REMEHA HMI Gas 610 ECO PRO Troubleshooting guide

Great Britain
EN
Control panel
HMI Gas 310/610 ECO PRO
Installation, User
and Service
Manual
125482-03

Contents
1 Introduction ................................................................................................4
1.1 Symbols used .......................................................4
1.2 Abbreviations ........................................................4
1.3 General ..................................................................4
1.3.1 Manufacturer's liability .............................................4
1.3.2 Installer's liability .....................................................5
1.3.3 User's liability ..........................................................5
2Safety instructions and recommendations ..............................................6
2.1 Safety instructions ...............................................6
2.2 Recommendations ................................................6
3Technical description ................................................................................7
3.1 Control panel .........................................................7
3.1.1 Functions of the keys ..............................................7
3.1.2 Meaning of the symbols on the display ...................8
4Installation ..................................................................................................9
4.1 Control panel assembly .......................................9
5Commissioning ........................................................................................10
5.1 Switch on the instrument panel ........................10
5.2 Reading out measured values ...........................11
5.2.1 Reading the various current values .......................11
5.2.2 Readout from the hour counter and percentage of
successful starts ....................................................12
5.2.3 Status and sub-status ...........................................12
5.3 Changing the settings ........................................13
5.3.1 Parameter descriptions .........................................13
5.3.2 Modification of the user-level parameters .............18
5.3.3 Modification of the installer-level parameters ........18
5.3.4 Setting the maximum heat input for central heating
operation ...............................................................19
5.3.5 Return to the factory settings ................................20
5.3.6 Carrying out an auto-detect ...................................20
5.3.7 Setting the manual mode ......................................21
1051112 - 125482-03

6 Troubleshooting .......................................................................................22
6.1 Shutdowns and lock-outs ..................................22
6.1.1 General .................................................................22
6.1.2 Blocking .................................................................22
6.1.3 Lock out .................................................................24
6.2 Error memory ......................................................27
6.2.1 Error readout memorised ......................................28
6.2.2 Deletion of the error display ..................................29
Contents
2051112 - 125482-03

3051112 - 125482-03

1 Introduction
1.1 Symbols used
In these instructions, various danger levels are employed to draw the
user's attention to particular information. In so doing, we wish to
safeguard the user's safety, obviate hazards and guarantee correct
operation of the appliance.
DANGER
Risk of a dangerous situation causing serious physical
injury.
WARNING
Risk of a dangerous situation causing slight physical
injury.
CAUTION
Risk of material damage.
Signals important information.
¼ Signals a referral to other instructions or other pages in the
instructions.
1.2 Abbreviations
4PCU: Primary Control Unit - PCB for managing burner operation
4PSU: Parameter Storage Unit - Parameter storage for PCBs
PCU and SU
4SCU: Secondary Control Unit - Extended control PCB
4SU: Safety Unit - Safety PCB
4Central heating: Central heating
1.3 General
1.3.1. Manufacturer's liability
Our products are manufactured in compliance with the requirements
of the various applicable European Directives. They are therefore
delivered with [ marking and all relevant documentation.
HMI Gas 310/610 ECO PRO 1. Introduction
051112 - 125482-03 4

In the interest of customers, we are continuously endeavouring to
make improvements in product quality. All the specifications stated in
this document are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the following
cases:
4Failure to abide by the instructions on using the appliance.
4Faulty or insufficient maintenance of the appliance.
4Failure to abide by the instructions on installing the appliance.
1.3.2. Installer's liability
The installer is responsible for the installation and inital start up of the
appliance. The installer must respect the following instructions:
4Read and follow the instructions given in the manuals provided
with the appliance.
4Carry out installation in compliance with the prevailing legislation
and standards.
4Perform the initial start up and carry out any checks necessary.
4Explain the installation to the user.
4If a maintenance is necessary, warn the user of the obligation to
check the appliance and maintain it in good working order.
4Give all the instruction manuals to the user.
1.3.3. User's liability
To guarantee optimum operation of the appliance, the user must
respect the following instructions:
4Read and follow the instructions given in the manuals provided
with the appliance.
4Call on qualified professionals to carry out installation and initial
start up.
4Get your installer to explain your installation to you.
4Have the required checks and services done.
4Keep the instruction manuals in good condition close to the
appliance.
This appliance is not intended to be used by persons (including
children) whose physcial, sensory or mental capacity is impaired or
persons with no experience or knowledge, unless they have the
benefit, through the intermediary of a person responsible for their
safety, of supervision or prior instructions regarding use of the
appliance. Care should be taken to ensure that children do not play
with the appliance.
To prevent hazardous situations from arising, if the mains lead is
damaged it must be replaced by the original manufacturer, the
manufacturer's dealer or another suitably skilled person.
1. Introduction HMI Gas 310/610 ECO PRO
5051112 - 125482-03

2 Safety instructions and
recommendations
2.1 Safety instructions
Strictly follow the safety instructions given.
WARNING
4This equipment operates using electricity.
4Disconnect the equipment from the power supply
before making electrical connections.
4Only qualified professionals are authorised to work
on the appliance and the installation.
4Only the manufacturer is authorised to carry out
repairs.
2.2 Recommendations
Only qualified professionals are authorised to work on the appliance
and the installation.
4Store this document in the document wallet on the
inside of the boiler casing.
4Keep the appliance accessible at all times.
4Never remove or cover labels and rating plates affixed
to the appliance.
HMI Gas 310/610 ECO PRO 2. Safety instructions and recommendations
051112 - 125482-03 6

3 Technical description
3.1 Control panel
For operation of the boiler Gas 610 ECO PRO:
Each module has its own instrument panel.
3.1.1. Functions of the keys
1Display
2> [Escape] or J key
3D Heating temperature key or [-]
4[+] key
5S [Enter] or cancel d Key lock-out
6B [Chimney-sweeping] keys
(press the 2 and 3 keys simultaneously)
7f [Menu] keys
(press the 4 and 5 keys simultaneously)
8On/Off switch
9PC connection
The display has several positions and symbols and provides
information on the operating condition of the boiler and any possible
failures. A service message may also appear in the display. Numbers,
dots and/or letters may be displayed. The symbols located above the
function keys indicate their current function.
4The display content can be changed using parameter p4.
4The brightness of the display lighting can be changed using
parameter p5.
Key lock-out is activated by setting parameter p4 to 3. If no key is
pressed for 3 minutes, the display lighting switches off and only the
current water pressure, the J key and the d symbol are
displayed.(Water level: Only with the hydraulic pressure sensor
connected) Press the S key for about 2 seconds to reactivate the
display and other keys. The d symbol disappears from the display.
T003479-D
rpm
kWµA
± 30l/min
barPsi
St ºC
ºCºFh
2
1 8
3 4 5 9
6 7
3. Technical description HMI Gas 310/610 ECO PRO
7051112 - 125482-03

3.1.2. Meaning of the symbols on the display
QInformation menu:
Reading the various current values. /On/Off switch (0/1):
After 5 lock-outs, the boiler must be switched off/on again.
BChimney-sweeping position:
Forced full or part load for CO2 measurement. bShunt pump:
The pump operates.
WUser menu:
Parameters at user level can be changed. DCentral heating function:
Access to central heating temperature parameter.
CHeating programme deactivated:
The heating function is deactivated. dLocking the keys:
Key lock-out is activated.
EManual mode:
Boiler is set to manual operation. KYellow display with the symbols:
$ + K + Z (Maintenance message).
?Service menu:
Parameters at installer level can be changed. eWater pressure:
The water pressure is too low.
(Only with the hydraulic pressure sensor connected)
cDefect:
Boiler indicates a fault. This can be seen from the e
code and red display.
]Frost protection:
Boiler is running in frost protection mode.
IBurner level:
Output level . \Hour counter menu:
Readout of the operating hours, number of successful
starts and hours on mains supply.
ZOutside sensor:
(Only if an outside temperature sensor is connected
= Accessory).
[Signal strength symbol:
Signal strength of the wireless controller (if connected).
gBattery symbol:
Status of battery of wireless controller (if connected).
HMI Gas 310/610 ECO PRO 3. Technical description
051112 - 125482-03 8

4 Installation
4.1 Control panel assembly
The instrument panel HMI GAS 310/610 ECO PRO is standard fitted
in the Gas 310/610 ECO PRO boiler.
4. Installation HMI Gas 310/610 ECO PRO
9051112 - 125482-03

5 Commissioning
5.1 Switch on the instrument panel
For operation of the boiler Gas 610 ECO PRO:
The features and instructions described are for each boiler
module.
The instrument panel HMI GAS 310/610 ECO PRO is ready for use,
as soon as the power to the boiler is switched on.
1. Open the gas valve on the boiler.
2. Turn on the boiler using the on/off switch.
3. Set the controls (thermostats, control system) so that they request
heat.
4. The start-up cycle begins and cannot be interrupted. During the
start-up cycle, the display shows the following information:
A short test where all segments of the display are visible.
fK[xx : Software version
pK[xx : Parameter version
The version numbers are displayed alternately.
By pressing the S key for a short time, the current operating status
is shown on the display:
Heat demand Heat demand stopped
1 : Fan ON 5 : Burner stop
" : Boiler is igniting 6 : Post-circulation of the pump
3 : Heating System 0 : Standby
In STAND-BY, the display normally shows the water pressure next to
0 (only when the hydraulic pressure sensor is connected) and the
symbols D and H.
Error during the start-up procedure:
4No information is shown on the display:
-Check the mains supply voltage
-Check the main fuses
-Check the connection of the mains lead to the connector in the
instrument box (Check the fuse F2 = 10 AT)
-Check the fuses on the control panel:
(F1 = 2 AT)
4A fault is indicated on the display by the fault symbol c and a
flashing fault code.
-The meaning of the error codes is given in the error table.
-Press for 2 seconds on key J to restart the boiler.
HMI Gas 310/610 ECO PRO 5. Commissioning
051112 - 125482-03 10

5.2 Reading out measured values
For operation of the boiler Gas 610 ECO PRO:
The features and instructions described are for each boiler
module.
5.2.1. Reading the various current values
The following current values can be read off the information menu
Q:
45t = State.
45v = Sub-status.
4t1 = Supply temperature (°C).
4t" = Return temperature (°C).
4t4 = Outside temperature (°C)
Only with an outside temperature sensor (Accessory).
4t6 = Exchanger temperature (°C).
45p = Internal set point (°C).
4fl = Ionization current (µA).
4Mf = Fan speed (rpm).
4pr = Water pressure (bar).
Only with the hydraulic pressure sensor connected (Accessory).
4p; = Supplied relative heat output (%).
451 = Pressure switch minimum Gps ( Kz = Not connected /
K1 = Gas pressure OK / K" = Gas pressure incorrect)
Only with connected minimum gas pressure switch (Accessory)
45" = Gas valve leak proving system Vps (Kz = Not
connected / K1 = No gas leak / K" = Gas leak present)
Only with connected gas leakage control (Accessory).
4V1 = Analogue input (V).
4V" = Analogue output (V).
The current values can be read as follows:
1. Press the two f keys simultaneously. The symbol Q flashes.
2. Confirm using key S. 5t is displayed, alternating with the
current status 3 (for example).
3. Press the [+] key. 5v is displayed, alternating with the current
sub-status 30 (for example).
4. Press the [+] key. t1 is displayed, alternating with the current
flow temperature 60°C (for example).
5. Press the [+] key successively to scroll down the various
parameters
6. Press the [+] key. The readout cycle starts again with 5t.
7. Press the > key 2 times to return to the current operating
mode.
T004355-A
4x
2x
5. Commissioning HMI Gas 310/610 ECO PRO
11 051112 - 125482-03

5.2.2. Readout from the hour counter and
percentage of successful starts
1. Press the two keys f simultaneously and then key [+] until the
symbol \ flashes on the menu bar.
2. Press the S key. hr and the number of hours of boiler
operation 3600 (for example) are displayed alternately.
3. Press the [+] key. The display shows D. hr is displayed,
alternating with the number of operating hours in central heating
operation 560 (for example).
4. Press the [+] key. The display shows @. 5Z is displayed,
alternating with the percentage of successful starts 92 % (for
example).
5. Press the > key 2 times to return to the current operating
mode.
5.2.3. Status and sub-status
The information menu Q gives the following status and sub-status
numbers:
State 5t Sub-status 5v
0Rest 0Rest
1Boiler start (Heat demand)
1Anti-hunting
2Open hydraulic valve
3Start pump
4Wait for the correct temperatures for burner start
2Burner start
10 Open external gas valve
11 Fan ON
12 Open flue gas damper (Accessory)
13 Pre-ventilation
14 Wait for release signal
15 Burner on
16 Gas valve leak proving system VPS
17 Pre-ignition
18 Main ignition
19 Flame detection
"0 Intermediate ventilation
T000816-G
5x
2x
HMI Gas 310/610 ECO PRO 5. Commissioning
051112 - 125482-03 12

State 5t Sub-status 5v
3Burner for central heating operation
30 Temperature control
31 Limited temperature control (ΔT safety)
32 Output control
33 Increase protection level 1 (Modulate down)
34 Increase protection level 2 (Part load)
35 Increase protection level 3 (Blockage)
36 Modulate up for flame control
37 Temperature stabilisation time
38 Cold start
5Burner stop
40 Burner off
41 Post ventilation
42 Fan OFF
43 Close flue gas damper (Accessory)
44 Stop fan
45 Close external gas valve
6Boiler stop (End of heat demand)
60 Pump post circulation
61 Pump off
62 Close hydraulic valve
63 Start anti-hunting
8Control stop 0Wait for burner start
1Anti-hunting
9Blocking xx Shutdown code xx
5.3 Changing the settings
The boiler control panel is set for the most common heating
systems. With these settings, practically all heating systems operate
correctly. The user or installer can optimise the parameters according
to own preferences.
For the settings of the Gas 610 ECO PRO boiler:
The parameters and settings described are for each boiler
module. Each parameter changing must therefore be done
identical on each module.
5.3.1. Parameter descriptions
nBoiler type Gas 310 ECO PRO
Parameter Description Adjustment range
Factory setting
Gas 310 ECO PRO
285 355 430 500 575 650
p1 Supply temperature: TSET 20 to 90 °C 80
p2 Post-circulation of the pump 1 to 98 minutes
99 minutes = continuous 5
p3 Boiler regulation 0 = Heating deactivated
1 = Heating activated 1
5. Commissioning HMI Gas 310/610 ECO PRO
13 051112 - 125482-03

Parameter Description Adjustment range
Factory setting
Gas 310 ECO PRO
285 355 430 500 575 650
p4 Display screen
0 = Simple
1 = Comprehensive
2 = Automatic switching to simple after 3
minutes
3 = Automatic switching to simple after 3
minutes; Key blocking is active
2
p5 Brightness of display lighting 0 = Dimmed
1 = Bright 1
p17 Maximum fan speed G20 (Gas H)
(x100 rpm) 52 55 35 38 43 41
p18 Minimum fan speed G20 (Gas H)
(x100 rpm) 14 15 9 10 11 10
p19 offset Minimum fan speed Do not modify
(x1 rpm) 0 50 50 50 0 50
p20 Start speed Do not modify
(x100 rpm) 25 25 13 14 14 14
p21 Maximum flow temperature
of system 0 to 90 °C 90
p22
Heat curve set point
(Maximum outside
temperature)
Only with an outside
temperature sensor
(Accessory)
0 to 30 °C 20
p23
Heat curve set point
(Supply temperature)
Only with an outside
temperature sensor
(Accessory)
0 to 90 °C 20
p24
Heat curve set point
(Minimum outside
temperature)
Only with an outside
temperature sensor
(Accessory)
-30 to 0 °C -15
p25
Antifreeze temperature
Only with an outside
temperature sensor
(Accessory)
from - 30 to 0°C - 10
p26 Fault relay function X4
(If connected)
0 = Operation signal
1 = Alarm signal 0
p27 Fault relay function X5
(If connected)
0 = Operation signal
1 = Alarm signal 1
p28
Minimum water pressure
Wps
Only with the hydraulic
pressure sensor connected
(Accessory)
0 - 7 bar (x 0.1 bar)
0 = Not connected 0
p29
Minimum gas pressure
check Gps
(Accessory)
0 = Not connected
1 = Connected 0
p30
Hydraulic valve running time
HdV
(If connected)
0 to 255 seconds 0
p31
Flue gas damper running
time FgV
If connected (Accessory)
0 to 255 seconds 0
HMI Gas 310/610 ECO PRO 5. Commissioning
051112 - 125482-03 14

Parameter Description Adjustment range
Factory setting
Gas 310 ECO PRO
285 355 430 500 575 650
p32 Release waiting time 0 to 255 seconds 0
p33
Gas valve leak proving
system VPS
(Accessory)
0 = Not connected
1 = Connected 0
p34 Mains detection phase 0 = Off
1 = On 1
p35 Shutdown input function
1 = Shutdown without frost-protection
2 = Shutdown with frost protection
3 = Lock-out with frost protection (Pump only)
1
p36
From Analogue output (0 -
10V)
SCU-S05 control PCB
0 =0-10 V Wilo control PCB
1 = 0-10 V Grundfos control PCB
2 = PWM pump
3 = Heat output feedback
4 = Temperature feedback
0
p37 From Analogue input (0-10V)
SCU-S05 control PCB
0 =OpenTherm regulator
1 = Analogue temperature-based control (°C)
2 = Analogue heat output-based control (%)
1
p38 Average flow temperature
factor
Do not modify 6
p39 Display units 0 = °C / bar
1 = F / PSI 0
p40 Maintenance message
0 = Service messages off
1 = Service messages on
2 = Customized service message
0
p41 Service operating hours ( x 100)
Do not modify 175
p42 Service burning hours ( x 100)
Do not modify 30
p43
Setting the pump speed
(Minimum pump speed for
central heating operation)
2 - 10 (x 10%) 2
p44
Setting the pump speed
(Maximum pump speed for
central heating operation)
6 - 10 (x 10%) 10
p45 ΔT Modulate down 10 to 30 °C 25
Zd Detection of connected SCUs 0 = No detection
1 = Detection 0
df and dV Factory setting
To restore the factory settings or when
replacing the main PCB, enter the values dF
and dU from the type plate in parameters
df and dV
X
Y
5. Commissioning HMI Gas 310/610 ECO PRO
15 051112 - 125482-03

nBoiler type Gas 610 ECO PRO
Parameter Description Adjustment range
Factory setting
Gas 610 ECO PRO
570 710 860 1000 1150 1300
p1 Supply temperature: TSET 20 to 90 °C 80
p2 Post-circulation of the pump 1 to 98 minutes
99 minutes = continuous 5
p3 Boiler regulation 0 = Heating deactivated
1 = Heating activated 1
p4 Display screen
0 = Simple
1 = Comprehensive
2 = Automatic switching to simple after 3
minutes
3 = Automatic switching to simple after 3
minutes; Key blocking is active
2
p5 Brightness of display
lighting
0 = Dimmed
1 = Bright 1
p17 Maximum fan speed G20 (Gas H)
(x100 rpm) 52 55 35 38 43 41
p18 Minimum fan speed G20 (Gas H)
(x100 rpm) 19 18 13 12 14 13
p19 offset Minimum fan speed Do not modify
(x1 rpm) 0 50 0 50 0 50
p20 Start speed Do not modify
(x100 rpm) 25 25 14 14 15 16
p21 Maximum flow temperature
of system 0 to 90 °C 90
p22
Heat curve set point
(Maximum outside
temperature)
Only with an outside
temperature sensor
(Accessory)
0 to 30 °C 20
p23
Heat curve set point
(Supply temperature)
Only with an outside
temperature sensor
(Accessory)
0 to 90 °C 20
p24
Heat curve set point
(Minimum outside
temperature)
Only with an outside
temperature sensor
(Accessory)
-30 to 0 °C -15
p25
Antifreeze temperature
Only with an outside
temperature sensor
(Accessory)
from - 30 to 0°C - 10
p26 Fault relay function X4
(If connected)
0 = Operation signal
1 = Alarm signal 0
p27 Fault relay function X5
(If connected)
0 = Operation signal
1 = Alarm signal 1
p28
Minimum water pressure
Wps
Only with the hydraulic
pressure sensor connected
(Accessory)
0 - 7 bar (x 0.1 bar)
0 = Not connected 0
HMI Gas 310/610 ECO PRO 5. Commissioning
051112 - 125482-03 16

Parameter Description Adjustment range
Factory setting
Gas 610 ECO PRO
570 710 860 1000 1150 1300
p29
Minimum gas pressure
check Gps
(Accessory)
0 = Not connected
1 = Connected 0
p30
Hydraulic valve running
time HdV
(If connected)
0 to 255 seconds 0
p31
Flue gas damper running
time FgV
If connected (Accessory)
0 to 255 seconds 0
p32 Release waiting time 0 to 255 seconds 0
p33
Gas valve leak proving
system VPS
(Accessory)
0 = Not connected
1 = Connected 0
p34 Mains detection phase 0 = Off
1 = On 1
p35 Shutdown input function
1 = Shutdown without frost-protection
2 = Shutdown with frost protection
3 = Lock-out with frost protection (Pump
only)
1
p36
From Analogue output (0 -
10V)
SCU-S05 control PCB
0 =0-10 V Wilo control PCB
1 = 0-10 V Grundfos control PCB
2 = PWM pump
3 = Heat output feedback
4 = Temperature feedback
0
p37
From Analogue input
(0-10V)
SCU-S05 control PCB
0 =OpenTherm regulator
1 = Analogue temperature-based control
(°C)
2 = Analogue heat output-based control (%)
1
p38 Average flow temperature
factor
Do not modify 6
p39 Display units 0 = °C / bar
1 = F / PSI 0
p40 Maintenance message
0 = Service messages off
1 = Service messages on
2 = Customized service message
0
p41 Service operating hours ( x 100)
Do not modify 175
p42 Service burning hours ( x 100)
Do not modify 30
p43
Setting the pump speed
(Minimum pump speed for
central heating operation)
2 - 10 (x 10%) 2
p44
Setting the pump speed
(Maximum pump speed for
central heating operation)
6 - 10 (x 10%) 10
p45 ΔT Modulate down 10 to 30 °C 25
Zd Detection of connected
SCUs
0 = No detection
1 = Detection 0
df and dV Factory setting
To restore the factory settings or when
replacing the main PCB, enter the values
dF and dU from the type plate in parameters
df and dV
X
Y
5. Commissioning HMI Gas 310/610 ECO PRO
17 051112 - 125482-03

5.3.2. Modification of the user-level parameters
Parameters p1 to p5 can be changed by the user.
CAUTION
Modification of the factory settings may be detrimental to
the functioning of the appliance.
1. Press the two keys f simultaneously and then key [+] until the
symbol W flashes on the menu bar.
2. Select the users menu using the key S. p[1 is displayed with
1 flashing.
3. Press the S key a second time. The value 80°C appears and
flashes (for example).
4. Change the value by pressing the [-] or [+] key. In this example
using key [-] to 60°C.
5. Confirm the value with the S key. p[1 is displayed with 1
flashing.
6. Press the > key 2 times to return to the current operating
mode.
4The parameters p2 to p5 are changed in the
same way as p1. After step 2, use the [+] key to
move to the required parameter.
5.3.3. Modification of the installer-level
parameters
Parameters p17 to df must only be modified by a qualified
professional. To prevent unwanted settings, some parameter settings
can only be changed after the special access code 0012 is
entered.
CAUTION
Modification of the factory settings may be detrimental to
the functioning of the appliance.
1. Press the two keys f simultaneously and then key [+] until the
symbol ? flashes on the menu bar.
2. Select the fitter menu using the key. c0de appears on the
display.
3. Use keys [-] or [+] to input the installer code 0012.
4. Confirm using key S. p[1 is displayed with 1 flashing.
5. Press the S key a second time. The value 80°C appears and
flashes (for example).
6. Change the value by pressing the [-] or [+] key. In this example
using key [-] to 60°C.
7. Confirm the value with the S key: p[1 is displayed with 1
flashing.
T001906-B
1x
2x
T000819-E
3x
2x
HMI Gas 310/610 ECO PRO 5. Commissioning
051112 - 125482-03 18

8. If necessary, set other parameters by selecting them using the
[-] or [+] keys.
9. Press the > key 2 times to return to the current operating
mode.
The boiler also returns to operating status if no keys are
pressed for 3 minutes.
5.3.4. Setting the maximum heat input for central
heating operation
Type Gas 310- ECO PRO 575
MMaximum heat input (natural gas)
FFactory setting
QPower input (kW)
RFan rotation speed (rpm)
The speed can be changed using parameter p17. A linear
relationship exists between the speed and the input: See graph. A
graph for the other boilers can be produced in the same way.
1. Press the two keys f simultaneously and then key [+] until the
symbol ? flashes on the menu bar.
2. Select the installers menu using the key S. c0de appears
on the display.
3. Use keys [-] or [+] to input the installer code 0012.
4. Confirm using key S. p[1 is displayed with 1 flashing.
5. Press the [+] key to go to parameter p[17.
6. Confirm using key S.
7. Press the [+] button to reduce the speed from 54 to 50, for
example.
8. Confirm the value with the S key.
9. Press the > key 2 times to return to the current operating
mode.
R000279
1100 2000 3000 4300 5000
0
109
300
200
500
400
700
539 F
R
Q
M
T004356-A
3x
...x
...x
2x
5. Commissioning HMI Gas 310/610 ECO PRO
19 051112 - 125482-03
This manual suits for next models
1
Table of contents
Other REMEHA Control Panel manuals
Popular Control Panel manuals by other brands

Honeywell
Honeywell Fire-Lite Alarms MRP-2001 instruction manual

Topcon Positioning Group
Topcon Positioning Group RDS TECHNOLOGY ISOCAN APOLLO ATHENE quick start guide

weintek
weintek MT-8000 Series installation instructions

nvent
nvent RAYCHEM TT-TS12 installation instructions

Greengate
Greengate LiteKeeper 4 installation instructions

technoswitch
technoswitch ORYX200 Series Installation & operation manual