red lion PAX2A User manual

1
3.80 (96.52)
(49.53)
(2.54)
(44.45)
3.60 (91.44)
4.14 (105)
1.95
0.10
1.75
1
32
4
PAX2A
1/8 DIN Analog Input Panel Meter
Installation Guide
DIMENSIONS In inches (mm) Note: Recommended minimum clearance (behind the panel) for mounting clip
installation is 2.1" (53.4) H x 5.5" (140) W.
See the Red Lion website at www.redlion.net or the enclosed
USB thumbdrive for a complete user manual
SPECIFICATIONS
POWER:
AC Power: 40 to 250 VAC, 50/60 Hz, 20 VA
DC Power: 21.6 to 250 VDC, 8 W
Isolation: 2300 Vrms for 1 min. to all inputs and outputs.
INPUT CAPABILITIES:
Current Input Ranges:
± 250 µADC ± 2.5 mADC ± 25 mADC
± 250 mADC ± 2 ADC
Voltage Input Ranges:
± 250 mVDC ± 2.0 VDC ± 10 VDC
± 25 VDC ± 100 VDC ± 200 VDC
Thermocouple Inputs:
Types: T, E, J, K, R, S, B, N, C (W5/W26)
Max Continuous Overvoltage: 30 V
RTD Inputs:
Type: 3 or 4 wire, 2 wire can be compensated for lead wire resistance
Excitation current: 100 ohm range: 136.5 µA ±10%
10 ohm range: 2.05 mA ±10%
Max. continuous overload: 30 VDC
Input Type:
100 ohm Pt alpha = .00385 100 ohm Pt alpha = .00392
120 ohm Nickel alpha = .00672 10 ohm Copper alpha = .00427
Resistance Inputs:
Max. continuous overload: 30 VDC
INPUT RANGE COMPLIANCE
100 ohm 0.175 V
999 ohm 1.75 V
9999 ohm 17.5 V
EXCITATION POWER: Jumper selectable
Transmitter Power: +18 VDC, ± 5% @ 50 mA max.
Reference Voltage: + 2 VDC, ± 2%
Compliance: 1KWload min (2 mA max)
Temperature Coefficient: 40 ppm/ºC max.
Reference Current: 1.05 mADC, ± 2%
Compliance: 10 KWload max.
USER INPUTS: Two programmable user inputs
Max. Continuous Input: 30 VDC
Isolation To Sensor Input Common: Not isolated.
ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50 °C
Storage Temperature Range: -40 to 60 °C
Vibration to IEC 68-2-6: Operational 5-150 Hz, 2 g
Shock to IEC 68-2-27: Operational 25 g (10 g relay)
Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Altitude: Up to 2000 meters
CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant
UL Listed: File #E179259
Type 4X Indoor Enclosure rating (Face only)
IP65 Enclosure rating (Face only)
IP20 Enclosure rating (Rear of unit)
CONNECTIONS: High compression cage-clamp terminal block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gauge Capacity: One 14 AWG (2.55 mm) solid,
two 18 AWG (1.02 mm) or four 20 AWG (0.61 mm)
CONSTRUCTION: This unit is rated NEMA 4X/IP65 for indoor use only.
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece
bezel/ case. Flame resistant. Synthetic rubber keypad. Panel gasket and
mounting clip included.
WEIGHT: 8 oz. (226.8 g)
Drawing No. LP0900A
Effective 04/13
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
CUS LISTED
UL
R
3RSD
PROCESS CONTROL EQUIPMENT
2
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired. Do not use this unit to directly
command motors, valves, or other actuators not equipped with safeguards. To do
so can be potentially harmful to persons or equipment in the event of a fault to
the unit.
METER INSTALLATION
The PAX2A meets NEMA 4X/IP65 requirements when properly installed.
The unit is intended to be mounted into an enclosed panel. Prepare the panel
cutout to the dimensions shown. Remove the panel latch from the unit. Slide the
panel gasket over the rear of the unit to the back of the bezel. The unit should
be installed fully assembled. Insert the unit into the panel cutout.
While holding the unit in place, push the panel latch over the rear of the unit
so that the tabs of the panel latch engage in the slots on the case. The panel latch
should be engaged in the farthest forward slot possible. To achieve a proper seal,
tighten the latch screws evenly until the unit is snug in the panel (Torque to
approximately 7 in-lbs [79N-cm]). Do not over-tighten the screws.
Installation Environment
The unit should be installed in a location that does not exceed the operating
temperature and provides good air circulation. Placing the unit near devices that
generate excessive heat should be avoided.
SETTING THE JUMPERS
The PAX2A controller has four jumpers that must be checked and/or changed
prior to applying power. The following Jumper Selection Figures show an
enlargement of the jumper area.
To access the jumpers, remove the meter base from the case by firmly
squeezing and pulling back on the side rear finger tabs. This should lower the
latch below the case slot (which is located just in front of the finger tabs). It is
recommended to release the latch on one side, then start the other side latch.
Warning: Exposed line voltage exists on the circuit boards. Remove all
power to the meter and load circuits before accessing inside of the
meter.
INPUT RANGE JUMPERS
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION:
Risk of electric shock.
PANEL
LATCHING
SLOTS
BEZEL
PANEL
GASKET
PANEL
LATCH
LATCHING
TABS
PANEL
MOUNTING
SCREWS
-.00
(92 )
-.0
+.8
3.62 +.03
(45 )
1.77
-.0
+.5
-.00
+.02
PANEL CUT-OUT
Main
Circuit
Board
REAR TERMINALS
FRONT DISPLAY
I
T
V
RTD
JUMPER
LOCATIONS
100
Finger
Tab
Finger
Tab
V
EXCITATION OUTPUT JUMPER
INPUT RANGE JUMPERS
18V @ 50mA
2V REF.
1.05 mA REF.
10 ohm RTD
100 ohm RTD
RTD INPUTS
CURRENT INPUTS
2 A
.25 A
.025 A
.0025 A
250 µA
TEMPERATURE
VOLTAGE
THERMOCOUPLE/
VOLTAGE
SELECTION
LV - 250mV/2V/100Ω/1KΩ
M - 10V/100V
HV - 25V/200V/10KΩ
VOLTAGE/RESISTANCE
INPUTS
REAR TERMINALS
3
POWER WIRING
The power supplied to the meter shall employ a 15 Amp UL
approved circuit breaker for AC input and a 1 Amp, 250 V UL
approved fuse for DC input. It shall be easily accessible and
marked as a disconnecting device to the installed unit. This device
is not directly intended for connection to the mains without a
reliable means to reduce transient over-voltages to 1500 V.
1
2
AC/DC
AC/DC
VOLTAGE/RESISTANCE/CURRENT INPUT SIGNAL WIRING
IMPORTANT: Before connecting signal wires, the Input Range Jumpers and Excitation Jumper should be verified for proper position.
Process/Current
Signal
(external powered)
Voltage Signal Process/Current Signal
(2 wire requiring 18V
excitation)
Excitation Jumper: 18 V
6 7 8
+
200VDC MAX.
V-TC-RTD IN
I INPUT
INP COMM
Current Signal (3 wire
requiring 18 V excitation)
Terminal 3: +Volt supply
Terminal 6: +ADC (signal)
Terminal 8: -ADC (common)
Excitation Jumper: 18 V
Voltage Signal (3 wire
requiring 18 V excitation)
Terminal 3: +Volt supply
Terminal 7: +VDC (signal)
Terminal 8: -VDC (common)
Excitation Jumper: 18 V
68
2A DC MAX.
I INPUT
INP COMM
Load
-
+
-
+
Resistance Signal
(2 wire requiring excitation)
Terminal 3: Jumper to
terminal 7
Terminal 7: Resistance
Terminal 8: Resistance
Excitation Jumper:
1.05 mA REF.
T/V Jumper: V position
Voltage/Resistance Input Jumper:
Set per input signal
3 7 8
V EXC
INP COMM
V-TC-RTD-IN
1.05 mA
REF.
10K MAX
Potentiometer Signal as Voltage Input
(3 wire requiring excitation)
Terminal 3: High end of pot.
Terminal 7: Wiper
Terminal 8: Low end of pot.
Excitation Jumper: 2 V REF.
T/V Jumper: V
Voltage/Resistance Input Jumper: 2 Volt
Module 1 Input Range: 2 Volt
Note: The Apply signal scaling style should be
used because the signal will be in volts.
6 7 83
V-TC-RTD-IN
I INPUT
V EXC
INP COMM
+
3 WIRE TRANSMITTER
_
VoutIout
3 7 8
Rmin=1KΩ
V EXC
INP COMM
V-TC-RTD-IN
2V REF.
2V
INPUT
5 63
RTD EXC
V EXEC
I INPUT
2 WIRE
TRANSMITTER
-+
4
COMM
CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safety of the controller application, the sensor input
common must be suitably isolated from hazardous live earth referenced voltages; or input common must be at protective earth ground potential. If not,
hazardous live voltage may be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given to the
potential of the user input common with respect to earth common; and the common of the isolated plug-in cards with respect to input common.
1
2
AC/DC
AC/DC
+
-
1
2
AC/DC
AC/DC
+
-
OR
AC Power DC Power
TEMPERATURE INPUT SIGNAL WIRING
IMPORTANT: Before connecting signal wires, verify the T/V Jumper is in the T position.
3-Wire RTDThermocouple 2-Wire RTD
578
RTD EXC
V-TC-RTD-IN
INP COMM
Sense Lead
Jumper
578
RTD EXC
V-TC-RTD-IN
INP COMM
Sense Lead
RTD (Excitation)
78
+
V-TC-RTD-IN
INP COMM
CAUTION: Sensor input common is NOT isolated from user input common. In
order to preserve the safety of the controller application, the sensor input
common must be suitably isolated from hazardous live earth referenced
voltages; or input common must be at protective earth ground potential.
If not, hazardous live voltage may be present at the User Inputs and User
Input Common terminals. Appropriate considerations must then be given to
the potential of the user input common with respect to earth common; and
the common of the isolated plug-in cards with respect to input common.
USER INPUT WIRING
If not using User Inputs, then skip this section. User Input terminal does not need to be wired in order to
remain in the inactive state.
Sourcing Logic
(UACt Hi)
When the UACt parameter is programmed
to Hi, the user inputs of the controller are
internally pulled down to 0 V with 20
KWresistance. The input is active when
a voltage greater than 2.2 VDC is
applied.
USER COMM
USER 2
USER 1
10 119
USER INPUTS
OR
Sinking Logic
(UACt Lo)
When the UACt parameter is
programmed to Lo, the user inputs
of the controller are internally
pulled up to +3.3 V with 20 KW
resistance. The input is active
when it is pulled low (<1.1 V).
10
91
1
+
-
(30V max.)
SUPPLY
V
USER COMM
USER 2
USER 1
USER INPUTS
OR
SETPOINT (ALARMS) WIRING
SERIAL COMMUNICATION WIRING
ANALOG OUTPUT WIRING



See appropriate plug-in card
bulletin for wiring details.
4
20 Willow Springs Circle | York, PA 17406 USA
+1 (717) 767-6511 | [email protected] | www.redlion.net
LIMITED WARRANTY
The Company warrants the products it manufactures against defects in materials and workmanship for a
period limited to two years from the date of shipment, provided the products have been stored, handled,
installed, and used under proper conditions. The Company’s liability under this limited warranty shall
extend only to the repair or replacement of a defective product, at The Company’s option. The Company
disclaims all liability for any afrmation, promise or representation with respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against
damages, claims, and expenses arising out of subsequent sales of RLC products or products containing
components manufactured by RLC and based upon personal injuries, deaths, property damage, lost prots,
and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable,
including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and
liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in
effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those
expressly contained herein. The Customer acknowledges the disclaimers and limitations contained herein
and relies on no other warranties or afrmations.
ORDERING INFORMATION
DESCRIPTION PART NUMBER
Universal DC Analog Input Panel Meter PAX2A000
Dual Setpoint Relay Output Card PAXCDS10
Quad Setpoint Relay Output Card PAXCDS20
Quad Setpoint Sinking Open Collector Output Card PAXCDS30
Quad Setpoint Sourcing Open Collector Output Card PAXCDS40
RS485 Serial Communications Card with Terminal Block PAXCDC10
Extended RS485 Serial Communications Card with Dual RJ11 Connector PAXCDC1C
RS232 Serial Communications Card with Terminal Block PAXCDC20
Extended RS232 Serial Communications Card with 9 Pin D Connector PAXCDC2C
DeviceNet Communications Card PAXCDC30
Profibus-DP Communications Card PAXCDC50
Analog Output Card PAXCDL10

Other manuals for PAX2A

1

This manual suits for next models

2

Other red lion Measuring Instrument manuals

red lion PAX2D User manual

red lion

red lion PAX2D User manual

red lion CUB4I User manual

red lion

red lion CUB4I User manual

red lion APOLLO IMR Series User manual

red lion

red lion APOLLO IMR Series User manual

red lion PAXS0010 User manual

red lion

red lion PAXS0010 User manual

red lion CUB4RT User manual

red lion

red lion CUB4RT User manual

red lion PAX Lite Series User manual

red lion

red lion PAX Lite Series User manual

red lion CUB5VR00 User manual

red lion

red lion CUB5VR00 User manual

red lion Legend Plus Series User manual

red lion

red lion Legend Plus Series User manual

red lion CUB4RT User manual

red lion

red lion CUB4RT User manual

red lion PAXLTC User manual

red lion

red lion PAXLTC User manual

red lion CUB 5TC-K User manual

red lion

red lion CUB 5TC-K User manual

red lion IMD1 User manual

red lion

red lion IMD1 User manual

red lion APOLLO IMS Series User manual

red lion

red lion APOLLO IMS Series User manual

red lion CUB5 Series User manual

red lion

red lion CUB5 Series User manual

red lion PAX LITE PAXLCR Series User manual

red lion

red lion PAX LITE PAXLCR Series User manual

red lion PAX2D User manual

red lion

red lion PAX2D User manual

red lion PAX LITE User manual

red lion

red lion PAX LITE User manual

red lion PAX Lite PAXLHV User manual

red lion

red lion PAX Lite PAXLHV User manual

red lion CUB5P User manual

red lion

red lion CUB5P User manual

red lion PAX2D User manual

red lion

red lion PAX2D User manual

red lion PAXDR Series Instruction Manual

red lion

red lion PAXDR Series Instruction Manual

red lion PAXLSG User manual

red lion

red lion PAXLSG User manual

red lion PAXI-1/8 User manual

red lion

red lion PAXI-1/8 User manual

red lion APLR User manual

red lion

red lion APLR User manual

Popular Measuring Instrument manuals by other brands

Siemens SENTRON PAC4220 manual

Siemens

Siemens SENTRON PAC4220 manual

International Light Technologies ILT5000 instruction manual

International Light Technologies

International Light Technologies ILT5000 instruction manual

Hanna Instruments HI 771 instructions

Hanna Instruments

Hanna Instruments HI 771 instructions

HomeFree iDEU 800-2 Operational guide

HomeFree

HomeFree iDEU 800-2 Operational guide

Hydreka HYDRINS 2 installation manual

Hydreka

Hydreka HYDRINS 2 installation manual

Ametek 888 user manual

Ametek

Ametek 888 user manual

Golf Buddy AIM L11 user guide

Golf Buddy

Golf Buddy AIM L11 user guide

Wavetek Meterman CT-238 Operator's manual

Wavetek

Wavetek Meterman CT-238 Operator's manual

Extech Instruments SDL600-NIST user manual

Extech Instruments

Extech Instruments SDL600-NIST user manual

CESVA FP122 user manual

CESVA

CESVA FP122 user manual

Conrad VOLTCRAFT CO-50 operating instructions

Conrad

Conrad VOLTCRAFT CO-50 operating instructions

Brüel & Kjær 2007 Instructions and applications

Brüel & Kjær

Brüel & Kjær 2007 Instructions and applications

Endress+Hauser Levelflex FMP53 operating instructions

Endress+Hauser

Endress+Hauser Levelflex FMP53 operating instructions

EuroLite VLS-1600RGB 40K user manual

EuroLite

EuroLite VLS-1600RGB 40K user manual

Greenheck Sure-Aire 386719 Installation, operation and maintenance manual

Greenheck

Greenheck Sure-Aire 386719 Installation, operation and maintenance manual

Unior 1721 manual

Unior

Unior 1721 manual

Rigel MULTI-FLO instruction manual

Rigel

Rigel MULTI-FLO instruction manual

Honeywell Q340A installation instructions

Honeywell

Honeywell Q340A installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.