Remote Control RCEL User manual

Top Quality Valve Actuators
Made in Sweden
Instruction
Digital Controller PCU Solid State
RCEL
- 1 -
www.rotork.com www.remotecontrol.se
ELECTRICAL SHOCK HAZARD.To avoid serious personal injury,
property damage, turn off ALL power to the actuator before remov-
ing the cover.
Before installation or use, verify the nameplate information infor-
mation to insure the correct model number, torque, voltage and
enclosure type.
Be sure to completly review the actuator manual prior to operation.
Final limit switch adjustment MUST be done after mounting the ac-
tuator to the valve. Incorrect adjustment may cause actuator failure.
Over torque switches are factory set, tampering with the over
torque switch settings may damage the actuator and void the war-
ranty.
The actuator must be properly grounded. Use the grounding lugs
provided on the inside and outside of the actuator body.
To minimize the possible damage caused by condensation, be sure
to energize the heater.
Care should be taken when wiring 3 phase actuators.
Conrm proper rotation and limit switch shutoff function during the
initial operation. If the actuator rotates in the reverse direction, then
the phasing needs to be corrected by switching two of the 3 phase
wires on the terminal block.
CAUTION Specications
Input Power
90~230V AC ±10%, 50/60Hz
DC 24V / AC 24V ±10%
Input Power must match motor Ratings
Command Signal 4~20mA DC (Default), 0~5VDC,
0~10VDC, 1~5VDC, 2~10VDC
Dead Band 1 ~ 7,5% (1 scale 0,5%)
Output Signal 4~20mA DC
Load Resistance 750
Ω
Terminals 1~12 Connector, +, - 2EA (In/Output)
Visual Indicators
4 LEDS,
Power (Blue), Fault (Yellow),
Open (Red), Close (Green)
Calibration Method ASCN (Autoscan) Button
Output Contact Relay Contact 250V AC 16A MAX.
(Inductive Load)
Delay Time 1 Sec
Parameters
Dead Band: 0.2mA(Step)
Fail operation (during loss of command
signal) Select input signal. A FULL Set
or Clear
Resolution Min 1/1,000
Ambient Temperatur -10 ºC ~ +60 ºC
Ambient Humidity 90% RH MAX. (Non-Condensing)
Dielectric Strenght 1,500V AC 1 MIN.
(Input to Output to Power to Ground)
Insulation Resistance 500V DC 30MΩ MIN.
Warranty Information
The warranty will be void under the following conditions:
1. Failure or damage caused by misuse or abuse.
2. Failure or damage caused by unauthorized modications or repairs done to the actuator.
3. Failure caused by the unauthorized modication / change or the wiring.
4. Failure caused by water entering the actuator due to improper sealing of the conduit entries.
5. Failure caused by improperly set limit switches.
6. Failure caused by re, ood damage or other natural disasters.
7. Failure occuring more than one year after shipment date.

- 2 -
E4L E4
H L H L
RC210 90 68 120 68
RC220-RC265 90 110 120 110
RC270-RC280,
RC88 100 160 130 160
RCG90-RCG100 155* 200* 185* 200*
Tabell 14pt bold
Bold på rubriker uppe, allt under ska vara regular.
Allt utom spalten med RC-förteckningar ska vara
centrerat i våg och lodrätt. RC-spalten ska vara
vänsterlagd.
Strl på texten varierar beroende på utrymme men
10pt är standard
www.rotork.com www.remotecontrol.se
PCU Board Spec.
1
3
7
2
4
5
6
8
9
10
No Name
1No. 1 ~ 12 Connector
2Dip Switch
3Output Connector
4
ZERO Button
SPAN Button
AUTO SCAN Button
5Dead Band
6OTS, CTS Connector
7Input Connector
8OLS, CLS Connector
9Potentiometer
Connector
10 DIP Switch for Input
Setting
1No. 1 ~ 12 Connector
1111098
7
65432 12
2DIP SWITCH
No. 1 2 3 4 5 6 7 8
Name FC FO AF CH1 CH2 REV Full Close
Output Control
Full Open
Output Control
Spec. Fail
Close
Fail
Open
A Full
3.8 ~ 4.3 Input Fully Close
19.7 ~ 20.2 Input Fully Open
Discretion
Setting
Manual
Setting
Reverse
Action ─ ─

- 3 -
www.rotork.com www.remotecontrol.se
1. Fail Close When there is no input signal, the actuator automatically turns to a full close position.
2. Fail Open When there is no input signal, the actuator automatically turns to a full open position.
3. AF If the input signal is at 3.8 ~ 4.3mA, the actuator turns to a full close position.
If the input signal is at 19.7 ~ 20.2mA, the actuator turns to a full open position.
4. CH1 Optional modulation
It is used when the user voluntarily changes the input signal.
ex) When setting to 6 ~ 18mA Input
●CH1 ON →Input 6mA and press ZERO button →Input 18mA and press SPAN button.
→CH1 OFF →Input and check if the device operates normally.
5. CH2 Optional modulation using manual handle.
Ii is used when the user controls the actuator using the manual handle.
ex) When controlling using the manual handle.
●CH2 ON →Put the actuator at Full Close. →Press the ZERO Button →Put the actuator at
Full Open →Press the SPAN Button →CH2 OFF →Input and check if the device operates
normally.
6. REV It is used when the actuator operates in the inverse direction.
When REV is on and at 4mA, the actuator turns to a full open position, and to a full close position
when at 20mA.
7. Full Close
Output Control
If the output is 3.7mA (not 4mA), put no.7 switch up and put SPAN button.
Whenever the button is put, the output increase. When it reaches at 4mA, put ASCN button for a
second to save it.
(If the output is higher than 4mA, (4.2mA), put ZERO button to decrease.)
8. Full Open
Output Control
If the output is not 20mA, follow the same step as above (7. Full Close Output Control).
↑
+−
↑↑
+−
↑
3In / Output Connector
7
4Name Spec.
ZERO Close manual control button
/ Input module button
SPAN Open manual control button
/ Input module button
ASCN AUTO SCAN BUTTON
(Actuator automatic control button)
Delivered from the factory the resistance value
of potentiometer may can be changed if the user
modies its limit setting. Please make sure to
press the autoscan button for at least 2 seconds
before operating proportional control.

- 4 -
E4L E4
H L H L
RC210 90 68 120 68
RC220-RC265 90 110 120 110
RC270-RC280,
RC88 100 160 130 160
RCG90-RCG100 155* 200* 185* 200*
Tabell 14pt bold
Bold på rubriker uppe, allt under ska vara regular.
Allt utom spalten med RC-förteckningar ska vara
centrerat i våg och lodrätt. RC-spalten ska vara
vänsterlagd.
Strl på texten varierar beroende på utrymme men
10pt är standard
www.rotork.com www.remotecontrol.se
Name Spec.
DEAD BAND Mechanical Steps at least 0.2mA
What is DEAD BAND ?
It’s an area/band where no action occurs due to the actuator input.
If the user inputs 12mA (50%), the actuator is supposed to stop exactly at 50% poaition. The actuator repeats from open
to close in order to stop at 50% position at this point.
This is what we call hunting, and if the hunting effect repeatedly occurs the motor can be damage. Therefor a dead band
is set to have some area in order to prevent this from happening.
It’s set to have 0.05mA per gradation. If it is at 1PH when shipped from the factory, it is set to have a 0.2mA dead band. If
it is at 3PH, on the other hand, it is set to have a 0.3mA dead band.
ex) If it is set to have a 0.2mA dead band, the actuator is positioned between 11.8mA to 12.2mA.
In case the actuator stops at the position of 12.1mA, the second least movement area will be at
12.3mA. At this position no action occurs even when there is the input signal.
5DEAD BAND
6OTS, CTS Connector 8OLS, CLS Connector
9Potentiometer Connector
P3
P1
P2
Color Resistance
P1 White LOW
0 ~ 1000ΩP2 Blue COM
P3 Black HIGH
When shipped from the factory and at full close, it is set at 80 ~ 120Ω.
( *Refer to P13 for Potentiometer setting)

- 5 -
www.rotork.com www.remotecontrol.se
10 DIP SWITCH for INPUT Setting
S/W 1 2 3
INPUT
4-20mA ON OFF OFF
2 - 10V OFF ON OFF
0 - 5V OFF OFF ON
0 - 10V OFF ON ON
1 - 5V OFF OFF OFF
How to use
1) Wire according to the product.
Close AOLSComACLS
Com
Auto
Open
12 7893456
AC Power
V
−
Input
4-20mA
+
4-20mA
Output
−+
2) AUTO SCAN Push (2 sec)
● Auto Scan Button (Actuator automatically setting button)
Delivered from the factory the resistance value of potentiometer may can
be changed if the user modies its limit setting.
Please make sure to press the autoscan button for at least 2 seconds
before operating proportional control.
3) Check the input and output are correct. (Standard: In/Output 4-20mA)
● If the input is not 4-20mA, refer to P9 CH1.
●0 ~10V INPUT Setting
1) DIP SWITCH CHANGE
S/W 123
INPUT
4-20mA ON OFF OFF
2 - 10V OFF ON OFF
0 - 5V OFF OFF ON
0 - 10V OFF ON ON
1 - 5V OFF OFF OFF
↕
ON
OFF

- 6 -
E4L E4
H L H L
RC210 90 68 120 68
RC220-RC265 90 110 120 110
RC270-RC280,
RC88 100 160 130 160
RCG90-RCG100 155* 200* 185* 200*
Tabell 14pt bold
Bold på rubriker uppe, allt under ska vara regular.
Allt utom spalten med RC-förteckningar ska vara
centrerat i våg och lodrätt. RC-spalten ska vara
vänsterlagd.
Strl på texten varierar beroende på utrymme men
10pt är standard
www.rotork.com www.remotecontrol.se
3. After manual operation, leave the lever as it is. It will
automatically return to the previous stage of manual op-
eration by the internal Hand / auto Decluting System when
the actuator is powered on.
4.If the lever does not stand straight even if you pull it in
trying to manually operate the actuator due to some prob-
lems during the actuator operation, you have to check the
possibillity of Jamming.
What is Jamming effect?
It is when worm gear is pressed by the stopper bolt and
gear does not move. The lever and the handles will not
move at this point.
Manual Mode
1. When you pull the lever located on the side of actuator
handle toward the handle, the lever stands straight. If you
turn the handle in that condition, the actuator moves.
2.If the lever does not stand straight when you pull the
lever toward the handle, turn the handle halfway while
pulling the lever toward the handle.
●Turn the handle clockwise for CLOSE
●Turn the handle counter clockwise for OPEN
Limit Setting
1. Pull the lever located on the side of the handle toward
the handle to make it stand straight and the turn the
handle clockwise to fully close the actuator
2) CH1 BUTTON ON
↕
ON
OFF
NO NAME
1 FAIL CLOSE
2 FAIL OPEN
3 A FULL
4 CH1
5 CH2
6 REV
7 Full Close Output Control
8 Full Open Output Control
3) 0V INPUT
ZERO Button
PUSH
←
4) 10V INPUT
SPAN Button
PUSH
←
5) CH1 BUTTON OFF
↕
ON
OFF

- 7 -
www.rotork.com www.remotecontrol.se
Electrical wiring
Inside & Outside earth terminal
1. Conrm that the wiring diagram located in the actuator
and Wiring No. on the name plate match with each other.
2. Conrm that the main power and power supply
described on the name plate of the actuator match with
each other.
3. Insert a small athead screwdriver to open the terminal
point, then insert the wire.
4. Be sure to properly ground the actuator wiring to the
grounding terminals provided on the inside and outside of
the actuator body.
The internal grounding wire size shall be at least the same
with the conductor used and the external grounding wire
size shall be 4.5 ~ 5.0mm2at least.
5. Be sure to wire and energize the heaer that is provided.
6. Each actuator must be powered by their own individual
relays to prevent voltage feedback and actuator damage.
7. After the wiring is completed in the actuator, use wire
ties to clean up the actuator and group wires togheter,
and be certain that the wires are secured away from any
moving parts, remove any loose debris.
8. When all the work is completed, replace the top cover
and secure it using the six cover screws.
9. Apply the power and do a nal check to conrm proper
operation.
Main Power must only be applied when the top
cover is re-installed on the actuator body. If the
main power is on while wiring the actuator stop
work immediately and turn the power off. Only
then it is safe to proceed.
Potentiometer Setting
Change the potentiometer
value by altering the gear.
Potentiometer Check
● Actuator delivered full close at 85 ~ 120Ω
● After limit setting it should check at closed 85 ~ 120Ω
● Make actuator full closed and power off by moving
of gear.
Warning when setting the POTENTIOMETER:
When setting the resistance value on the
potentiometer, always operate when the actuator
power is OFF.
If the power is on, the resistance value on the
calibrator will not show accurately.
● When nished setting device, x the stop screw so that
the gear will not move.
AOLS Dry Contact Open Limit Switch
OLS Open Limit Switch
ACLS Dry Contact Closed Limit Switch
CLS Closed Limit Switsh
2. Loosen the xed bolt of Close Limit Switch and align the
Limit Switch to meet the contact point of Micro Switch.
AOLS
OLS
CLS
ACLS
3. Firmly fasten the xed bolt again.
4. As for Open Limit Switch Setting, follow the instruction
of Close Limit Switch setting.

- 8 -
Ref No 626 / Art No 980626
We reserve the right to
make changes without notice
www.rotork.com www.remotecontrol.se
ROTORK SWEDEN AB
Box 80, Kontrollvägen 15, SE-791 22 Falun, Sweden
Tel: +46 (0)23-587 00 • Fax: +46 (0)23-587 45 • [email protected]
Troubleshooting
PCU card is due to various reasons does not function properly if use the environment and actuators determine the fre-
quency of use, and if there is no more than refer to the following items to verify abnormality.
Problem Cause Sollution
Manual override will not move
The worm wheel and
mechanical limit stop
is jammed
Loosen the mechanical limit stop and
the valve mounting bolts.
Correct the mechanical stop position
and then secure the mounting bolts
and limit stop.
Level will not hold position when
pulled toward the hand wheel
When the OVER LIMIT SWITCH
Actuator to move the handle when
not in operation
In manual operations,
the actuator will not cycle full open
or full close.
Limit switch malfunction and / or
mechanical limit stop set incorrectly
Reset the limit switch cam and reset
the mechanical limit stop
Actuator suddenly stops
during operation
The over torque switch
has tripped
Valves torque has increased.
Valve needs to be checked/ repaired
or replaced, or the over torque switch
has failed and needs to be reset.
When the motor does not operate
Main power failure Main power check
Wire disconnect or shot circuit Replace defective wire
Motor or condenser is damaged Replace motor or condenser
PCU Board failure Replace PCU Board
When 3 phase operation rotates ac-
tuator in the opposit direction than the
signal that is applied
Phase reversal Switch two of the 3 phase wires
When actuator continues to rotate
even after the cam strikes
the limit switch
When PCU board
FAULT LAMP ashes
INPUT failure
circuit & disconnection INPUT check
PCU board FAULT LAMP lighted,
When CLOSE LAMP ashes POTENTIOMETER disconnection POTENTIOMETER check
PCU board FAULT LAMP lighted,
When the lights OPEN LAMP
POTENTIOMETER
P1, P3 reversal P1, P3 re-wiring
* In addition to the above described mechanical / electric failures, other causes may be the reason for a failure based
on the site conditions. For more information please contact Rotork Sweden AB for consultation.
For faster service, please have all of the nameplate information avalibe.
Table of contents
Other Remote Control Controllers manuals
Popular Controllers manuals by other brands

Controlsoft
Controlsoft AC-3100 installation instructions

Robotis
Robotis MX-28AT manual

PIETRO FIORENTINI
PIETRO FIORENTINI CIRVAL Operation & maintenance manual

Hebei
Hebei CCT-3300 Operation manual

Watlow
Watlow Ramping and Profiling Microprocessor-Based Control SERIES... user manual

PowerTech
PowerTech MP3743 instruction manual