- 3 -
www.rotork.com www.remotecontrol.se
Indicator Setting
The valve position is easily conrmed from a dis-
tance by looking at the indicator at located on the
top of the actuator cover
Explosion proof
Standard conduit and conduit seal ttings may be
used when installing and wiring the actuator. To
provent moisture and humidity from entering the
actuator, it is highly recommended that a seal be in-
stalled in the actuator conduit entry. After the conduit
and wiring has been completed, then the seal tting
can be sealed with packing or a potting material.
Cable Glands used in explosion
proof applications must be certied
for the proper explosion proof
application class and properly
sealed. Failure to use the correct components
may ressult in the failure of the actuator enclosure.
Rotork Sweden AB is not responsible the improper
installation of these actuators.
Cable Glands shall be suitable for the enviroment
and shall be certied as ameproof if used in Zone 1
application (Ex d IIB certied cable grand or entries
at least). Cable Glands and conduit(s) of metric
thread shall be so installed that at least 5 full threads
are engaged and the engagement depth is not less
than 8 mm. Cable Gland of NPT thread shall be
installed with 5 threads provided at least.
Wire Connection
Electric Wiring
Remove the actuator cover by loosing the four
captive cover bolts.
Conrm that the wiring diagram located in the
actuator and the wiring number on the nameplate
match each other.
Conrm that the main power and supply described
on the nameplate of the actuator match with each
other.
1.
2.
3.
Connect the wire to the terminal strip ac-
cording to the wiring diagram provided. The
RCEL005X/009X actuators uses the push type
WAGO brand terminal strip. The push type strip
makes wiring connections easy and also helps
to protect against pipeline vibration. Use the wire
thickness within the standard size AWG 28~14.
4.
Be sure to properly ground the actuator by using
the grounding lugs provided on the inside and
outside of the actuator body. The integral ground-
ing wire size shall be 4.0 mm2 and the external
grounding wire size shall be 4.5~5.0 mm2at least.
5.
Inside & Outside Earth Terminal
Push
Wire
AWG 28~4??
Be sure to wire and energize the heater as shown
in the wiring diagram.
Each actuator must be powered by their own
individual relays to prevent voltage feedback and
actuator damage.
After the wiring is completed in the actuator, use
wire ties to group the wires together up their ap-
pearance. Be certain that the wires are secure
and away from any moving parts. Remove any
loose debris before replacing the cover.
When all the work is completed, replace the top
cover and secure it using the four cover screws.
Apply power and do a nal check to conrm
proper operation.
Main power must only be applied when
the top cover is re-installed on the
actuator body. If the main power is on
while wiring the actuator, stop work
immediately and turn the power off, only then its is
safe to proceed.
6.
7.
8.
9.
10.