety Precautions
3
Safety Precautions
The following safety symbols are used throughout this manual to alert you to important safety hazards and
precautions.
EXPLOSIVE
Fuels and their vapors are extremely explosive if
ignited.
FLAMMABLE
Fuels and their vapors are extremely flammable.
ELECTRICITY
High voltage exists in, and is supplied to, the device.
A potential shock hazard exists.
TURN POWER OFF
Live power to a device creates a potential shock
hazard. Turn Off power to the device and associ-
ated accessories when servicing the unit.
WARNING indicates a hazardous situation
which, if not avoided, could result in death or
serious injury.
CAUTION indicates a hazardous situation
which, if not avoided, could result in minor or
moderate injury.
WEAR EYE PROTECTION
Wear eye protection when working with pressurized
fuel lines to avoid possible eye injury.
NOTICE is used to address practices not
related to physical injury.
WEAR GLOVES
Wear gloves to protect hands from irritation or injury.
NO POWER TOOLS
Sparks from power tools (such as drills) can
ignite fuels and their vapors.
NO SMOKING
Sparks and embers from burning cigarettes or pipes
can ignite fuels and their vapors.
NO OPEN FLAMES
Open flames from matches, lighters, welding
torches, etc. can ignite fuels and their vapors.
READ ALL RELATED MANUALS
Knowledge of all related procedures before you
begin work is important. Read and understand all
manuals thoroughly. If you do not understand a pro-
cedure, ask someone who does
TURN OFF CELL PHONES/PAGERS
Sparks from electronic devices in the vicinity of
gasoline storage tanks could cause an explosion
or fire resulting in bodily injury or death.
OFF
WARNING
CAUTION
NOTICE

Introduction Warnings and Instructions
4
In addition to the specified torque values noted in this manual, when properly tightened, all flanged fittings should
have metal-to-metal contact.
Warnings and Instructions
This section introduces the hazards and safety precautions associated with installing,
inspecting, maintaining or servicing this product. Before performing any task on this
product, read this safety information and the applicable sections in this manual, where
additional hazards and safety precautions for your task will be found. Fire, explosion,
electrical shock or pressure release could occur and cause damage to property,
environment, resulting in serious injury or death, if these safe service procedures are
not followed.
PRELIMINARY PRECAUTIONS
You are working in a potentially dangerous environment of flammable fuels, vapors, and high
voltage or pressures. Only trained or authorized individuals knowledgeable in the related
procedures should install, inspect, maintain or service this equipment.
Read the Manual
Read, understand and follow this manual and any other labels or related materials supplied with this equipment. If
you do not understand a procedure, call 1-800-323-1719 to locate a qualified technician. It is imperative to your
safety and the safety of others to understand the procedures before beginning work. Make sure your
employees and any service contractors read and follow the instructions.
Follow the Regulations
Applicable information is available in National Fire Protection Association (NFPA) 30A; Code for Motor Field
Dispensing Facilities and Repair Garages, NFPA 70; National Electrical Code (NEC), Occupational Safety and
Hazard Association (OSHA) regulations and federal, state, and local codes. All these regulations must be
followed. Failure to install, inspect, maintain or service this equipment in accordance with these codes, regulations
and standards may lead to legal citations with penalties or affect the safe use and operation of the equipment.
Prevent Explosions and Fires
WARNING
This product operates in the highly combustible atmosphere of a gasoline storage tank.
FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY PRECAUTIONS
COULD CAUSE DAMAGE TO PROPERTY, ENVIRONMENT, RESULTING IN SERIOUS INJURY
OR DEATH.
1. All installation work must comply with the latest issue of the National Electrical Code
(NFPA 70), the Code for Motor Fuel Dispensing Facilities and Repair Garages (NFPA
30A), and any European, national, state, and local code requirements that apply.
2. Turn off, tag, and lockout power to the STP before connecting or servicing the STP.
3. Before installing pipe threads apply an adequate amount of fresh, UL classified for
petroleum, non-setting thread sealant. For AG applications, Loctite 564 is
recommended for all field serviceable pipe threads.
4. When servicing unit, use non-sparking tools and use caution when removing or
installing equipment to avoid generating a spark.
5. To protect yourself and others from serious injury, death, or substantial property
damage, carefully read and follow all warnings and instructions in this manual.
OFF
WARNING
WARNING

Introduction Warnings and Instructions
5
Fuels and their vapors will explode or burn, if ignited. Spilled or leaking fuels cause vapors. Even filling customer
tanks will cause potentially dangerous vapors in the vicinity of the dispenser or island.
Working Alone
It is highly recommended that someone who is capable of rendering first aid be present during servicing.
Familiarize yourself with Cardiopulmonary Resuscitation (CPR) methods, if you work with or around high voltages.
This information is available from the American Red Cross. Always advise the station personnel about where you
will be working, and caution them not to activate power while you are working on the equipment. Use the OSHA
Lockout/Tagout procedures. If you are not familiar with this requirement, refer to OSHA documentation.
Working With Electricity Safely
Ensure that you use safe and established practices in working with electrical devices. Poorly wired devices may
cause a fire, explosion or electrical shock. Ensure that grounding connections are properly made. Ensure that you
do not pinch wires when replacing covers. Follow OSHA Lockout/Tagout requirements. Station employees and
service contractors need to understand and comply with this program completely to ensure safety while the
equipment is down. Before you start work, know the location of the Emergency Power Cutoff Switch (the E-
STOP). This switch cuts off power to all fueling equipment and submerged turbine pumps and is to be used in the
event of an emergency. The buttons on the console at the cashier’s station WILL NOT shut off electrical power to
the pump/dispenser. This means that even if you press a button on the console labeled EMERGENCY STOP,
ALL STOP, PUMP STOP, or something similar, fuel may continue to flow uncontrolled.
Hazardous Materials
Some materials may present a health hazard if not handled correctly. Ensure that you clean hands after handling
equipment. Do not place any equipment in the mouth.
FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY
PRECAUTIONS COULD RESULT IN PROPERTY DAMAGE, INJURY OR DEATH.
FIRE HAZARD! Do NOT use power tools (Class I Division I and Class I Division II) during the installation or
maintenance of equipment. Sparking could ignite fuel or vapors, resulting in fire.
CHEMICAL EXPOSURE HAZARD! Wear appropriate safety equipment during installation or maintenance of
equipment. Avoid exposure to fuel and vapors. Prolonged exposure to fuel may cause severe skin irritations and
possible burns.
REQUIREMENTS FOR USE
• The Red Jacket is designed for use only at facilities dispensing motor fuels.
• Application of The Red Jacket must be consistent with NFPA Code 30A, OSHA regulations, and federal, state
and local fire codes, and other applicable local regulations.
• The selection of any Veeder-Root product must be based upon physical specifications and limitations and the
product’s compatibility with the materials to be handled. Veeder-Root makes no warranty of fitness for a
particular purpose.
• All Veeder-Root products should be used in accordance with applicable federal, state and local laws,
ordinances and regulations.
OPERATING PRECAUTIONS
•NO SMOKING. Extinguish all open flames and pilot lights, such as on RV appliances.
•TURN OFF cell phones and other electronic devices to prevent sparks which could cause an explosion or fire.
WARNING

Introduction Reference Manuals - As Required
6
Reference Manuals - As Required
• Variable Speed Flow Controller Installation Guide- P/N 577013-815
• PLLD (Pressurized Line Leak Detection) Site Prep and Installation Guide - P/N 576013-902
• FXV Leak Detectors Installation Instructions - P/N D042-106-1
Fuel Compatibilities
Pumps are designed to operate in a Class 1, Group D atmosphere and in accordance with CENELEC standard
and the European Directive 94/9/EC “Equipment for Potentially Explosive Atmoshpere” (II2 G Ex IIA T4).
The STP is designed to be compatible with 100 percent gasoline, or diesel and 80 percent gasoline with 20
percent methanol, ethanol, TAME, ETBE, or MTBE (see Table 1 for UMP models and working parameters).
The Red Jacket features an adjustable column pipe and electrical conduit that allows the overall length to be
adjusted to a wide range of overall pump lengths. By loosening a collet on the column pipe, the length of the UMP
may be varied by extending or retracting the column pipe. Three sizes of adjustable column pipe are available to
cover most pump length requirements (RJ1, RJ2, and RJ3).
Operation with Mechanical Leak Detection
A Red Jacket FXV Series leak detector can be installed in the pressure transducer port when mechanical leak
detection is desired.
When a mechanical leak detector is installed in place of the pressure transducer, the STP
will automatically revert to fixed speed operation due to the absence of a pressure
transducer signal. Flow rates will be lower than what can be obtained with variable speed
operation.
To maintain variable speed operation with mechanical leak detection, a pressure transducer must be mounted in a
2-inch tee fitting that is installed in the discharge line within the submersible sump, and before the ball valve.
All Models of the STP are UL Listed for the Following Fuel Compatibility
Diesel Gasoline
Gasoline and up to
15%
Ethanol
15%
Methanol
20%
MTBE
20%
ETBE
20%
TAME
Table 1. Maximum Specific Gravity And Maximum Viscosity
UMP Model
Maximum Specific
Gravity Maximum Viscosity
UMP200U20-2 .95 70SSU at 60°F (15°C)
NOTICE

Introduction Installation and Manifold Dimensions
7
Installation and Manifold Dimensions
Figure 1 shows several views and dimensions of The Red Jacket pac/man.
Figure 1. Red Jacket Pac/Man Components And Dimensions
Recommended Floating Suction Installation
Figure 2 is an example of a floating suction installation. The floating suction arm can be mounted to pump previous
to installing in tank.
Veeder-Root supplies adapter only, not the apparatus.
2'' discharge to
dispensers
Tank port for
mechanical LLD
4'' riser
Tank
Manhole
Driveway grade
Vacuum siphon
port
Check valve
pressure
release
The Red Jacket
VSFC STP
Contractor's
box
Extractable
PLLD transducer port 7.7'' (196 mm) installation
radius (15.4'' [392 mm]
diameter)
Line test port
10.9 "
(277 mm)
11.7''
( 297 mm)
8.97"
(228mm)
rjpumps/fig1vsfc.eps
Air Purge Screw
Secondary vacuum port
NOTICE

Introduction Dimensions for Pump Selection
8
Figure 2. Floating Suction Installation
Figure 3 is an enlarged view within the circle in the above figure.
Figure 3. Floating Suction Adapter
Easy service access is provided by unbolting manhole lid through which pump is mounted and removing entire
assembly. Use proper thread sealant and insert gasket between flanges of floating suction and pump. This
prevents hindrance to pump performance when product level is below this point.
The Red Jacket is a centrifugal type pump and is not designed to pump product when the
level is below the bottom end of the UMP.
Dimensions for Pump Selection
Figure 4 shows the dimensions needed to ensure a correctly sized pump.
Manhole:
should be larger than manhole
welded on tank, keep area open
down to tank.
Opening for gauging and
adjusting cable
14''
(356 mm)
Minimum 3 ' (914 mm)
4''
(102 mm)
rjpumps/fig2.eps
2'' NPT female thread
14''
(356 mm)
Bottom of tank
rjpumps/fig3.eps
NOTICE

Introduction Dimensions for Pump Selection
9
Figure 4. Measuring The Tank (See Table 2 For Adjustment Ranges)
Distance between centerline of UMP and centerline of bottom fill tube should be 3 feet (914
mm) minimum. Air locking of pump after product delivery may occur at distances less than
this.
5" (127 mm) Standard inlet and trapper
14" (356 mm) For floating suction adapter
Tank
Diameter
Riser
Length
L
Bury
Depth
11.7 "
(297 mm)
4 " (102 mm)
minimum
rjpumps/fig4.eps
Adjust The
Red Jacket
to this
dimension
NOTICE

Introduction Specifications
10
Specifications
Table 2 shows the adjustable pump lengths by model
Table 3 shows pump electrical service requirements.
Table 4 lists UMP weights and lengths.
The weights and lengths listed below are approximate values and will vary due to
manufacturing tolerances.
The optional trapper intake screen is available as a field installed accessory. Trapper options will increase the
length of the UMP by 3.3 inches (83 mm). For installation instructions, see Red Jacket installation instructions
#051-256-1. For models with floating suction adapter, add 2-3/8 inches (59 mm) and 4 pounds (1.8 kg).
Table 2. Distances From Top Of Lifting Screw To Inlet
Model#
Retracted Extended
in. mm in. mm
P200U20-2RJ1 75 1902 105.5 2673
P200U20-2RJ2 105 2665 165.5 4197
P200U20-2RJ3 165 4188 225.5 5721
Table 3. Electrical Service Information
Required power supply rating for 60 Hz, 1 phase is 208 - 230 Vac. For 50 Hz, 1 phase, required rating is 220 - 240 Vac. For
3 phase, required rating is 200 - 240 Vac.
UMP Model No. HP Hz PH
Voltage Fluctuation
Range
Max.
Load
Amps
Locked
Rotor
Amps
Winding Resistance (Ohms)
Min. Max.
Black-
Orange
Red-
Orange Black-Red
UMP200U20-2 2
60/50 1
180 265
16 –
2.0 - 3.0 2.0 - 3.0 2.0 - 3.0
60/50 3 10 –
Table 4. UMP Model Dimensions
A
(Use these lengths for UMPs with
end view A shown in Figure 5)
B
(Use these lengths for UMPs with
end view B shown in Figure 5) Weight
UMP Model HP in. mm in. mm lb. kg
UMP200U20-2 2 20 508 20¾ 527 37 16.8
NOTICE

Introduction Specifications
11
Figure 5 identifies UMP models by their end view.
Figure 5. Identifying UMP Models By Their End View
Table 5 lists pump shut off pressure range.
Note: Instructions in the VSFC Installation and Operation manual explain how to set desired pressure.
Table 5. Approximate Pump Shut Off Pressure Range
UMP Model Approximate Shut Off Pressure Range
UMP200U20-2 14 - 45 psi (96.5 - 297 kPa)
UMP End View A UMP End View B rjpumps\umpend.eps

12
Installation
Attaching the UMP
Table 6 lists the applicable UMPs for each packer/manifold.
The UMP is identified by the model number marked on the shell. The packer/manifold with piping is identified by
the catalog number on the packer nameplate. The hardware kit consists of four 5/16-18 socket head cap screws,
four 5/16 lock washers and one discharge head gasket identified by the kit number (144-327-4) marked on the
bag (see Figure 6).
The UMP attaches to the packer/manifold column piping discharge head using hardware kit number 144-327-4.
Figure 6. Packer/Manifold With Piping Attaching To UMP
1. Visually inspect the pigtail connector in the end of the discharge head. Be certain the pigtail connector is
seated in its socket and its index tab is in the socket’s notch (see Figure 7).
Figure 7. Verifying Pigtail Female Connector Is Seated Properly
Table 6. UMP And Packer/Manifold Combinations
Packer/Manifold UMP
P200U20-2RJ1, RJ2, RJ3 UMP200U20-2
Ump
rjpumps/fig5.eps
Packer/manifold
with piping
Kit
Discharge head
Alignment dowel
Insert the positioning dowel
on the UMP in thishole rjpumps\fig36.eps
Connector'so-ring
(-015 [0.551'' ID x
0.070'' wide])
Pigtail female connector/indexing tab isout
of itssocket - thisisthe incorrect position
when attaching the UMP!
Pigtail female connector/index-
ing tab isfitted in notch of its
socket - thisisthe correct
position when attaching the
UMP!

Installation Installing the Pump
13
2. Place the new gasket on the new UMP so that all holes align (see Figure 8).
Gaskets from competitive UMPs will not seal properly and performance will be
reduced.
3. Align the UMP positioning dowel insert in the proper hole in the discharge head (see Figure 7) and push the
UMP into position using hand force only. The UMP should be snug against the discharge head prior to
installing the UMP retaining bolts.
Use hand force to push the UMP onto the discharge head. If the UMP does not seat
snug against the discharge head, remove the UMP and correct the problem.
4. Install the UMP retaining bolts and lock washers (see Figure 8). Snug and then torque the bolts using a cross
pattern technique. Torque to 7 ft-lbs (11 N•m).
Do not use the bolts to pull the UMP into position. Use the cross pattern technique.
Do not over torque the bolts. Not following instructions may cause parts to fail.
Figure 8. Aligning The UMP Gasket
Installing the Pump
Disconnect, lock out, and tag power at the panel before starting to
service the pump
When servicing equipment, use non-sparking tools and use caution when removing or installing
equipment to avoid generating a spark.
NOTES:
• The Red Jacket STP is designed to operate in a Class 1, Group D atmosphere.
• The manufacturer may recommend new specifications and installation instructions.
• The product temperature must not exceed 105°F (41°C) because the thermal overload protectors in the
submersible motor may trip.
CAUTION
WARNING
WARNING
rjpumps/fig6.eps
UMP
Positioning
dowel
Gasket
Discharge head
WARNING
OFF

Installation Installing the Pump
14
1. Install the riser pipe into the 4-inch tank opening. Before installing pipe threads, apply an adequate amount of
fresh, UL classified for petroleum, non-setting thread sealant. Tighten the riser pipe in the tank until watertight.
2. Measure the distance from the bottom of the tank to the top of the 4-inch riser pipe as shown in Figure 9.
FOR FIXED-LENGTH PUMPS, SKIP TO Step 7.
Figure 9. Measuring Tank
3. Uncoil the pigtail at the top of the packer and lay it flat so it will feed into the packer without knotting or
kinking.
4. Loosen the clinch assembly on the column pipe by unscrewing the set screw in the side of locking nut, then
backing off the locking nut (see Figure 10).
A slight twisting of the UMP will loosen the seals and facilitate adjusting it to the correct
length. Do not rotate piping beyond 1/4 turn.
rjpumps/fig7.eps
Top of 4'' riser
NOTICE
Table of contents
Other Red Jacket Water Pump manuals
Popular Water Pump manuals by other brands

Brinsea
Brinsea AD24 User instructions

Biral
Biral A 802 Installation and operating instructions

XPOtool
XPOtool 52900 user manual

Gardena
Gardena 3000/3 Jet operating instructions

Ariston
Ariston SOLARcomfort Instructions for installation and servicing

Armstrong
Armstrong Design Envelope 4300 Installation and operating instructions

Wilo
Wilo TWU 3 Series Installation and operating instructions

Bosch
Bosch 0 986 580 943 installation instructions

Cosmo
Cosmo Cosmo CPZ Installation and operating instructions

STRANGKO
STRANGKO 8560 930 user manual

BLACKMER
BLACKMER V Series Installation, operation and maintenance instructions

Rossato
Rossato AIR COMBO EVO Installation and Maintenance