REO REOVIB MFS 368 User manual

MFS368_ANL_rev01.en.doc
18.08.2023
□
REOVIB
Control units for vibratory conveyor technology
MFS 368
Frequency converter for vibratory feeders

REOVIB MFS 368
Operating instructions
2
Table of contents
Safety instructions for the user..................................................................................................................... 3
Declaration of Conformity ............................................................................................................................. 6
Changes / Copyright..................................................................................................................................... 6
1.0 General................................................................................................................................................... 7
2.0 Function.................................................................................................................................................. 7
2.1 Track control ....................................................................................................................................... 8
2.2 Operation with two speeds (2
nd
setpoint for coarse/fine switching).................................................... 8
2.3 Control inputs and outputs.................................................................................................................. 9
2.3.1 Enable input..................................................................................................................................9
2.3.2 Sensor input for track control .......................................................................................................9
2.3.3 External setpoint........................................................................................................................... 9
2.3.4 Control output status relay ........................................................................................................... 9
2.3.5 Control output 24 VDC Timeout (IP54)........................................................................................9
2.3.6 Ready relay .................................................................................................................................. 9
2.3.7 Control output 24 VDC Valve (IP54) ............................................................................................9
2.3.8 Thermal switch ............................................................................................................................. 9
2.4 Touch panel ......................................................................................................................................10
3.0 Structure ............................................................................................................................................... 11
3.1 IP54...................................................................................................................................................11
3.2 IP20...................................................................................................................................................11
4.0 Technical data ......................................................................................................................................11
4.1 Load supply requirements ....................................................................................................................12
4.2 Terminal details ....................................................................................................................................12
4.3 Temperature of protective housing.......................................................................................................12
4.4 Coolant type..........................................................................................................................................12
4.5 Current consumption ............................................................................................................................12
4.6 Warning signs.......................................................................................................................................12
5.0 Ordering code (Standard units) ............................................................................................................13
6.0 Possible settings...................................................................................................................................14
7.0 Operating elements ..............................................................................................................................16
7.1 Setting behaviour..............................................................................................................................16
7.1.1 Parameter setting example............................................................................................................17
7.1.2 External setpoint example .................................................................................................................17
8.0 Commissioning.....................................................................................................................................18
8.1 Preparatory measures.......................................................................................................................18
8.2 Operating frequency of the feeder coils............................................................................................18
8.3 Measurement of output voltage and output current..........................................................................18
9.0 Settings.................................................................................................................................................19
9.1 Notes on controller mode..............................................................................................................19
9.2 Mounting the accelerometer..........................................................................................................19
9.3 Correlation between acceleration and vibration amplitude...........................................................21
9.4 Determining the resonant frequency.............................................................................................21
9.5 Commissioning the control unit in control mode ...........................................................................22
10.0 Troubleshooting ..............................................................................................................................23
11.0 Housing version connection ...............................................................................................................24
12.0 Connection of control cabinet version ................................................................................................25
13.0 Dimension drawing.............................................................................................................................27
14.0 Assembly instruction...........................................................................................................................30
A 1.0 Accessories / Options .......................................................................................................................31

3
Safety instructions for the user
IMPORTANT!
READ CAREFULLY BEFORE USE AND KEEP FOR FUTURE REFERENCE!
This description contains the information required for correct use of the products described in it. It is
intended for technically qualified personnel.
Qualified personnel are persons who, because of their training, experience and instruction, as well as
their knowledge of applicable standards, regulations, health and safety requirements and operating
conditions, have been authorized by those responsible for the safety of the equipment to carry out
required activities at any time, and who can recognize and avoid possible hazards in the course of these
activities (definition of qualified employees according to IEC 364).
General safety instructions
The following instructions are provided for the personal safety of operating staff and also for the safety of
the products described and connected equipment.
WARNUNG
Hazardous voltage
Non-observance can result in serious or fatal injury as well as material damage.
- Isolate from the mains before installation or dismantling work, as well for
post-installation modifications.
- Observe the accident prevention and safety rules applicable for the specific
application
- Before putting into operation, check if the rated voltage for the unit conforms with
the local mains supply voltage.
WARNING!
Electric shock in the absence of earthing
If the protective earth connection of devices with protection class I is missing or
incorrectly executed, high voltages may be applied to exposed parts and the housing
which, if touched, can result in serious or fatal injury.
- Ground the unit correctly.
WARN
ING
Electric shock in case of damaged equipment
Improper handling may result in damage to equipment. If units are damaged, dangerous
voltages may be present on the housing or on exposed components which, if touched,
can result in serious or fatal injury.
- During transport, storage and operation, observe the limit values specified in the
technical data.
- Do not use damaged equipment.

REOVIB MFS 368
Operating instructions
4
WARNING
Electric shock if the cable shield is not connected
Capacitive coupling can cause life-threatening touch voltages if the cable shields are not
connected.
- Connect cable shields and unused cores of power lines to earthed housing potential
on at least one side.
WARNING
Arcing when disconnecting a plug connection during operation
Disconnecting a plug connection during operation can cause an electric arc, which can
result in serious or fatal injury.
- Only open plug connections when they are de-energised.
WARNING
Before opening the housing, pull out the mains plug
Before any intervention in the unit, allow at least 5 minutes for the capacitors to
discharge.
WARNING
Injury due to hot surfaces
In case of malfunction, overload and insufficient ventilation, contact with a hot surface may
cause skin burns. With the 6A and 8A versions, the heat sink temperature can reach 70 °C
during operation.
WARNING
Material damage due to incorrect output voltage
Independent of the input voltage, the frequency converter's output voltage is 205 VAC when
delivered. When using 110 VAC feeder coils, the output voltage must be set with parameter:
"Umax", otherwise the feeder coil may be damaged.
WARNING
Improper assembly of parts
Unsuitable assembly tools, screwing methods, or non-observance of the assembly
instructions can lead to falling parts or equipment.

REOVIB MFS 368
Operating instructions
5
WARNING
Influence of electromagnetic fields on active implants
Frequency converters generate electromagnetic fields (EMF) during operation.
Electromagnetic fields can affect active implants, e.g. pacemakers. This puts people with
active implants in the immediate vicinity of an frequency converter at risk.
- As the operator of an EMF-emitting installation, assess the individual risk to persons
with active implants.
WARNING
Total failure of power supply
Interrupting and restoring the power supply to the control unit can lead to hazardous
situations. In particular, once the power supply has been restored, the system can restart
without additional enabling.
WARNING
Unintentional or accidental breach of safety
An unintentional or accidental change of the unit's parameters can disable the protective
functions of the control unit.
WARNING
Unrecognised dangers due to missing or illegible warning signs
Missing or illegible warning signs can lead to hazards going unrecognised. Unrecognised
hazards can result in accidents with serious or fatal injury. See Chapter 4.6 "Warning signs".
Missing signs must be replaced.
CAUTION
Equipment damage due to unsuitable screwing tools
Unsuitable screwing tools or unsuitable screwing methods can damage the screws of the
unit.
- Use screw drives that exactly match the screw head.
- Tighten the screws with the torques specified in the technical documentation.
C
AUTION
Material damage due to loose power connections
Insufficient tightening torques or vibrations can lead to loose power connections. This may
cause fire damage, defects in the unit or malfunctions.
- Tighten all power connections to the prescribed tightening torques.
- Check all power connections at regular intervals, especially after transport.

REOVIB MFS 368
Operating instructions
6
NOTE
Current consumption
The current specified in the technical data is the maximum permissible value for the unit
over the entire input voltage range. A higher current than specified can lead to malfunctions
and failure. See also chapter 4.5 "Current consumption".
Intended use
The units described here are classed as electrical equipment for use in industrial plants.
They are designed for controlling vibratory feeders.
The housing version (IP54) is not suitable for installation in control cabinets.
Failure to maintain the ambient temperature may result in a shortened life span.
Please mount the units on a vibration-free surface.
Declaration of Conformity
We declare that these products conform with the following standards:
REO AG, D-42657 Solingen
Changes / Copyright
We reserve the right to make changes to the technical design and documentation without prior notice.
REO AG reserves the copyright to these instructions. Reproduction, computerisation and filming of any
kind is not permitted without written consent.
Guideline:
Stan
dard:
2014/30/EU
EMC
EN 61000
-
6
-
4:2007 +A1:2011; EN 61000
-
6
-
2
:2019
2014/35/EU
LVD
EN 62477
-
1:2012 +A11:2014 +A1:2017
2011/65/EU
RoHs
RoHS
COMPLAINT

REOVIB MFS 368
Operating instructions
7
1.0 General
The control unit generates an adjustable output frequency for the vibratory feeder independently of the
mains frequency. The PFC circuit on the input side ensures a constant output voltage both at an input
voltage of 110 V and 230 V.
Mains voltage fluctuations have no influence on the feed rate. In addition, the operating mode “Amplitude
control" combined with an accelerometer enables a constant feed rate even with changing feeder loads.
In this operating mode, the feeder's resonant frequency can also be determined and the output frequency
for the feeder continuously tracked.
An integrated track control enables a backlog circuit to be set up for material control via a PNP distance
sensor.
For the operation of a blowing air valve, a 24 VDC output is available in the IP54 housing version.
The unit is operated via an LC display and programming buttons. All the settings can be done using this
display without opening the housing.
Special features:
•Output voltage up to 205 VAC, independent of
mains supply.
•Mains frequency independent, adjustable
output frequency
•Min and max limits of the frequency range
adjustable
•Adjustable current limit for maximum coil
current
•Constant feed rate in the event of mains
fluctuations
•Control of the resonant frequency
•Status relay On / Off
•Ready relay (IP20 only)
•Track control
•24 VDC Output for e.g. air valve (IP54 only)
•Four application-specific parameter sets can
be stored
•With option "Interface operation via field bus"
•Thermal switch input for coil temperature
monitoring
2.0 Function
The controller generates an adjustable output voltage with an adjustable output frequency that is
independent of the mains supply. The input-side PFC circuit ensures a constant output voltage at an input
voltage of 99 V to 264 V. The output voltage is changed to control the feed rate. The output can be
switched on or off via the keyboard or an enable input by a higher-level external control unit. After
switching on the unit, the output is ramped up over an adjustable time ramp (soft start) or ramped down
after switching off (soft stop). The unit can be operated in a manual mode at constant output frequency or
in controller mode with amplitude control and frequency control. For controller mode an acceleration
sensor e.g. SW10 is required, which is mounted on the vibrating part of the feeder. This sensor detects
the feeder's vibration movement and reports this actual value back to the internal controller. In this
operating mode, in addition to the amplitude control, the feeder's resonant frequency is determined and
adjusted accordingly with different loads, so that a constant flow of parts results with an optimum vibrating
frequency of the feeder. The setpoint for the feed rate is specified as standard via the internal display but
can also be supplied externally by means of a 0...10 V or 0/4...20 mA DC signal. For feed rate control, an
integrated track control allows the realisation of a material flow control. This function requires an external
24 V PNP distance sensor to detect the conveyed parts. This creates a defined material flow via
adjustable time stages for switch-on and switch-off delay. The "time out" function can be used to monitor
Housi
ng version
Control cabinet version

REOVIB MFS 368
Operating instructions
8
t ON
t OFF
Sensor
Feeder
ON
OFF
ON
OFF
Soft Start
Soft Stop
whether parts pass the sensor within a period of time (e.g. no-load signal). As an alternative to the
material flow control, the sensor input can be used for switching to a second, internally adjustable
setpoint, e.g. to realise a "fast/slow" function. In parallel with control of the feeder, a 24 V DC output is
available for the IP54 housing version, which can control a blowing air valve to support the parts flow.
This output can switch on before the feeder starts and switch off with a time delay after the feeder has
switched off. The time delays are adjustable. Depending on the conveyor, the nominal unit current can be
set between 5% and 100%. If the current limit is reached, the output voltage is reduced so that the current
limit is not exceeded. Sensitive settings such as current limit and frequency limits are combined in a limit
menu. Settings in the menu can only be made after enabling the key number in the "Service menu". In the
service menu, the current settings can also be saved and the factory settings of the units can be restored.
2.1 Track control
Via internal, adjustable
time steps ("t on" and "t
off"), the output is
switched ON or OFF
depending on the
material level measured
via a track component
sensor. The level of the
conveyed material thus
varies around the
position of the track component sensor installed on the feeder. The output of the control unit is switched
on when the conveyed material falls below the sensor and the set switch-on time delay has elapsed. If the
conveyed material exceeds the position of the sensor, the control unit's output is switched off after expiry
of the switch-off delay (indication in the display: " full"). Gaps in the flow of conveyed material reset
the time stages. The times are always determined by the last or first conveyed part.
The switch-on or switch-off delay time is set in the programming menu. The run-down of the internal time
stages is shown by the clock in the display.
When the feeder is switched on, a further time stage "sensor timeout" can be started, which switches
the feeder off after an adjustable time (1...240 sec.) if no material parts have passed the sensor within this
time. When the feeder is switched off, the status relay also switches off. The display then shows "Track
Timeout and Info 0001" flashing alternately. This function is optional and must be activated in the track
control menu with function "Timeout On" = .
2.2 Operation with two speeds (2
nd
setpoint for coarse/fine switching)
Instead of track control, coarse/fine operation can also be used. Switching to the second setpoint is done
via the sensor input that is otherwise used for track control. Switching can be done with a contact or an
external 24 VDC signal voltage. If a 24 V signal is present, the system switches to the second setpoint
"Fine" without any time delay.
(The track control function is not available.)

REOVIB MFS 368
Operating instructions
9
2.3 Control inputs and outputs
2.3.1 Enable input
Potential-free contact or 24 VDC signal.
External control option for switching the power output On/Off, e.g. for linking several units or control by a
PLC.
2.3.2 Sensor input for track control
Sensor for monitoring the material level in a backlog section or input for switching to a second setpoint.
24 VDC (PNP).
2.3.3 External setpoint
The feeder amplitude set point can be provided from and external, analogue reference value 0...10 VDC,
0/4...20 mA. The parameter "External setpoint" must be activated in the “Feeder" menu, for an external
setpoint source to be used.
Adjust the desired minimum value using the "arrow keys". Switch only now to the external setpoint. The
adjusted value remains at setpoint "0" as a minimum.
2.3.4 Control output status relay
Relay contact 250 V (changeover contact (IP20))
Relay contact 24 V (normally open contact (IP54))
The relay is energised while the feeder is running, and is de-energised if there is no enable signal or fault
message.
2.3.5 Control output 24 VDC Timeout (IP54)
The "Timeout" message is active if no material is detected by the sensor after the set time. (Adjustable
with parameter “Timeout On")
2.3.6 Ready relay
Relay contact 250 V (changeover contact). If an error occurs (e.g. overload error), or if the current limit is
reached, contact 44,45 opens. (Only for IP20)
2.3.7 Control output 24 VDC Valve (IP54)
Output for a blowing air valve.
"On" with feeder start, "Off" 4 sec. after feeder stop (factory setting).
Switch-off and switch-on times can be adjusted with the parameters "Air lead time" and "Air delay time".
2.3.8 Thermal switch
The frequency converter has a special input for the connection of a thermal switch, which can be attached
to the magnet by the user. This can effectively protect the conveyor system from overheating.

REOVIB MFS 368
Operating instructions
10
2.4 Touch panel
The units are operated via the operating keys and the text/graphic display.
: 90.0 %
50,5 Hz
A
Operatingdisplay
Conveyorsetpoint
Frequencyconveyor
Status line
Frequency:
I
0
Start /Reset
Stop
Key Function for menu navigation Function for changing
values
Arrow keys
Select
menu item
Cha
ng
e values
F
key
One menu level back
Abort during value
entry
P key
Open sub
-
menu
Apply value
100
STOP
A
Conveying capacity
Limits
Time out
Information
Language
Sym
"Fun
"
bols
ction
Symbols of the status line
Locked
( )no enable
Stop-Button
TrackCtrl.
„Busy“on storage
Keyset
Service enabled
Mainsundervoltage
Feeder

REOVIB MFS 368
Operating instructions
11
3.0 Structure
The unit is available as IP54 or IP 20 version.
3.1 IP54
•Power switch
•Control and display panel
•Mains supply lead (optional)
•Output cable or output socket for feeder connection
•Sensor sockets. 24 VDC sensors with PNP output are provided.
3.2 IP20
Fixing points for attachment to a mounting plate.
Electrical connection on external terminals.
4.0 Technical data
Protection type IP54 IP20
Protection class I
Supply voltage 99…264 VAC
Max. permissible input current*
1
(Important information in Chapter 4.5)
I
n
: 2 A
Input frequency 50 / 60 Hz
Inrush current Î= 9 A, 20 ms
Power loss max. 55 W
Output voltage 0... 205 V +/- 5%
Output current 3 / 6 / 8 A +/- 5%
Output frequency*
2
20…140 Hz
Recommended automatic circuit
breaker 6 A B/C
RCD Type "B".
Mains system
TN system
Rated short-time withstand current
(I
cw
) <10 kA
Rated short-circuit current (I
cc
) <10 kA
Enable input Contact / 24 VDC
Analogue setpoint 0...+10 VDC, 0/4…20 mA
Air valve output 24 V, 100 mA, DC -/-
Timeout output
Backlog sensor 24 V, PNP (100 mA, DC)
Status relay (On/Off)*
3
Make contact (24 V, 1 A)
Changeover
contact (250 V,
1 A)
Ready relay (fault) -/-
Operating temperature 0...+40 °C
Storage temperature -10...+65 °C
Rel. humidity (storage) 10...95 % RH without condensate
Weight approx. 2.7 kg approx. 2.3 kg
*
1
Important information in Chapter 4.5 "Current consumption".
Non-observance can lead to malfunction and failure.
*
2
Other frequencies on request.
*
3
The connections of status and ready relays cl. 21-23 and cl. 44-46 must not be combined with
different mains classes. Both relay contacts may only be used with signals of the same mains
class.

REOVIB MFS 368
Operating instructions
12
4.1 Load supply requirements
The unit is not suitable for feeder coils with a power of <18 VA (100 mA).
4.2 Terminal details
Tightening torque:
Terminals MSTB/GMSTB, GMSTB-GIC: 0.5-0.6 Nm Connections: 21-29 and 44-46
MC terminals: 0.22-0.25 Nm Connections: 1-9, 31-34 and 51-52
4.3 Temperature of protective housing
Only suitable for mounting on concrete or other non-combustible surfaces.
4.4 Coolant type
Free convection.
4.5 Current consumption
The current consumption specified in the technical data is the maximum permissible value for the unit. A
higher current consumption than specified can lead to malfunctions and failure. Please note that the input
current is inversely proportional to the input voltage. When the input voltage is high, the input current is
low and when the input voltage is low, the input current is high.
Example:
A 230 V vibratory feeder is operated on a 230 V mains supply using the MFS368. A current of 1 A is
detected at the input of the controller. The same 230 V vibratory feeder is then operated on a 110 V
mains supply. The input voltage is only half as high as before and the input current is therefore twice as
high. This means that the input current of the controller on the 110 V mains supply is then 2 A.
NOTE: When dimensioning, especially for international markets, ensure that the maximum specified input
current is not exceeded at the lowest expected supply voltage.
4.6 Warning signs
Warning sign "Warning of too hot surface" must be visibly attached to the heat
sink.

REOVIB MFS 368
Operating instructions
13
5.0 Ordering code (Standard units)
1 0 200 6368 2 1 2 1
Interfaces:
--- = without
EC = EtherCat
E I/P = EtherNet
PN = ProfiNet
DP = ProfiBus
CAN = CAN-Bus
DN = DeviceNet
EK = Input cable (open cable ends) V = Vertical design
AK = Output cable H = Horizontal design
AD = Output socket
PV = Plug & Vib
Control connections:
-Track control sensor
- Status relay
- Ready relay
- Enable input
- External setpoint 0...10 V, 0/4...20 mA
- Amplitude sensor
- Thermal switch (Series)
The following control connections are internally
included in all versions (IP54):
- Thermal switch (Series)
- External setpoint input: 0...10 V, 0/4...20 mA
0= ---
1= EC
2= E I/P
3= PN
4= DP
5= CAN
6= DN
1= 3 A
2= 6 A
3= 8 A
0= IP20 V
1= IP20 V UL
4= IP54 EK/AK
5= IP54 EK/AK UL
6= IP54 EK/AD
7= IP54 EK/AD UL
8= IP54 PV
9= IP54 PV UL
1= IP20 Basic
2= IP20 Series
4= IP54 Basic
5= IP54 Series

REOVIB MFS 368
Operating instructions
14
6.0 Possible settings
No. Icon Menu item Meaning Setting Factory
setting
1
P
Output
1.1
Feeder Feed rate 0...100% 0%
1.1.1 Fine Setpoint "Fine" (previously "Activate
coarse / fine") 0...100% 0%
2
Feeder
2.1 Frequency Set frequency 35...140 Hz 100 Hz
2.2 Invert Enable Invert Enable
switched Off
2.3 External setpoint Activate external setpoint
switched Off
2.3.1 Setpoint Setpoint type 0/2/1...10 V / 0/4...20 mA 0/2/1...10 V /
0/4...20 mA 0...10 V
2.4 Soft start Set soft start time (setpoint 0...100 %) 0...60 sec. 1 sec.
2.5 Rundown Set soft stop time (setpoint 100...0 %) 0...60 sec. 0.1 sec.
2.6 Max. Limit maximum feed rate 0...100% 90%
2.7 Acc. controller Activate Acc. controller (switch-off
deactivates Auto. freq.) switched Off
2.7.1 Prop. gain Adjust P setting of Acc. controller 0.01...100 0.40
2.7.2 Integral Adjust I portion of Acc. controller 0.01...100
sec. 0.15 sec.
2.7.3 Auto. freq. Activate frequency search and
frequency tracking (only if Acc.
controller is activated) switched Off
2.8 Air jet present*
1
Activate air blow function
switched Off
2.8.1 Air lead time*
1
Air blow lead time 0...60 sec. 0 sec.
2.8.2 Air delay time*
1
Blowing air shut-off delay 0...60 sec. 4 sec.
2.9 Hopper cycle Feeder output is cycled
switched Off
2.9.1 Time On Hopper On time 0...60 sec. 15 sec.
2.9.2 Time Off Hopper Off time 0...60 sec. 4 sec.
3
Track control
3.1 Coarse / Fine Coarse / Fine
switched Off
3.2 T-On Switch-on time delay 0...60 sec. 5 sec.
3.3 T-Off Switch-off time delay 0...60 sec. 5 sec.
3.4
Timeout On Activate sensor timeout
switched Off
3.5
Timeout Set sensor timeout time 1...240 sec. 180 sec.
3.6 Inv. sensor Invert sensor
switched Off
4
100
Limit values
4.1 Actual current Actual current display View only
4.2 Current limit*
3
Current limit 5...100% 100%
4.3 El. fuse*
3
Output switch-off, instead of output
current limitation switched Off
4.4 Min. freq.*
3
Set minimum frequency 20...140 Hz*
2
35 Hz
4.5 Max. freq.*
3
Set maximum frequency 20...140 Hz*
2
140 Hz
4.6 Umax*
3
Output voltage limiting
230 V coil -> Umax: 100%
115 V coil -> Umax: 50% 0...100% 100%
5
In
terface
5.1 Bus operation Activate / deactivate bus mode
Switched Off*
4
5.2 Bus address Internal bus address (do not change) 1...16 1
5.3 Bit rate Internal bus bit rate (do not change) 1 Mbit/s / 500
kbit/s 1 Mbit/s
5.4 Protocol Interface protocol (do not change) V1.i / V2.f V1.i

REOVIB MFS 368
Operating instructions
15
6
Info
6.1 Software version
7
Service
7.1 Clear ERROR &
reset Clear ERROR & reset execute
7.2 Factory settings*
5
Load factory settings execute
7.3 Parameter set Select parameter set 1 / 2 / 3 / 4
7.4 Save parameters Save current parameters in the
selected parameter set (only if key no.
143 is activated)
7.5 Load parameter
set Load and apply selected parameter set execute
7.6 Language Select language DE, EN
EN
7.7 Key Enter key number 117 / 127 /
143
7.8 Backlight Backlight: Permanently On / Off /
timeout On/Off /
0...999 sec
7.9 Display inverted Invert display colours
switched Off
*
1
only available with the housing version
*
2
Other frequencies on request
*
3
These menu items are only displayed if key no. 127 is activated.
*
4
depending on unit type
*
5
After loading the factory settings, check the "UMax" parameter.
Key 117: Entry "Close" becomes visible. This can be used to hide/show various menus.
Key 137: "Lock" entry This can be used to hide/show additional menus.
Key 127: Entry "Service On" becomes visible. This makes further items visible in the service menu.
Key 143: Entry "Save parameters" becomes visible.

REOVIB MFS 368
Operating instructions
16
7.0 Operating elements
Abort,
Exit
Confirm,
Apply,
Selectmenu
Select menu /parameter,
Adjustvalue
Start/Reset
Stop
7.1 Setting behaviour
3
4
5
6
7
8
1
Change p Adjust valuearameter /
Activate parameter entry (Editing mode)
End parameter input, the new value is saved
Back to previous menu
Jumping to the menu from the home screen
Select menu and open the submenu
Select parameter
Start on the Homescreen
2
Navigate to the desired menu item
3
4
5
1
Back to Homescreen
Leads to the shortcut menu (to the setpoint parameter)
Adjust parameters (Setpoint)
End parameter input
Start on the Homescreen
2
Activate parameter entry (Editing mode)
Use shortcut menu

REOVIB MFS 368
Operating instructions
17
7.1.1 Parameter setting example
1 2 3 4
100
: 90.0 %
50,5 Hz
A
P P P
Frequency:
Black background u p selected: Men / arameter
Operating mode
Track Ctrl.
Feeder
Limits
Power
Feeder 10.0%
Power Power
Feeder 10.0%
5 6 7
P P P
Frameblinks
Power Power Power
Feeder 20.0%
Feeder 10.0% Feeder 20.0%
7.1.2 External setpoint example
1 2 3 4
100
: 90.0 %
50,5 Hz
A
PP
Frequency:
Operating mode
Track Ctrl.
Feeder
Limits
Power
Feeder 90.0%
Power Feeder 90.0%
Feeder
100
Track Ctrl.
Limits
Frequency 50.5 Hz
Invert. Enable
External Setpoint
External Setpoint
5
Feeder 90.0%
External Setpoint
Feeder 90.0%
External Setpoint
67
Ext-Setp. 0-10 V
8
Feeder 90.0%
External Setpoint
Feeder 90.0%
Ext-Setp. 0-10 V
External Setpoint
8
Feeder 90.0%
External Setpoint
Ext-Setp. 0-10 V
9
Feeder 90.0%
External Setpoint
Ext-Setp. 0-20 mA
10
Feeder 90.0%
Ext-Setp. 0-20 mA
External Setpoint
11

REOVIB MFS 368
Operating instructions
18
8.0 Commissioning
8.1 Preparatory measures
Notes
With the control units described here, it is possible to adjust the resonant frequency of
the connected feeder. Since in this case even a small setpoint value can lead to full
operation of the feeder, appropriate care must be taken to ensure that no damage
occurs in the feeder due to coil hammering.
In practice, however, the resonant frequency range cannot be used without feedback of
the acceleration, as the feeder would not be loadable or controllable. Therefore, a certain frequency offset
from the resonant frequency must be set. The frequency offset can be both below and above the
resonant frequency.
Independent of the input voltage, the frequency converter's output voltage is 205 VAC
when delivered. When using 110V VAC coils, the output voltage must be set using
parameter: "Umax", otherwise the feeder coil and the drive or the vibratory feeder may
be damaged.
•Check whether the local supply voltage corresponds to that of the unit (type plate information) and
whether the connected power of the feeder is within the permissible power range.
•Check that the output voltage and frequency of the control unit are compatible with the selected
magnet.
•Connect the control unit according to the enclosed connection diagram
•Adjust setpoint to zero
•Switch off Enable (if used)
The control unit is now basically ready for operation and can be switched on (mains, Enable).
Resonance frequencies: Due to the structure of the spring-mass system of the feeders, the system can
resonate at several vibrating frequencies. The additional resonant points are at a multiple of the desired
frequency. In critical cases, the automatic frequency search cannot reliably detect the desired vibrating
frequency; in this case, the frequency may have to be adjusted manually.
Storage: After a storage period of one year, the internal DC link capacitors must be reformed. To do this,
connect the MFS to the supply voltage for 60 minutes without load; for the IP54 version, also switch on
the mains switch. If the product is stored for more than one year, the manufacturer must take care of the
reforming. Failure to observe the reforming prescriptions may result in the destruction of the unit.
8.2 Operating frequency of the feeder coils
When using the unit for the first time the current in the solenoid circuit should be
checked with an RMS meter or the heat development at the coil should be monitored,
as the current through the coil may increase at low frequency settings.
In order to avoid excessive power consumption and thus possibly an overload of the coils, please make
sure that the coils are designed for the operating frequency.
An incorrect vibrating frequency may lead to the destruction of the coils and the drive or the vibratory
feeder. Make sure that suitable feeder coils are used for the desired vibrating frequency.
8.3 Measurement of output voltage and output current
Since the unit output is an electronic frequency converter with pulse-width modulated switching signals,
the voltage and current values cannot be measured with any standard measuring device. Moving iron
meters are recommended for measuring these values.
!
!
!

REOVIB MFS 368
Operating instructions
19
9.0 Settings
9.1 Notes on controller mode
•For controller mode, an accelerometer mounted on the vibratory feeder is required, e.g. SW 70 (for
IP54 units) or SW10 (for IP20 units).
•In control mode with sensor feedback, all vibrations detected by the sensor are processed in the
control circuit. External vibrations caused by neighbouring machines, by an unstable position of the
feeder, or by unstable mounting of the accelerometer can lead to erroneous control performance.
Especially during the AFS automatic frequency search, no external influences must be allowed to
affect the feeder.
9.2 Mounting the accelerometer
The accelerometer must return the movement and the acceleration of the feeder to the control circuit of
the control unit. It is therefore very important that no additional spurious vibrations caused by an
unfavourable sensor mounting are measured.
The sensor should be mounted in the direction of
vibration (ideally at the same inclination as the
feeder springs) on a solid mounting block which
does not generate any natural vibrations.
The accelerometer cable must be supported with a cable clamp to prevent the cable
from being damaged.
In control mode, the output signal level directly determines the feeder's maximum vibration
amplitude.
!
SW SW
SW
100
1
0
0
Cable clamp

REOVIB MFS 368
Operating instructions
20
In the case of bowl feeders, it is advisable to mount the sensor as
far as possible on the outer diameter so that the largest possible
vibration displacement is covered.
If the sensor signal is too low, the setpoint's control range is
significantly restricted.
s = vibration displacement
Mounting point 1 = small vibration amplitude
Mounting point 2 = large vibration amplitude
Example of bowl feeder
1. small amplitude with vertical
mounting.
2. larger amplitude when
mounted at the same
inclination angle as the
springs.
Example of linear feeder
The control system and the sensor attached to the feeder form a closed control loop, whereby the signal
supplied by the sensor has a decisive influence on the setpoint's control range. I.e. the feeder is
controlled so that the actual value (feed rate or vibration intensity) corresponds to the specified setpoint
(ideal: 100 % setpoint = 100 % actual value). However, since the actual value depends on the feeder
(frequency, acceleration, vibration amplitude) and also on the sensor's mounting location, the control
range must usually be adjusted.
The adjustment is made with the "Max" parameter in the "Feeder" menu. The measured sensor signal is
adjusted with the value that can be set here. In most cases, a value below 100 must be entered so that
the setpoint’s control range reaches 100 % or appears to be as large as possible.
If no satisfactory adjustment is possible, the accelerometer should be mounted at a location with a larger
vibration amplitude (see example of bowl feeder).
The importance of adjusting this value can be seen, for example, in the time response of the controller.
Where the actual value is badly adjusted, for example, the result can be that the feeder only ramps up
very slowly when it is switched on.
1 2
2
1
s
Sensor
Swing Direction
Mounting Block
Moving Part
Fixed Part
1
2
Table of contents
Popular Industrial Equipment manuals by other brands

GREEN INSTRUMENTS
GREEN INSTRUMENTS G3610 instruction manual

Parat
Parat PARAPROJECT TROLLEY U40 WOL user manual

Siemens
Siemens SIPLUS HCS4200 PROFINET Compact operating instructions

SCHUNK
SCHUNK SRM Series Assembly and operating manual

Master
Master Sorter 500 Instructions for use and maintenance

Pfeifer
Pfeifer 114204 Translation of the original operating manual