REMEHA QUINTA PRO RANGE - SUGGESTED SCHEMATICS WITH CONTROL AND POWER WIRING DETAILS
QUINTA PRO RANGE
Suggested Schematics with Control
and Power Wiring Details
QUINTA PRO RANGE OUTPUTS
QP30: 8.0 - 31.4 kW
QP45: 8.0 - 43.0 kW
QP65: 12.0 - 65.0 kW
QP90: 14.1 - 89.5 kW
QP115: 16.6 - 114.0 kW
High efficiency wall hung condensing boiler
with ultra low NOx emissions
2
Schematics with Control Page
Control Options for the Quinta Pro Series of Boilers p3
External controls by others
Simple Quinta Pro boiler domestic installation - p4-5
Typical ‘S’ plan, heating and hot water
Single Quinta Pro boiler, heating only p6-7
Single Quinta Pro boiler, heating only with low loss header p8-9
Single Quinta Pro boiler, heating and priority hot water using a low loss header p10-13
and pump or valve kit
Remeha supplied controls
Single Quinta Pro boiler, heating only using the iSense controller p14-16
(room/weather compensation)
Single Quinta Pro boiler, heating and Priority DHW using the iSense controller p17-19
(room or outside compensation)
Multiple Quinta Pro boilers HTG only using a low loss header with the Celcia MC4 p20-21
and iSense (room or outside compensation)
Multiple Quinta Pro boilers HTG and Priority DHW using a low loss header with p22-24
the Celcia MC4 and iSense (room or outside compensation)
Multiple boilers, heating and hot water using a low loss header with the p25-30
iSense Pro controller (optimising/weather compensated control for dual
heating zone and hot water from all or single boilers)
Connecting multiple boilers with external control interlocks and alarm p31
and run signals
Quinta Pro nominal flow rates and boiler resistances p31
Note: We supply the Grundfoss 25/80 (Part No. S101621) as standard for the full Quinta Pro
range. This will alter due to changes in EU regulations. The Quinta Pro 30 will operate on speed
1, the 45 and 65 will operate on speed 2, and the 90 and 115 will operate on speed 3. They are
intended to act as a shunt pump. In the layouts illustrated, they are designed to operate on a
20ºC Delta TΔ. If using a pump without a low loss header, please take into account both the
boiler and system resistance and also when being used in conjunction with a calorifier and low
loss header. Contact our sales or technical departments for further assistance.
The hydraulic and control layouts illustrated in this brochure are for guidance only and must be
used in conjunction with the Quinta Pro and iSense Pro installation and service manuals. They
do not constitute a full system design. Remeha Commercial accept no liability for any loss or
damage rising from any errors or omissions that may be inadvertently contained in this booklet.
When connecting a control cable to the OT terminals on the main control PCB, disconnect and
remove the factory fitted lead connected to the IF- 01 PCB.
Some earths and neutrals are omitted for clarity.
All systems, mechanical and electrical, must be installed to the current regulations by a suitably
qualified engineer.
3
Control Options for the Quinta Pro 30 / 45 / 65 / 90 and 115 series
The Remeha range of Quinta Pro boilers are supplied as standard with an “Open Therm”
control interface which enables direct weather compensation using Remeha single and
multi boiler controls. The customer can choose to use external control options supplied
by others without affecting boiler performance.
Supplied by others
On/off control:
• Boiler requires a permanent 230v supply and is enabled using a volt free switch/relay.
The boiler will modulate its output to maintain the flow temperature setpoint,
normally 80ºC, but can be adjusted on the boiler between 20ºC and 90ºC
0-10 volt control:
• Boiler requires a permanent 230v supply and is enabled and modulated using a 0-10
volt signal from a Building Management System or quality panel mounted optimiser/
compensator. The control can be flow temperature or percentage output based
• Temperature based example: if 56ºC ow is required from the boiler, the control will need to
supply 5.6v. The output will be modulated to maintain a flow temperature of 56ºC
• Percentage based example: if the control logic requires that a boiler should be running
at 33%, the control will need to supply 3.3v to the boiler. The boiler will run at 33% output
with a variable flow temperature
• Applications - domestic/commercial and industrial installations, with a variety of heat
emitters, DHW via calorifiers or plate heat exchangers, and installations where a variety
of different temperature zones are required at the same time
Supplied by Remeha Commercial as optional extras
iSense Controller - Single/multi boiler weather compensating controller
• A simple to operate room/boiler mounted thermostat/timer which can be used with a
combination of outside/room and flow temperature sensors to vary the boiler output
(flow temp) to suit weather conditions. The iSense can be installed in a reference room
and can also be mounted in a boiler when used in weather compensated mode.
It has a 7 day timer with multiple on/off and night setback periods, holiday function,
frost protection and manual override
Celcia MC4
• Multiple boiler weather compensating controller with step control (up to 4 boilers)
to be used in conjunction with the iSense controller
• The iSense can be mounted in a reference room, in the plant room or on the boiler
• The MC4 is mounted adjacent to the boiler group
iSense Pro -Multiple boiler weather compensating controller with sequence control (up to 8 boilers)
• Optimiser compensator which can provide 2 timed heating zones and uses a combination
of outside, flow and room temperature to vary the boiler output (flow temp) to suit weather
conditions. Can also provide time control to DHW circuit. The iSense Pro controller is mounted
in a wall box when used with the Quinta Pro and is complete with timer, night setback, frost
protection and pump cycling protection. The iSense Pro controller will sequence and rotate
the lead boiler on multiple installations. This controller also has the ability to accept remote
extension timers, supplied as an optional extra, which will allow the heating system to run
on daytime compensation outside the normal timed settings without need for access or
interference to the boiler or controller. Ideal for school lettings/night classes etc.
Note: We do not advise using a combination of external and built-in controls as in most cases
there can be no interface between them; it is likely they will ‘conflict’ with each other
and neither will work properly. The exception to this is when using the iSense Pro kit KT1154
in conjunction with a Remote BMS controller (see page 31).
4
Simple Quinta Pro boiler domestic installation
Typical ‘S’ plan, heating and hot water
(Time and temperature control by others)
Power Supply
• Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected
to the factory fitted fly lead
Boiler Control Settings
(see 5.7.2 in technical documentation)
• Set boiler code P1 to the required ow temp i.e. 80 = 80ºC (system design requirements)
• Boiler will recognise the control being used
• Use the zone valve end switches to provide the volt free switch pair on OT on the main
control PCB to enable the boiler
• Boiler output will vary between 18% part load set point and 100% full load set point
to achieve the boiler flow set point (code P1)
System Components
(not supplied)
• Simple two channel time clock providing 230v switched supplies to control
heating and domestic hot water
• System pump
• Cylinder thermostat
• Room thermostat
• HTG and DHW zone valves c/w a single end switch (closes on valve fully open)
• Wiring centre
Note:
1. Maintain polarity on all connections
2. Some Neutral and Earth connections have been omitted for clarity
3. The schematic is for guidance only and does not constitute a design
4. Heating and hot water can be operated independently or simultaneously
with this layout provided the control selected will allow it
5
Shunt
O
QP 001S
QP 001SA
Quinta Pro single boiler heating and domestic hot water, usinga
simple ‘S’ Plan
Shunt
O
QP 001S
QP 001SA
Quinta Pro single boiler heating and domestic hot water, usinga
simple ‘S’ Plan
QP 001S
QP 001SA
Single Quinta Pro boiler, heating and domestic hot water,
using a simple ‘S’ Plan
6
Single Quinta Pro boiler, heating only
(Time and temperature control by others)
Power Supply
• Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected to the
factory fitted fly lead
Boiler Interlocks
(for pressure switches etc.)
• Safety Interlock - remove the existing link and t volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed
Indication Controls
(to report actual function)
• Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
• Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)
Boiler Control Settings
(see 5.7.2 in technical documentation)
• Connect the external controls (volt free) to the OT terminals on the main control PCB (on/off).
Boiler will modulate to the set point set in P1 or the 0 -10v terminals on the IF-01.
Control option based on temperature or output can be adjusted on the jumper on the IF-01.
(See installation manual for full details)
• Boiler will recognise the type of control being used
• Set boiler code P1 to the required ow temp i.e. 80 = 80ºC (system design requirements)
• Pump: connect the heating pump to terminals shown on the PCB SCU - S02 max 400Va
(1.5 amp). Alternatively, pump can be connected to the fly lead supplied with the boiler
to plug X81; this a max duty of 200w (0.8 amp)
7
7
QP 002
QP 002A
Quinta Pro single boiler heating only
7
QP 002
QP 002A
Quinta Pro single boiler heating only
QP 002
QP 002A
Single Quinta Pro boiler, heating only
8
Single Quinta Pro boiler, heating only with low loss header
(Time and temperature control by others)
Power Supply
• Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected
to the factory fitted fly lead
Boiler Interlocks
(for pressure switches etc.)
• Safety Interlock - remove the existing link and t volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed
Indication Controls
(to report actual function)
• Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
• Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)
Boiler Control Settings
(see 5.7.2 in technical documentation)
• Boiler will recognise the type of control being used
• Set boiler code P1 to the required ow temp i.e. 80 = 80ºC (system design requirements)
• Connect the external controls (volt free) to the OT terminals on the main control PCB
(on/off). Boiler will modulate to the set point set in P1 or the 0 -10v terminals on the IF- 01.
Control option based on temperature or output can be adjusted on the jumper on the IF- 01.
(See installation manual for full details)
• Pumps: connect pump PM1 to the heating pump terminals shown on the PCB SCU - S02
max 400Va (1.5 amp). Connect the shunt pump SH1 to the pump y lead supplied with the
boiler to plug X81
9
9
QP 003
QP 003A
Quinta Pro single boiler heating only with loss heading
9
QP 003
QP 003A
Quinta Pro single boiler heating only with loss heading
QP 003
QP 003A
Single Quinta Pro boiler, heating only with low loss header
10
Single Quinta Pro boiler, heating with priority hot water
using a low loss header and pump or valve kit
(Time and temperature control by others)
Power Supply
• Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected
to the factory fitted fly lead
Boiler Interlocks
(for pressure switches etc.)
• Safety Interlock - remove the existing link and t volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed
Indication Controls
(to report actual function)
• Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
• Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)
Boiler Control Settings
(see 5.7.2 in technical documentation)
• Boiler will recognise the type of control being used
• Set boiler code P1 to the required ow temp i.e. 80 = 80ºC (system design requirements)
• Connect the external controls (volt free) to the OT terminals on the main control PCB
(on/off). Boiler will modulate to the set point set in P1
• Pumps: connect pump PM1 to the heating pump terminals shown on the PCB SCU - S02 max
400Va (1.5 amp). Connect the shunt pump SH1 to the y lead supplied with the boiler to plug
X81 max 200w (0.8 amp). On pump installations, connect the shunt pump to the terminals
shown; a contactor or relay will be required if loading exceeds 1.5 amps
• 3-way valve: on the 3-way valve option, connect the valve to the terminals shown on the PCB
SCU – S02
Important:
When using the Remeha supplied low loss header and pump kit and the DHW diverting valve or
primary pump kit, the calorifier must be sited within 3M of the boiler. In both cases, the DHW
cylinder must be a high recovery unit capable of accepting the full or adjusted DHW output of the
boiler being used (reference parameter P18).
11
11
QP 004
QP 004A
Quinta Pro single boiler heating with priority hot water using a low
loss header. Three way valve DHW priority Quinta Pro 30/45/65 only
Quinta Pro single boiler heating with priority hot water using a
low loss header pump option DHW priority can be used on all
Quinta Pro range
11
QP 004
QP 004A
Quinta Pro single boiler heating with priority hot water using a low
loss header. Three way valve DHW priority Quinta Pro 30/45/65 only
Quinta Pro single boiler heating with priority hot water using a
low loss header pump option DHW priority can be used on all
Quinta Pro range
QP 004
QP 004A
Single Quinta Pro boiler, heating with priority hot water using a low
loss header. 3-way valve DHW priority Quinta Pro 30/45/65 only
Single Quinta Pro boiler, heating with priority hot water using a
low loss header pump option. DHW priority can be used on all
Quinta Pro range
12
3 way valve
Wiring detail of controls when using a
Remeha Commercial Calorifier, a volt free
HWS time control and a 2 Port spring return
valve. Ifusing a different type of calorifier, please
follow manufacturer’s instructions regarding
control and wiring details
2 C 1 2 C 1
Factory tted
supply lead to
be connected
to a 230v fused
spur for boiler
permanent supply
Time/temp control
HTG (volt free)
Time control DHW
(volt free)
230v fused
supply for
2 port valve
(connected to
boiler supply)
2 Port
spring
return
valve Cylinder
Thermostat
Note:Control PCBs are shown diagrammatically
Earths are omitted forclarity
Boiler HWS time
control
230v Fused
Supply
(connected to
boilersupply)
Boiler Signal out (volt free)
Boiler Signal in (volt free)
Live
Neutral
Thermostat
2 C 1 2 C 1
SafetyLimiter
2 Port Spring Return
Motorised Valve
Orange
Grey
Blue
Brown
Tdhw
Contactororrelay required if both pumps
PM1 and SH1 loading exceeds1.5amps
Pump
PM1
Pump
PM2
Shunt pump
SH1
Wiring detail of controls when using a Remeha
Commercial with a 2Calorifier Port spring return
valve. If
usi
ng a different type of calorifier, please
follow manufacturer’s instructions regarding
control and wiring details
QP 004C
fi
Factory tted
supply lead to
be connected
to a 230v fused
spur for boiler
permanent supply
fi
Time/temp control
HTG (volt free)
Time control DHW
(volt free) 2 Port
spring
return
valve
230v fused
supply for
2 port valve
(connected to
boiler supply)
Boiler Signal out (volt free)
Boiler Signal in (volt free)
Live
Neutral
2 Port Spring Return
Motorised Valve
Orange
Grey
Blue
Brown
Thermostat SafetyLimiter
Note:Control PCBs are shown diagrammatically
Earths are omitted forclarity
Boiler HWS time
control
230v Fused
Supply
(connected to
boilersupply)
Tdhw
Cylinder
Thermostat
3 way valve
Wiring detail of controls when using a
Remeha Commercial Calorifier, a volt free
HWS time control and a 2 Port spring return
valve. Ifusing a different type of calorifier, please
follow manufacturer’s instructions regarding
control and wiring details
2 C 1 2 C 1
Factory tted
supply lead to
be connected
to a 230v fused
spur for boiler
permanent supply
Time/temp control
HTG (volt free)
Time control DHW
(volt free)
230v fused
supply for
2 port valve
(connected to
boiler supply)
2 Port
spring
return
valve Cylinder
Thermostat
Note:Control PCBs are shown diagrammatically
Earths are omitted forclarity
Boiler HWS time
control
230v Fused
Supply
(connected to
boilersupply)
Boiler Signal out (volt free)
Boiler Signal in (volt free)
Live
Neutral
Thermostat
2 C 1 2 C 1
SafetyLimiter
2 Port Spring Return
Motorised Valve
Orange
Grey
Blue
Brown
Tdhw
Contactororrelay required if both pumps
PM1 and SH1 loading exceeds1.5amps
Pump
PM1
Pump
PM2
Shunt pump
SH1
Wiring detail of controls when using a Remeha
Commercial with a 2Calorifier Port spring return
valve. If
usi
ng a different type of calorifier, please
follow manufacturer’s instructions regarding
control and wiring details
QP 004C
fi
Factory tted
supply lead to
be connected
to a 230v fused
spur for boiler
permanent supply
fi
Time/temp control
HTG (volt free)
Time control DHW
(volt free) 2 Port
spring
return
valve
230v fused
supply for
2 port valve
(connected to
boiler supply)
Boiler Signal out (volt free)
Boiler Signal in (volt free)
Live
Neutral
2 Port Spring Return
Motorised Valve
Orange
Grey
Blue
Brown
Thermostat SafetyLimiter
Note:Control PCBs are shown diagrammatically
Earths are omitted forclarity
Boiler HWS time
control
230v Fused
Supply
(connected to
boilersupply)
Tdhw
Cylinder
Thermostat
QP 004B
Single Quinta Pro boiler, heating with priority hot water using a
low loss header (3-way valve option)
QP 004C
Single Quinta Pro boiler, heating with priority hot water using a
low loss header (Pump option)
13
13
Boiler 230v Fused Supply
Boiler Signal out (volt free)
volt free)
Boiler Signal in (
Live
Neutral
2 C 1 2 C 1
R L
QP004D
QP004E
13
Boiler 230v Fused Supply
Boiler Signal out (volt free)
volt free)
Boiler Signal in (
Live
Neutral
2 C 1 2 C 1
R L
QP004D
QP004E
Wiring detail of controls when using a Remeha
Commercial Calorifier with a 2 Port spring
return valve and an iSense or Open Therm
controller. If using a different type of calorifier,
please follow manufacturer’s instructions
regarding control and wiring details.
Set Boiler parameter P37 to 0.
Note: Calorifier Thermostat temperature should
be set 5oC higher than the iSense control hot
water setting.
Wiring detail of controls when using a Remeha
Commercial Calorifier. If using a different type
of calorifier, please follow manufacturer’s
instructions regarding control and wiring details.
QP 004D
QP 004E
14
Single Quinta Pro boiler, heating only using the iSense controller
(room or weather or room/weather compensated)
Power Supply
• Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected to the
factory fitted fly lead
Boiler Interlocks
(for pressure switches etc.)
• Safety Interlock - remove the existing link and t volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed
Indication Controls
(to report actual function)
• Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
• Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)
Boiler Control Settings
(see 5.7.2 in technical documentation)
• Set boiler code P1 to the required ow temp i.e. 80 = 80ºC (system design requirements)
• Boiler will recognise the type of control setting used
Fitting the Control
• For room compensation, t the control in a normally occupied reference room within the
building being heated
• For room/weather compensation, an outside sensor can be tted. If requiring weather
compensation only, the iSense can be fitted into the boiler control panel. In this case an
outside sensor must be fitted and connected to ‘Tout’ in the boiler on the main control PCB
• Connect the 2 wire control to the OT terminals on the main PCB. Please refer to the
instructions supplied with the iSense controller package
• Set up the controller to suit the design requirements and occupancy times for HTG in
accordance with the instruction documents supplied with the controller
Note: The iSense controller can provide both room or weather compensation or room and
weather compensation.
Room compensation = iSense tted in a reference room, no outside sensor
Weather compensation = iSense tted in a boiler or plant room, outside sensor required
Room/weather compensation = iSense tted in a reference room, outside sensor required
15
15
1.6M
Suggested height in room
Normal position for the iSense controller
mounted in reference room within the building
(room compensation)
100m Max
230v Supply
Condensate
Gas
Flow
Return
Pump PM1
1.6M
Suggested height in room
Normal position for the iSense controller
mounted in reference room within the building
100m Max
230v Supply
Condensate
Gas
Flow
Return
Pump PM1
iSense can be fitted in the boiler if
used for weather compensation only
100m Max
Outside sensor
on North
facing wall
QP 005
Quinta Pro single boiler heating only room compensation using the
iSense controller
QP 005A
Quinta Pro single boiler heating only weather compensation using
the iSense controller
15
1.6M
Suggested height in room
Normal position for the iSense controller
mounted in reference room within the building
(room compensation)
100m Max
230v Supply
Condensate
Gas
Flow
Return
Pump PM1
1.6M
Suggested height in room
Normal position for the iSense controller
mounted in reference room within the building
100m Max
230v Supply
Condensate
Gas
Flow
Return
Pump PM1
iSense can be fitted in the boiler if
used for weather compensation only
100m Max
Outside sensor
on North
facing wall
QP 005
Quinta Pro single boiler heating only room compensation using the
iSense controller
QP 005A
Quinta Pro single boiler heating only weather compensation using
the iSense controller
QP 005
Single Quinta Pro boiler, heating only, room compensation using the
iSense controller
QP 005A
Single Quinta Pro boiler, heating only, weather compensation using
the iSense controller
16
Factory fitted
supply lead to
be connected
to a 230v fused
spur for boiler
permanent supply
Note: Control PCBs are shown diagrammatically
Earths are omitted for clarity
Pump PM1
iSense controller
O T
Factory fitted
supply lead to
be connected
to a 230v fused
spur for boiler
permanent supply
Note: Control PCBs are shown diagrammatically
Earths are omitted for clarity
iSense controller
Pump PM1
Outside Sensor
O T
QP 005B
Single Quinta Pro boiler heating only using the iSense controller
QP 005C
Single Quinta Pro boiler heating only using the iSense controller
(room/weather or weather compensation)
Single Quinta Pro boiler, heating only using the iSense controller
(room/weather or weather compensation)
Single Quinta Pro boiler, heating only using the iSense controller
QP 005C
Factory fitted
supply lead to
be connected
to a 230v fused
spur for boiler
permanent supply
Note: Control PCBs are shown diagrammatically
Earths are omitted for clarity
Pump PM1
iSense controller
O T
Factory fitted
supply lead to
be connected
to a 230v fused
spur for boiler
permanent supply
Note: Control PCBs are shown diagrammatically
Earths are omitted for clarity
iSense controller
Pump PM1
Outside Sensor
O T
QP 005B
Single Quinta Pro boiler heating only using the iSense controller
QP 005C
Single Quinta Pro boiler heating only using the iSense controller
(room/weather or weather compensation)
QP 005B
17
Single Quinta Pro boiler, heating with hot water priority, heating
room or weather compensated with the iSense controller
(Optimising/Weather compensated heating with timed hot water)
Power Supply
• Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected to the
factory fitted fly lead
Boiler Interlocks
(for pressure switches etc.)
• Safety Interlock - remove the existing link and t volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed
Indication Controls
(to report actual function)
• Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
• Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)
Boiler Control Settings
(see 5.7.2 in technical documentation)
• Set boiler code P1 to the required ow temp i.e. 80 = 80ºC (system design requirements)
• Boiler will recognise the type of control setting used
• Fit the control in a normally occupied reference room within the building being heated.
Refer to the instructions supplied with the control package
• Set up the controller to suit the design requirements and occupancy times for heating and
hot water in accordance with the instruction documents supplied with the controller
• Install the outside sensor on a North facing wall in a sheltered position and connect to
terminals ‘Tout’ on the main PCB of the boiler
DHW Control
Diverting valve option:
Connect valve to the terminals shown, connect shunt pump PM1 to the terminals shown.
Connect valve ports AB, A and B as shown (AB = boiler, A = hot water, B = heating)
Primary Pump option:
Connect pump PM1 to the terminals shown
Connect shunt pump to the terminals shown
Note: This option will only operate with a calorifier sensor. This is to allow the iSense to control
the hot water times.
18
18
1.6M
Suggested height in room
Normal position for the iSense controller
mounted in reference room within the building
(room compensation)
100m Max
230v
Supply
Condensate
Gas
Flow
Return
Pump PM1
100m Max
DHW Sensor
DHW Diverting valve
A
AB
B
2 Port spring return valve Bypass valve
1.6M
Suggested height in room
Normal position for the iSense controller
mounted in reference room within the building
(room compensation)
100m Max
230v
Supply
Condensate
Gas
Flow
Return
Pump PM1
100m Max
DHW Sensor
2 Port spring
return valve
Bypass valve
Pump PM2
Outside sensor on
North facing wall
iSense can be fitted into boiler
control panel for outside
weather compensation only
QP 006
Quinta Pro single boiler heating and hot water priority. Heating room
or outside weather compensated with the iSense controller.
Three way valve hot water priority Quinta Pro 30/45/65 only
QP 006A
Quinta Pro single boiler heating and hot water priority. Heating room
or outside weather compensation with the iSense controller.
Pump option hot water priority can be used on all Quinta Pro range
18
1.6M
Suggested height in room
Normal position for the iSense controller
mounted in reference room within the building
(room compensation)
100m Max
230v
Supply
Condensate
Gas
Flow
Return
Pump PM1
100m Max
DHW Sensor
DHW Diverting valve
A
AB
B
2 Port spring return valve Bypass valve
1.6M
Suggested height in room
Normal position for the iSense controller
mounted in reference room within the building
(room compensation)
100m Max
230v
Supply
Condensate
Gas
Flow
Return
Pump PM1
100m Max
DHW Sensor
2 Port spring
return valve
Bypass valve
Pump PM2
Outside sensor on
North facing wall
iSense can be fitted into boiler
control panel for outside
weather compensation only
QP 006
Quinta Pro single boiler heating and hot water priority. Heating room
or outside weather compensated with the iSense controller.
Three way valve hot water priority Quinta Pro 30/45/65 only
QP 006A
Quinta Pro single boiler heating and hot water priority. Heating room
or outside weather compensation with the iSense controller.
Pump option hot water priority can be used on all Quinta Pro range
QP 006
Single Quinta Pro boiler, heating and hot water priority. Heating
room or outside weather compensated with the iSense controller.
3-way valve hot water priority Quinta Pro 30/45/65 only
QP 006A
Single Quinta Pro boiler, heating and hot water priority. Heating
room or outside weather compensation with the iSense controller.
Pump option hot water priority can be used on all Quinta Pro range
19
Single Quinta Pro boiler, heating and priority hot water
using the iSense controller (Pump option)
QP 006B
Single Quinta Pro boiler, heating and priority hot water
using the iSense controller (3 Port valve option)
QP 006C
Factory fitted
supply lead to
be connected
to a 230v fused
spur for boiler
permanent supply
Note: Control PCBs are shown diagrammatically
Earths are omitted for clarity
Boiler parameter P37 must be set to 0
See drawing QP004E
Pump PM1
iSense controller
O T
230v fused
Outside
Sensor 3 way valve
supply for
2 port valve
2 Port
spring
return
valve
Calorifier
Sensor
Factory fitted
supply lead to
be connected
to a 230v fused
spur for boiler
permanent supply
Note: Control PCBs are shown diagrammatically
Earths are omitted for clarity
iSense controller
O T
Pump PM1 Pump PM2
230v 3amp fuses
Outside
Sensor
Calorifier
Sensor
supply for
2 port valve
2 Port
spring
return
valve
Boiler parameter P37 must be set to 0
See drawing QP004E
20
Multiple Quinta Pro boilers, heating only, outside weather or room
compensation with the Celcia MC4 and iSense controller with a low
loss header (Optimising/weather compensated)
Power Supply
• Boilers require a permanent 230v single phase supply fused at 6.3 amps connected to the
factory fitted fly lead
Boiler Interlocks
(for pressure switches etc.)
• Safety Interlock - remove the existing link and t volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed
Indication Controls
(to report actual function)
• Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
• Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)
Fitting the Controls
• Fit the iSense controller in a normally occupied reference room within the building being
heated if room and weather compensation is required. If weather only is required,
the iSense can be fitted in a boiler control panel. Install the MC4 controller adjacent
to the boiler plant and connect as shown
• Install the outside sensor on a North facing wall, and connect to the MC4
(for weather compensation only)
Boiler Control Settings
(see 5.7.2 in technical documentation)
• Set boiler code P1 to the required ow temp i.e. 80 = 80ºC (system design requirements)
• Boiler will recognise the type of control setting used
• Set up the controller to suit the design requirements and occupancy times for HTG in
accordance with the instruction documents supplied with the controller
Note: Installation can be designed without the use of a low loss header. Omit the header and
shunt pumps. A heating pump must be capable of overcoming the combined resistance of the
boiler, system and pipe work.
A reverse return with a common loop and single primary pump would be suitable.

Other manuals for Quinta Pro 30

4

This manual suits for next models

4

Other REMEHA Boiler manuals

REMEHA Gas 320 Ace User manual

REMEHA

REMEHA Gas 320 Ace User manual

REMEHA Gas 210 Ace 80 User manual

REMEHA

REMEHA Gas 210 Ace 80 User manual

REMEHA Quinta Ace 30 User manual

REMEHA

REMEHA Quinta Ace 30 User manual

REMEHA Gas 350 L User manual

REMEHA

REMEHA Gas 350 L User manual

REMEHA Gas 320 Ace Series User manual

REMEHA

REMEHA Gas 320 Ace Series User manual

REMEHA Avanta 18v User manual

REMEHA

REMEHA Avanta 18v User manual

REMEHA W40 User manual

REMEHA

REMEHA W40 User manual

REMEHA HFS 600 Manual

REMEHA

REMEHA HFS 600 Manual

REMEHA Avanta 18v Manual

REMEHA

REMEHA Avanta 18v Manual

REMEHA P 500 Manual

REMEHA

REMEHA P 500 Manual

REMEHA GAS 360 S Manual

REMEHA

REMEHA GAS 360 S Manual

REMEHA GAS 360 S User manual

REMEHA

REMEHA GAS 360 S User manual

REMEHA Gas 110 Eco 115 Troubleshooting guide

REMEHA

REMEHA Gas 110 Eco 115 Troubleshooting guide

REMEHA Quinta Pro 30 Troubleshooting guide

REMEHA

REMEHA Quinta Pro 30 Troubleshooting guide

REMEHA P 520 User manual

REMEHA

REMEHA P 520 User manual

REMEHA Gas 210 ECO Manual

REMEHA

REMEHA Gas 210 ECO Manual

REMEHA CALORA TOWER GAS 15S EX Manual

REMEHA

REMEHA CALORA TOWER GAS 15S EX Manual

REMEHA Gas 220 Ace Series User manual

REMEHA

REMEHA Gas 220 Ace Series User manual

REMEHA Quinta Ace 30 User manual

REMEHA

REMEHA Quinta Ace 30 User manual

REMEHA Quinta Ace 160 Troubleshooting guide

REMEHA

REMEHA Quinta Ace 160 Troubleshooting guide

REMEHA Gas 220 Ace 220 Troubleshooting guide

REMEHA

REMEHA Gas 220 Ace 220 Troubleshooting guide

REMEHA Avanta Plus 35c Manual

REMEHA

REMEHA Avanta Plus 35c Manual

REMEHA Gas 210 ECO User manual

REMEHA

REMEHA Gas 210 ECO User manual

REMEHA Gas 550 Manual

REMEHA

REMEHA Gas 550 Manual

Popular Boiler manuals by other brands

VOKERA Mynute 28e User instructions

VOKERA

VOKERA Mynute 28e User instructions

Trianco Greenflame 18kW Installation & operation

Trianco

Trianco Greenflame 18kW Installation & operation

Beretta MYNUTE X C Series installer and user manual

Beretta

Beretta MYNUTE X C Series installer and user manual

Sime Planet AquaQuick 25 BF Installer's instructions

Sime

Sime Planet AquaQuick 25 BF Installer's instructions

Kostrzewa Mini Bio user manual

Kostrzewa

Kostrzewa Mini Bio user manual

Hoval BioLyt (8-36) operating instructions

Hoval

Hoval BioLyt (8-36) operating instructions

Viessmann Vitogas 100 GS1 Series installation instructions

Viessmann

Viessmann Vitogas 100 GS1 Series installation instructions

Italtherm CITY CLASS Series Service manual

Italtherm

Italtherm CITY CLASS Series Service manual

Sime SOLO 25-35 BF TS instructions

Sime

Sime SOLO 25-35 BF TS instructions

Crown Boiler BWC070 Installation manual supplement

Crown Boiler

Crown Boiler BWC070 Installation manual supplement

Crown Boiler AWI037 installation instructions

Crown Boiler

Crown Boiler AWI037 installation instructions

Kostrzewa Twin Bio Luxury Series user manual

Kostrzewa

Kostrzewa Twin Bio Luxury Series user manual

Viessmann VITOROND 200 Service instructions

Viessmann

Viessmann VITOROND 200 Service instructions

DeDietrich DTG 330 S user guide

DeDietrich

DeDietrich DTG 330 S user guide

Immergas NIKE MYTHOS 24 2E Series Instructions and warnings

Immergas

Immergas NIKE MYTHOS 24 2E Series Instructions and warnings

Ferroli BlueHelix HiTech RRT C Instructions for use, installation & maintenance

Ferroli

Ferroli BlueHelix HiTech RRT C Instructions for use, installation & maintenance

Bryan Boilers CLM Specification sheet

Bryan Boilers

Bryan Boilers CLM Specification sheet

Integra Xmart HEAT MASTER instructions

Integra

Integra Xmart HEAT MASTER instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.