Response Alarms SA3 Installation instructions

Installation & Operating Manual
SA3
6 Zone Wirefree
Alarm System
123
456
7
*
0#
8
ESC ENTER
ZONE 1ZONE 2ZONE 3ZONE 4
ZONE 5ZONE 6FIRE TAMPER
9

FOREWORD
All components in this wirefree Alarm System are
designed and manufactured to provide a high standard
of security protection and long, reliable service.
The system is designed for ease of installation using
only conventional domestic tools. However, it is
essential that the installer reads and fully understands
the advice and procedures contained in this manual and
plans the system before proceeding with the installation.
During installation, it is important that the procedures
described in this manual are followed in sequence.
This manual should be retained in a safe place for
future reference.
IMPORTANT
All components, with the exception of the External
Solar Siren are suitable for mounting in dry interior
locations only.
DECLARATION
Novar ED&S hereby declares that this wirefree alarm
system is in compliance with the essential
requirements and other relevant provisions of the
Radio and Telecommunications Terminal Equipment
(R&TTE) directive, 1999/5/EC.
No radio operating licence is required for this equipment.
Tools and Equipment Required:
No.0 Philips Screwdriver Drill
No.1 Philips Screwdriver Bradawl
No.2 Philips Screwdriver Small Spirit Level
5 & 6mm Masonry Drill Bits
DEVICE RANGE
The quoted range of the system devices (see
component specification on rear cover) is measured
in ideal conditions. Any solid object (e.g. walls,
ceilings, reinforced PVC doors etc) placed between
the transmitter devices and the Receiver(s) will
reduce the transmission range of the devices.
The amount by which the range will be reduced is
dependant upon the nature of the barrier. e.g.
Wall Type Range Reduction
Dry-lined partition wall: 10-30%
Single layer brick wall: 20-40%
Double layer brick wall: 30-70%
Metal Panel/Radiator: 90-100%
Note: The effect on the range of multiple walls is
cumulative. i.e. if there are two brick walls in the way,
the range will be reduced by up to 40% by each wall.
SYSTEM SECURITY
This system has been designed to both detect
intruders and act as a strong deterrent to would-be
intruders when installed correctly.
Please remember that given adequate knowledge and
time it is possible to overcome any alarm system and
we therefore recommend that an Intruder Alarm is
used in conjunction with good physical protection
such as security window and door locks.
All units in the system are encoded to operate
together using an 8 bit House Code which is
configured by the user/installer to provide the unique
identification code for your installation. The system
House Code can be changed at any time by the user.
The system is operated from one or more Remote
Control units and/or the Control Panel. Care should
be taken to ensure that your Remote Control Unit(s)
are not lost or the User Access Codes for the Control
Panel do not become known to other people as this
will compromise the security of your system. In either
event the system house code and User Access Codes
should be changed as soon as possible.
SAFETY
Always follow the manufacturers advice when using
power tools; steps, ladders etc. and wear suitable
protective equipment (e.g. safety goggles) when
drilling holes etc.
Before drilling holes in walls, check for hidden
electricity cables and water pipes, the use of a
cable/pipe locater maybe advisable if in doubt.
When using ladders, ensure that they are positioned
on a firm stable surface at the correct angle and
suitably secured before use.
The use of ear defenders is advisable when working in
close proximity to the Siren due to the high sound
level produced by this device.
SA3 6 Zone Wirefree Alarm SystemFriedland
IMPORTANT: All units in your system must be set
to the same House Code which must be changed
from the factory supplied setting.

CONTENTS
Page No.
KIT CONTENTS 2
INTRODUCTION AND OVERVIEW
3
System Arming
3
Entry/Exit Delay
3
Zones
3
Zone Lockout
3
Tamper Protection
4
Jamming Detection
4
Battery Monitoring
4
System House Code
4
PLANNING AND EXTENDING YOUR WIREFREE
ALARM SYSTEM
5
REMOTE CONTROL UNIT
6
General Information
6
Configuring the Remote Control
7
CONTROL PANEL
7
Positioning the Control Panel
7
Installing the Control Panel
7
Configuring the Control Panel House Code
8
Testing the Control Panel & Remote Control
9
PASSIVE INFRA-RED (PIR)
MOVEMENT DETECTORS
10
Positioning the PIR Movement Detectors
10
Installing and Configuring the PIR
Movement Detectors
11
Testing the PIR Movement Detectors
12
MAGNETIC CONTACT DETECTORS
12
Positioning the Magnetic Contact Detectors
13
Installing and Configuring the Magnetic
Contact Detectors
13
Testing the Magnetic Contact Detectors
14
EXTERNAL SOLAR SIREN
14
General Information
14
Positioning the Solar Siren
15
Installing and Configuring the Solar Siren
15
Power-up of the Solar Siren
16
Testing the Solar Siren
17
Page No.
EXTERNAL CONNECTIONS
17
TESTING THE SYSTEM
17
Initial Testing
17
Testing An Installed System
17
FACTORY DEFAULTS
18
Reset Factory Default Conditions
19
PROGRAMMING
19
User Access Code
19
System House Code
19
Instant/Delay Zones
20
Entry/Exit Delay
20
Alarm Duration
20
Part-Arm
20
Zone Lockout
21
Entry/Exit Warning Tone
21
Jamming Detection
21
NO/NC Relay Contacts
22
Zone Operating Modes
22
OPERATING INSTRUCTIONS
23
Arming The System
23
Part-Arming The System
23
Disarming The System
23
Personal Attack (PA) Alarm
24
Tamper
24
Siren Service Mode
24
Siren Operating Mode
24
Battery Monitoring
25
MAINTENANCE
25
ALARM RECORD
26
TROUBLE SHOOTING
27
EXTENDING YOUR ALARM SYSTEM
29
COMPONENT SPECIFICATION
Back Cover
1SA3

KIT CONTENTS
The Alarm System should contain the following
components.
1xExternal Solar Siren
1xControl Panel
1xRemote Control
2xPIR Movement Detectors
2xMagnetic Contact Detectors
Also included:
Power Supply Adaptor
Installation & Operating Manual
Fixing pack
Batteries
EXTENDING THE ALARM SYSTEM
The following additional accessories are available to
enhance your system and provide further protection
and a higher level of security where required.
Component: Product Code
Two Magnetic Contact Detectors
and one Remote Control SU1
Two Passive Infra-Red
Movement Detectors SU2
Two Remote Controls SU3
Two Magnetic Contact Detectors SU4
Remote Keypad SU5
External Solar Siren SU6
Full details of these accessories are given on page 29.
2SA3
123
456
7
*
0#
8
ESC ENTER
ZONE 1ZONE 2ZONE 3ZONE 4
ZONE 5ZONE 6FIRE TAMPER
9
WP1.2-6
External Solar Siren
Control Panel
Magnetic
Contact
Detector
Remote
Control
PIR Movement
Detector
6V/1.2Ahr
Sealed lead acid battery
(supplied fitted in
Solar Siren)
9V PP3 Alkaline
battery
(for PIR Detectors)
3V CR2032
Lithium Cell
(for Remote
Control and
Magnetic Contact
Detectors)

INTRODUCTION AND OVERVIEW
SYSTEM ARMING
The system has a full ‘Arm’ and a ‘Part-Arm’ mode.
Full ARM will arm all zones while the ‘Part-Arm’ will
only arm the zones that are enabled for “Part-Arm”.
For example:
The system could be configured such that during night
time, ‘Part-Arm’ would arm only zones protecting the
lower floor and outbuildings leaving the upper floor
free for movement without triggering the alarm.
However, when the property is left un-occupied, the full
‘Arm’ mode will arm all zones to protect the entire
property, (i.e. upper and lower floors and outbuildings).
ENTRY/EXIT DELAY
Each zone can be programmed to be Armed in either
Instant or Delay mode.
Usually the zone covering the main entrance door and
the route to and from the Control Panel would be
configured in Delay mode. This allows time for the
user to exit the property after setting the system at the
Control Panel or to Disarm the system before an alarm
condition is triggered when re-entering the property.
The remaining zones would be configured as Instant
allowing them to initiate an alarm immediately a
detector on the zone is triggered.
Delay Armed zones will not become fully armed until
after the Entry/Exit delay period has expired. When a
detector on a Delay Armed zone is triggered, an alarm
condition will not be triggered until after the Entry/Exit
period has elapsed. If the system is not disarmed
during the delay period, an alarm condition will occur
when the delay period expires.
Instant Armed zones are immediately able to initiate
an alarm as soon as the system begins to arm.
Note: To conserve power and maximise battery life
the PIR Detector will only detect movement if there
has been no movement detected within the previous
2 minutes. Consequently the PIR Detector will not
become active until the protected area has been free
from movement for more than 2 minutes.
ZONES
The system incorporates 6 wirefree Alarm Zones for
the connection of the system detectors that are used
to independently monitor different areas of the
property. In addition to standard intruder protection,
each zone may also be configured to operate in one of
three other modes:
- ‘Personal Attack’ mode provides 24 hour monitoring
of any Personal Attack (PA) switches incorporated
into the system.
- ‘24-hour Intruder’ mode provides 24 hour intruder
protection for areas where continuous monitoring is
required, (e.g. gun cupboards).
- ‘Fire’ mode provides 24 hour monitoring of any
Fire/Smoke detectors incorporated into the system.
ZONE LOCKOUT
If a detector on an active zone is triggered while the
system is armed an alarm condition will occur. After
the programmed alarm duration has expired the alarm
will stop and the system will automatically reset.
Subsequent detectors triggered will again initiate an
alarm condition. If a single zone initiates an alarm
condition more than three times then that zone will be
‘Locked Out’ and any further alarm signals from that
zone will be ignored until the system is disarmed.
Note: The ‘Zone Lockout’ feature can be disabled if
required.
SA3 3
Full Arm
Part-Arm
INTRODUCTION

TAMPER PROTECTION
All system devices (except any Remote Control
Units) incorporate Tamper protection features to
protect against unauthorised attempts to interfere
with the device.
Any attempt to remove the battery cover from any
device (except a Remote Control) or to remove the
Solar Siren or Control Panel from the wall will initiate
an alarm condition (unless the system is in Test or
Programming modes), even if the system is Disarmed.
JAMMING DETECTION
In order to detect any attempts to illegally jam the
radio channel used by your alarm system, a special
jamming detection function is incorporated into the
Control Panel and Solar Siren. If this feature is
enabled, and the radio channel is jammed
continuously for 30 seconds, when the system is
armed, the Solar Siren will emit a pre-alarm series of
rapid bleeps for 5 seconds. If the jamming continues
for a further 10 seconds or more a full alarm condition
will occur. In addition if the system is jammed for
more than three periods of 10 seconds in a 5 minute
interval, this will also generate a Full Alarm condition.
The Jamming Detection circuit is designed to
permanently scan for jamming signals. However, it is
possible that it may detect other local radio
interference operating legally or illegally on the same
frequency. If it is planned to operate the jamming
detection feature we recommend that the system is
monitored for false jamming alarms for at least 2
weeks prior to leaving the Jamming Detection function
permanently enabled.
Note: The jamming detection features incorporated
into the Control Panel and optional Solar Siren operate
independently.
BATTERY MONITORING
All devices powered by non-rechargeable batteries
incorporate a battery level monitoring feature which
will warn of a low battery status. In addition the
Control Panel will also indicate a low battery status
within any Passive Infra-Red or Magnetic Contact
Detector on the system. The batteries on any device
indicating a low battery status should be replaced
immediately.
SYSTEM HOUSE CODE
In order to prevent any unauthorised attempt to
operate or disarm your system, you must configure
your system to accept radio signals only from your
own system devices. This is done by setting a series
of eight miniature (DIP) switches in all devices
(except the Control Panel) to the same ON/OFF
combination (the House Code) selected by the
user/installer. The Control Panel is then programmed
to operate only with devices set to this House Code.
All detectors and Remote Control Unit(s) must be
configured with the same House Code in order for
the system to operate correctly.
Inside the Siren, Detectors and Remote Control Unit is
a series of 8 DIP switches.
The House Code is set up by moving each of the 8
switches in each device to the same randomly selected
ON/OFF sequence. When setting the DIP switches,
ensure that each switch ‘clicks’ fully into position. Use
the tip of a ballpoint pen or a small screwdriver to move
each switch in turn.
SA34
e.g. Switch 1
= set to ON
position
ON
1 2 3 4 5 6 7 8
INTRODUCTION
Note: It is recommended that the system House
Code is always changed to a code other than the
factory default.

Before attempting to install your Alarm System it is
important to study your security requirements and plan
your installation.
PIR Movement Detectors are used to protect the main
areas of the property, (e.g. lounge, study, hallway and
landing). Magnetic Contact Detectors are typically used
to protect the main access points to the property, (e.g.
front door, back door, patio doors). However, they can
also be used to protect other vulnerable doors/windows
or access doors to important rooms.
TYPICAL INSTALLATION
The following example below shows typical property
incorporating the suggested positions for the External
Siren, PIR and Magnetic Detectors. Use this as a
guide for your installation in conjunction with the
detailed positioning requirements for each device
provided in the appropriate installation sections in this
manual for planning your intruder alarm system.
PLANNING AND EXTENDING YOUR WIREFREE
ALARM SYSTEM
LED
Control
Panel
Magnetic
Contact
Detector
Magnetic Contact
Detector
External Solar
Siren
PIR Movement
Detector
PIR Movement
Detector
Remote
Control
SHED
LOUNGE
GROUND FLOOR GARAGE
KITCHEN
HALL
DINNING
ROOM
PIR Movement
Detector
PIR
Movement
Detector
PIR
Movemen
t
Detector
Back Door
SA3 5
INTRODUCTION

SA36
Typical Installation using only detectors supplied:
1.
Place the 1st Magnetic Contact detector (set on
Zone 1) on the front door.
2.
Place the 1st PIR Detector (also set on Zone 1) in
the hall covering the Control Panel and routes
between downstairs rooms.
3.
Place the 2nd Magnetic Contact detector (set on
Zone 2) on the back or Patio doors.
4.
Place the 2nd PIR Detector either
i) downstairs in the main living room containing most
valuables, (set on Zone 3), or
ii) upstairs on the landing covering the access
routes between bedrooms and the stairs, (set on
Zone 5). This will be inactive if Part-Arm is used.
The system may be expanded with additional
detectors, Remote Controls and Keypads to provide
even greater protection. However the following rules
should be followed:
a) Any detectors covering the main door and the route
to the Control Panel should be set on zone 1 only.
b) Any detectors covering the remainder of the lower
floor should be set on zones 2 to 4 only.
c) Any detectors placed upstairs should be set on
zones 5 or 6 only.
The system default settings are pre-configured to
provide a basic functional system to suit most typical
basic installations:
•Zone 1 is configured as a Delay zone with a 30s
entry/exit delay.
As soon as installation is complete, this should be
changed to your own code that only you and other
system users know.
All other zones are instant.
•The system has a 3 minute alarm duration.
•Zone Lockout is enabled.
•PART-ARM is configured to operate with detectors
on zones 1 to 4 only. Detectors on zones 5 & 6 are
inactive in part-arm.
Note: If you wish to change the system configuration
away from the above example and system default
settings and customise it to your own unique
requirements then refer to the Programming section
on page 19.
REMOTE CONTROL UNIT
The Remote Control Unit(s) are used to Arm, Part-Arm
and Disarm the system.
The Remote Control Unit also incorporates a Personal
Attack (PA) switch. Activating the PA switch on the
side of the Remote Control will immediately initiate a
Full Alarm condition whether the system is Armed or
Disarmed. The alarm can be cancelled by pressing
the ’DISARM’ button on the Remote Control or via the
Control Panel.
Any number of Remote Control Units can be used with
your system, providing they are all coded with the
system House Code.
The Remote Control is powered by a CR2032 type
Lithium cell which under normal conditions will have an
expected life in excess of 1 year. Under normal battery
conditions the LED on the Remote Control will only
illuminate when a button is pressed. However, under
low-battery conditions this LED will continue to flash
after the button has been released. When this occurs
the battery should be replaced as soon as possible.
Slide up
to operate
Transmit LED
Personal Attack
Arm
Part-Arm
Disarm
INSTALLATION
Note:
All system components must be set to the
same House Code.
IMPORTANT:
All system components must be set to the same
House Code.
The default User Access Code for the Control
Panel is "1234", this should be changed to your
own code that only you and other system users
know as soon as installation is complete.

CONFIGURING THE REMOTE
CONTROL
1.
Remove the rear cover by undoing the small screw
on the rear of the Remote Control.
2. Select and record a random combination of ‘ON’ and
‘OFF’ positions for the DIP switches. This will be the
system House Code that enables all elements of your
transmitters to communicate with the Control Panel.
IMPORTANT: The House Code for your system
should be changed from the factory default setting.
3.
Ensure that the jumper link located immediately
below the House Code DIP switches is fitted in
position for use with this alarm system.
4.
Insert the battery under the clip ensuring that the
+ve terminal faces upwards away from the PCB.
5. Replace the rear cover and fixing screw. Do not over
tighten the screw as this could damage the thread.
CONTROL PANEL
Outside View of Control panel
POSITIONING THE CONTROL PANEL
When choosing a suitable location for the Control
Panel, the following points should be considered.
1.
The Control Panel should be located in a position out
of sight of potential intruders and in a safe location,
but easily accessible for system operation.
2.
The Control Panel should be mounted on a sound
flat surface to ensure that the rear tamper switch
on the Control Panel is closed when the Panel is
mounted. The Control Panel should be mounted
at a convenient height of between 1.5 and 2m and
in a position where it will be seen each day.
Note: If small children are in the household, a
further consideration should be given to keeping
the units out of their reach.
3. It is recommended that the Control Panel should
be positioned such that the Exit/Entry tone
(emitted by the Control Panel) can be heard from
outside the property.
4. The Control Panel should be mounted within a
protected area so that any intruder cannot reach
the Control Panel without opening a protected door
or passing through an area protected by a PIR
movement detector when the system is armed.
5. The Control Panel must be located within reach of
a mains socket.
6.
Do not locate the Control Unit closer than 1m to any
large metallic object, (e.g. mirrors, radiators, etc) as
this may affect the radio range of the Control Panel.
INSTALLING THE CONTROL PANEL
1.
Undo the two captive fixing screws on top of the
panel and open the cover. The cover is hinged
along the bottom edge.
2.
Unclip and remove the two back-up batteries on
either side of the panel.
3.
Hold the Control Panel in position on the wall and
mark the positions of the four fixing holes.
Remove the Panel and drill four 5mm holes and fit
the 25mm Wall Plugs.
Note: The wall plugs supplied with the product are
not suitable for plasterboard walls, if mounting the
Control Panel onto plasterboard use appropriate
wall plugs.
IMPORTANT: Do not drill the fixing holes with the
Control Panel in position; as the resulting dust and
vibration may damage the Control Panel’s internal
components and invalidate the guarantee.
House Code
DIP Switches
Jumper Link
Battery Clip
Battery
Zone LEDs
Status LED
s
Keypad
ENTER
ESC
123
456
789
0
*#
ZONE 1 ZONE2 ZONE 3 ZONE 4
ZONE 5 ZONE6 FIRE TAMPER
SA3 7
INSTALLATION

4.
Fit two 18mm No.4 screws into the top holes until
almost fully home and hang the Control panel
over these screws using the two keyhole slots in
the top corners of the panel casing.
5. Route the cable from the Power Supply Unit up
behind and on the right hand side of the Control
Panel and connect the plug to the DC power socket
in the panel, (see diagram above). Ensure that the
cable is not trapped between the panel and the wall.
6.
Fix the Panel to the wall using two 18mm No.4
screws in the lower two fixing holes in the panel and
tighten the upper fixing screws until they just grip
the casing. Do not over tighten the fixing screws as
this could damage or distort the casing.
7.
Ensure that the "Reset" and the "Hard-Wired
Siren tamper detect" jumper links are set in the
OFF position.
8.
Connect battery leads to both back-up batteries
and refit batteries.
Battery 1 (left): Red lead to +ve battery terminal
Blue lead to
–
ve battery terminal
Battery 2 (right): Blue lead to +ve battery terminal
Black lead to
–
ve battery terminal
IMPORTANT: Take care when connecting battery
leads to the batteries as connecting incorrectly
could damage the batteries or the Control Panel.
Note: The Power LED may flash to indicate that the
unit is being operated from the back-up batteries
and that mains supply is not present.
9.
Close the lid of the Control Panel and tighten the
captive fixing screws.
10.
Plug in and switch ON the Power Supply Unit, (the
Power LED should illuminate).
Note: If the Panel Tamper alarm sounds during the
installation reset the alarm by pressing:
, ,
on the Control Panel.
CONFIGURING THE CONTROL
PANEL HOUSE CODE
With unit in Standby mode (Power LED only
illuminated).
1. Press
, ,
123 4 ENTER
8SA3
TAMP GND B+ GND N.C. C N.O. GND V+ OUT GND
Upper Keyhol
e
Fixing Hole
-
ve Terminal
(Black Lead)
+ve Terminal
(Blue Lead)
Reset Jumper
Link P1
Power Supply
Jack Socket
Upper Keyhole
Fixing Hole
+ve Terminal
(Red Lead)
-
ve Terminal
(Blue Lead)
Lower Fixing
Hole
External Tamper
Switch Jumper
Link P51
Power Supply
Cable Route
Inside View of Control Panel
123 4 ENTER
User Access Code
User Access Code
INSTALLATION

The Panel will beep twice and the Arm and
Part-Arm LEDs will illuminate. All Zone, Fire
and Tamper LEDS will flash.
This puts the Control Panel into programming mode.
2. Press ,
This configures the Control Panel ready to learn
the system house code.
The current House Code setting will be displayed
on the Zone, Fire and Tamper indicator LEDs. For
example, a house code of 1101 0011, will be
indicated as shown below:
3.
The new system House Code can be programmed
either directly at the Control Panel or via a Remote
Control Unit as follows:
At the Control Panel:
Press buttons 1-8 on the Control Panel to
configure the LEDs so that they indicate the
required house code. The LEDs will switch to
the opposite state each time the corresponding
button is pressed.
LED ON = 1, (House Code DIP
Switch On/Up)
LED OFF = 0, (House Code DIP
Switch Off/Down)
Using a Remote Control:
With the required House Code already
configured, press the button on the
Remote Control.
The Control Panel will beep twice to
acknowledge the signal and the LED status will
change to correspond with the House Code set
on the Remote Control.
4. Press to save the new setting.
5. Press again to return to Standby mode.
TESTING THE CONTROL PANEL
& REMOTE CONTROL
1.
Arm the Panel by pressing the button on
the Remote Control.
The Zone LED will illuminate for a few seconds
to indicate which zones are being armed. As the
entry/exit delay expires the Panel will slowly beep and
the Arm LED will flash. Towards the end of the delay
the beep rate will increase. When the Entry/Exit delay
is completed the beeping will stop and the Arm LED
will stop flashing and be constantly illuminated.
2.
Disarm the system by pressing the button
on the Remote Control.
The Panel will beep twice and the Arm LED will
turn OFF.
3.
Activate the Personal Attack switch on the Remote
Control.
The Panel alarm will sound and all Zone/Fire/
Tamper LEDs will flash.
4.
Disarm the system by pressing the button
on the Remote Control.
The Panel alarm will stop. The LEDs will continue
to flash.
5.
Press on the Control Panel to return to
Standby mode and cancel any warning LEDs.
6.
Test the range of the Remote Control by pressing
the button on the Remote Control from in
and around the property and from all locations
where you plan to install detectors. Check that the
Control Panel acknowledges the signal from the
Remote Control by beeping twice each time the
button is pressed.
Note: Wait for 10s after pressing the
button before pressing it again.
7.
Press
, ,
The Panel will beep to acknowledge the signal and
the Arm and Part-Arm LEDs will flash.
This put the Control Panel into Test mode.
ENTER
ESC
2
SA3 9
ESC
123 4 ENTER
User Access Code
INSTALLATION
ZONE 1ZONE 2ZONE 3ZONE 4
ZONE 5ZONE 6FIRE TAMPER

PASSIVE INFRA RED (PIR)
MOVEMENT DETECTORS
PIR detectors are designed to detect movement in a
protected area by detecting changes in infra-red
radiation levels caused for example when a person
moves within or across the devices field of vision. If
movement is detected an alarm signal will be
generated, (if the system is armed). PIR detectors will
also detect animals, so ensure that pets are not
permitted access to areas fitted with Passive Infra Red
Movement Detectors when the system is armed.
The Detector incorporates a tamper protection feature
to protect against attempts to interfere with the
device. If the battery cover is removed, an alarm will
immediately occur at any time.
The Detector also incorporates a sensitivity
adjustment feature to compensate for situations
where the detector may be affected by environmental
changes, (e.g. insects, air temperature, etc).
To conserve power and maximise battery life the PIR
detector will only detect movement if there has been
no movement detected within the previous 2 minutes.
The PIR Detector is powered by a PP3 Alkaline battery
which under normal conditions will have an expected
life in excess of 1 year. When the battery level drops,
with the PIR in normal operation mode and the battery
cover fitted, the LED behind the detection window will
flash. When this occurs the battery should be
replaced as soon as possible. (Note: in normal
operation with the LED behind the lens will not flash
on detection of movement).
Any number of PIR Movement Detectors can be used
with your system, providing they are all coded with the
system House Code and are mounted within effective
radio range of the Solar Siren.
POSITIONING THE PIR MOVEMENT
DETECTORS
The recommended position for a PIR Movement
Detector is in the corner of a room mounted at a
height between 2 and 2.5m. At this height, the
detector will have a maximum range of up to 12m with
a field of view of 110°.
The Position of the PCB inside the PIR can be set to 5
different positions to adjust the range of the detection
Detection Zone Pattern for PCB in position 5
pattern created by the PIR. Setting the PCB in position
3 will reduce the range to approximately 9m, with
position 1 providing a range of approximately 6m. The
recommended position setting for the PCB is in
position 5.
When considering and deciding upon the mounting
position for the detector the following points should be
considered to ensure trouble free operation:
1. Do not position the detector facing a window or
where it is exposed to or facing direct sunlight.
PIR Movement Detectors are not suitable for use in
conservatories.
2. Do not position the detector where it is exposed to
draughts.
3. Do not position the detector directly above a heat
source, (e.g. fire, radiator, boiler, etc).
4.
Where possible, mount the detector in the corner of
the room so that the logical path of an intruder would
cut across the fan detection pattern. PIR detectors
respond more effectively to movement across the
device than to movement directly towards it.
5. Do not position the detector in a position where it
is subject to excessive vibration.
6.
Ensure that the position selected for the PIR
detector is within effective range of the Control
Panel, (refer to "Testing the Control Panel &
Remote Control").
2m - 2.5m
23416785910
Detector Range (metres)
5m
110°
180°
10m
3m
10 SA3
INSTALLATION

Note: When the system is Armed, pets should not
be allowed into an area protected by a PIR Detector
as their movement would trigger the PIR and trigger
an alarm.
Note: DO NOT fix the detector to metalwork or
locate the unit within 1m of metalwork (i.e. radiators,
water pipes, etc) as this could affect the radio range
of the Device.
INSTALLING AND CONFIGURING THE
PIR MOVEMENT DETECTORS
Ensure that the system is in Test mode, (see
page 17).
1. Undo and remove the fixing screw from the bottom
edge of the PIR. Carefully pull the bottom edge of
the detector away from the rear cover and then
slide down to release the top clips.
2. Carefully drill out the required mounting holes in
the rear cover using a 3mm drill according to
whether the unit is being mounted in a corner or
against a flat wall.
3. Using the rear cover as a template, mark the
positions of the fixing holes on the wall.
4. Fix the rear cover to the wall using the two 18mm
No.4 screws and 25mm wall plugs, (a 5mm hole
will be required for the wall plugs). Do not over-
tighten the fixing screws as this may distort or
damage the cover.
Note: The wall plugs supplied with the product
are not suitable for plasterboard walls, if mounting
the Detector onto plasterboard use appropriate
wall plugs.
5. Configure the House Code for the PIR Detector
by setting DIP switches 1-8 of SW2 to the same
ON/OFF combination as the House Code DIP
switches in all other system devices.
6. Configure the alarm zone which the detector will
operate on by setting DIP switches 1-3 of SW3 as
follows:
DIP 1 DIP 2 DIP 3
Zone 1 OFF OFF OFF
Zone 2 OFF OFF ON
Zone 3 OFF ON OFF
Zone 4 OFF ON ON
Zone 5 ON OFF OFF
Zone 6 ON OFF ON
e.g. To configure the detector to operate on Zone
3 set DIP switches 1, 2 and 3 of SW3 as follows:
7. DIP 4 of SW3 is used to configure the PIR Detector
for walk test mode, which allows the operation of
the detector to be checked during installation
without triggering a Full Alarm.
ON Walk Test mode
OFF Normal operation
Note: On initial installation the detector should be
configured into Walk-Test mode ready for testing.
8. To select the required sensitivity, set DIP 5 of SW3
as follows:
ON HIGH sensitivity
OFF LOW sensitivity
Note: The recommended setting is HIGH. However,
in cases of extreme environmental problems or if
unexplained false alarms are experienced, it may be
necessary to set the sensitivity to LOW. Setting the
device to LOW sensitivity will require a greater
amount of movement in order to trigger the device.
9. Connect the PP3 Alkaline battery to the battery clip.
The LED behind the lens will rapidly flash for
approximately 2-3 minutes until the PIR has stabilised.
The LED will then stop flashing and turn OFF.
Note: If the device is configured in Walk Test mode
(i.e. DIP 4 of SW3 ON) then the LED will flash upon
detection of movement after the warm up period
has expired.
Mounting Hole
Positions
Fixing
Screw
Rear Cover
ON
1 2 3 4 5
SA3 11
INSTALLATION

10.
Check that the detector PCB is located and set in
the correct position to give the detection zone
pattern required.
To adjust the PCB position simply slide it up or down
ensuring that the location legs are aligned with the
required position number marked on the board.
PCB Position Range
16m
39m
512m
11. Refit the PIR detector to the rear cover by offering
the detector up to the rear cover and locate the
clips in the top edge into the rear cover. Push the
lower edge of the detector into place and refit the
fixing screw in the bottom edge of the PIR to
secure in position. Do not over-tighten the fixing
screws as this may damage the casing.
TESTING THE PIR MOVEMENT
DETECTORS
Ensure that the system is in Test mode, (see
page 17).
Ensure that the PIR is configured in Walk Test mode, (i.e.
DIP 4 of SW3 ON) and mounted in position on the wall.
Allow 2-3 minutes for the detector to stabilise before
commencing testing.
1. Put the Control Panel into "Walk Test" mode by
pressing on the Control Panel.
The Panel will beep and the Zone 1 LED will illuminate.
2. Walk into and move slowly around the protected
area, each time the detector senses movement the
LED behind the lens will flash. In addition, the Control
Panel will bleep twice to indicate that the alarm signal
has been received and the appropriate zone LED
which the detector is configured for will illuminate.
If necessary re-adjust the detection pattern by
changing the mounting position of the PCB within
the PIR housing.
Note: In normal operation, the LED behind the PIR
lens will not flash on movement detection, (unless
the battery is low).
3.
Press on the Control Panel to exit Walk
Test mode.
4. Reconfigure the PIR Detector into Normal
operation mode and refit in position.
Note: When the detector is fully installed i.e. battery
cover is refitted, to conserve power and maximise
battery life the PIR detector will only detect
movement if there has been no movement detected
within the previous 2 minutes.
MAGNETIC CONTACT
DETECTORS
The Magnetic Contact Detector comprises two parts;
a Detector and a Magnet. They are designed to be
fitted to either doors or windows with the Magnet
screwed to the moving/opening part and the
Detector screwed to the fixed door or window frame.
When the protected door or window is opened and
the magnetic field from the Magnet moved away
from the Detector an alarm signal will be generated,
(if the system is armed).
The Magnetic Contact Detector has the facility to
connect an additional wired Magnetic Contact. This
must be of a normally closed contact type with the
contact being opened in order to generate an alarm
condition.
The Magnetic Contact Detector is powered by two
CR2032 type Lithium cells which under normal
conditions will have an expected life in excess of 1
year. Under normal battery conditions the LED on the
Detector will not illuminate when the Detector is
triggered, (unless in test mode). However, under low-
battery conditions this LED will be illuminated for
approx 1s when the detector is triggered. When this
1
DIP Switches
(SW2 and SW3)
PCB Board
(slides up and
down to adjust
position)
5
4
3
2
1
PCB Position
Indicator
(positions 1-5)
ON
12345 6 7 8
ON
12345
SW3 SW2
SA312
ESC
INSTALLATION

occurs the batteries should be replaced as soon as
possible.
Any number of Magnetic Contact Detectors can be
used with the system, providing they are all coded
with the system House Code and are mounted
within effective radio range of the Solar Siren.
POSITIONING THE MAGNETIC
CONTACT DETECTORS
The Magnetic Contact Detector is suitable for
mounting in dry interior locations only.
Decide which doors and windows are to be
protected by fitting Magnetic Contact Detectors,
(usually the front and back doors as a minimum will
have Magnetic Contact Detectors fitted). However
additional detectors may be fitted where required to
other more vulnerable doors or windows, (e.g.
garage, patio/conservatory doors etc.).
Ensure that the position selected for the Magnetic
Contact Detector is within effective range of the
Control Panel, (refer to "Testing the Control Panel &
Remote Control").
Note: Take care when fixing the Detector to a metal
frame, or mounting within 1m of metalwork (i.e.
radiators, water pipes, etc) as this could affect the
radio range of the device. On uPVC Door/Window
frames, it may be necessary to space the magnet and
detector away from the metal surface using a plastic or
wooden spacer to achieve the necessary radio range.
INSTALLING AND CONFIGURING THE
MAGNETIC CONTACT DETECTORS
Ensure that the system is in Test mode, (see
page 17).
1. Remove the battery cover by sliding and lifting it
off. (DO NOT use a screwdriver to lever it off).
2. The detector and magnet should be mounted
together along the opening edge of the Window/
Door opposite the hinges. Ensure that the parallel
gap between the magnet and detector is less than
10mm and that the arrow on the magnet is aligned
with the mark on the detector.
The detector should be mounted on the fixed part
of the frame and the magnet on the opening part.
The detector and magnet should be mounted
using the double sided adhesive pads or screws
provided.
3. If fixing the detector with screws first remove the
battery holder by carefully tilting up the end and
pulling away from the printed circuit board.
The top of the detector is secured with a keyhole
slot over the head of the smaller pan head screw
and the bottom of the detector is secured using
the 12mm counter-sunk head screw fitted within
the battery compartment. Carefully drill out the
centre of the fixing screw hole in the battery
compartment using a 3mm drill. Fit the magnet
using the two 15mm fixing screws. Do not over
tighten the fixing screws as this may distort or
damage the casing.
4. If an additional wired Magnetic Contact is
required, this should be wired to the terminal
block provided in the battery compartment. The
wired contact should be connected using two
core (24AWG) wire of maximum length 1.5m. A
cable entry cut-out is provided beside the
terminal block in the battery cover.
Battery
Connector
Tilt and Remov
e
Battery Holder
and Insert
Two Batteries
Double Sided Tape
OR Screw Fixing
Raised Head Screw,
Key-hole Slot Fixing
Small Counter-sunk
Screw Fixing
Slide Open and Lift Off
Do Not Use A Screwdrive
r
SA3 13
(Ensure back
s
urfaces are flush)
Detector
Magnet
Alternative
Mountin
g
INSTALLATION

If an additional wired contact is connected to the
detector then jumper link S2 on the PCB must be
removed.
IMPORTANT: If an additional wired contact is not
connected, then the jumper link S2 must be fitted
for the detector to operate correctly.
5. Configure the House Code for the Magnetic
Contact Detector by setting DIP switches 1-8 to
the same ON/OFF combination as the House
Code DIP switches in all other system devices.
6. Configure the alarm zone which the detector will
operate on with DIP switches 9-11 as follows:
DIP 9 DIP 10 DIP 11
Zone 1 OFF OFF OFF
Zone 2 OFF OFF ON
Zone 3 OFF ON OFF
Zone 4 OFF ON ON
Zone 5 ON OFF OFF
Zone 6 ON OFF ON
e.g. To configure the detector to operate on Zone
2 set DIP switches 9, 10 and 11 as follows:
Note: DIP switch 12 is not used.
7. Slide the two batteries supplied into the battery
holder, ensuring that the positive (+) side is
uppermost on each battery as it is installed.
8. If necessary, refit the battery holder into the
detector ensuring that the spring clip connectors
slide onto either side of the circuit board.
9. Refit the battery cover.
TESTING THE MAGNETIC CONTACT
DETECTORS
Ensure that the system is in Test mode , (see
page 17).
1. Put the Control Panel into "Walk Test" mode by
pressing on the Control Panel.
The Panel will beep and the Zone 1 LED will
illuminate.
The LED on the Detector will illuminate for
approx. 1s as the battery cover is removed and
the tamper switch is activated. In addition, the
Control Panel will beep twice to indicate that the
alarm signal has been received and the Tamper
LED will illuminate.
3. Open the door/window to remove the magnet from
the Detector.
As the magnet is moved away from the detector
the LED will illuminate for approximately 1s to
indicate that the Detector has been triggered. In
addition, the Control Panel will beep twice to
indicate that the alarm signal has been received
and the appropriate zone LED, which the detector
is configured for, will illuminate.
4. If any external Magnetic Contact Sets are
connected to the Detector, operate these one at a
time. Each time a contact is opened the LED on
the Detector should illuminate for 1s to indicate
that it has been triggered.
5. Replace the battery cover on the Detector.
6. Press on the Control Panel to exit Walk Test
mode.
EXTERNAL SOLAR SIREN
The Siren and Solar Panel are all encapsulated within a
tough polycarbonate housing. This housing provides full
protection against adverse weather conditions.
An LED indicator unit is built into the siren to act as a
visible deterrent/indication that the system is active. The
Indicator LEDs will slowly and alternately flash whether
the system is Armed or Disarmed. During an alarm
condition the Indicator LEDs will flash rapidly together.
An integral anti-tamper switch provides additional
security protection to the Siren and will immediately
House Code
Location of Key-hole
Screw (underside)
Hole for
Mounting
Screw
Zone
Terminal Block for Additional
Wired Magnetic Contact
Jumper
Link S2
Anti-Tamper
Switch
ON
1 2 3 4 5 6 7 8 9 10 11 12
8mm
11mm
ON
1 2 3 4 5 6 7 8 9 10 11 12
DIP Switch 12 Not Used
ON
1 2 3 4 5 6 7 8 9 10 11 12
1
14 SA3
ESC
INSTALLATION

generate a full alarm should any unauthorised attempt
be made to interfere with and remove the siren cover.
The Siren is powered by a high capacity 6V/1.2Ahr
rechargeable sealed lead acid battery. A Solar Panel
mounted on the top of the housing charges the
battery during daylight hours. During darkness, only
a small amount of energy is required to operate the
Siren unit. A 9V Alkaline PP3 battery is supplied in
the External Siren to boost the initial power to the
unit when the system is first activated until the Solar
Panel charges the main battery. (This battery is only
designed to last for a short period until the main
rechargeable battery has obtained sufficient charge).
The Siren unit incorporates the installations Jamming
Detection system which will (if activated) generate an
alarm if any attempt is made to continuously jam the
radio channel used for the system.
POSITIONING THE SOLAR SIREN
The Siren should be located as high as possible in a
prominent position so that it can be easily seen and
heard. The Siren should be mounted on a sound flat
surface so that the rear tamper switch is not activated
when mounted. Ensure that the tamper switch does
not fall into the recess between brick courses as this
could prevent the switch from closing and give a
permanent tamper signal.
In order to provide the maximum amount of daylight to
the Solar Panel, the siren should ideally be mounted
on a south facing wall. However, an easterly or
westerly position will suffice.
Mounting the device on a north facing wall should be
avoided as this could mean that during the short dark
days of winter months the solar panel may not receive
sufficient daylight in order to maintain the battery charge
at acceptable levels.
Shadows cast by neighbouring walls, trees and roof
overhangs should also be avoided. If the Siren is to be
mounted below the eaves, it should be positioned a
distance of at least twice the width of the eaves
overhang below the eaves. Remember that in winter
the sun is lower in the sky and you should avoid winter
shadows where possible.
The External Solar Siren contains a sophisticated
radio receiver. However, reception of radio signals can
be affected by the presence of metallic objects within
the vicinity of the Solar Siren. It is therefore important
to mount the Solar Siren a minimum distance of 1m
away from any external or internal metalwork, (i.e.
drainpipes, gutters, radiators, mirrors etc).
Ensure that the position selected for the Siren is within
effective range of the Control Panel, (refer to "Testing
the Control Panel & Remote Control").
INSTALLING AND CONFIGURING THE
SOLAR SIREN
(See diagram overpage).
1. Remove the fixing screw from the bottom edge of
the Siren housing and carefully hinge off the front
cover. All electronic components are housed
within the front cover.
2. Hold the mounting plate in position and mark the
positions of the four mounting holes. A spirit level
placed on the casing will ensure a perfect level.
Drill four 6mm holes and fit the wall plugs
3.
Fit the two 30mm fixing screws in the top holes
leaving approximately 10mm of the screw protruding.
4. Fit the top keyhole slots of the mounting plate over
the screw heads. Remove the mounting plate and
adjust the screws until they form a neat fit with the
mounting plate with minimal movement.
5. Secure the mounting plate in position using the
two 25mm fixing screws in the bottom fixing holes.
6. Ensure that the Solar Siren main configuration
switch on the LED indicator board is set to
"SIREN" for use with this alarm system.
NORTH
WEST EAST
SOUTH
Avoid if
possible
Main Configuration Switc
h
(in SIREN Position)
C.U. SIREN
SA3 15
INSTALLATION

7. Undo the 3 screws holding the DIP Switch Cover
in place and remove the cover.
8. Under the cover you will find a series of 9 DIP
switches.
Note: When the Solar Siren is viewed as shown
above (Solar panel at top) the DIP switches are
‘upside down’.
9. DIP switches 1-8 are used to set the House Code
for the Siren and must be set to the same ON/OFF
combination as all other system devices.
10
.If required the maximum length of time that the
External Solar Siren will sound for when activated
under an alarm condition may be limited to 3
minutes using DIP switch 9 as follows:
ON as Control Panel setting
OFF 3 minutes
11
.The Solar Siren will acknowledge Disarm signals
from the Remote Control and Service Mode
signals by beeping. It is possible to disable these
acknowledgement beeps if required by removing
the jumper link P2 on the circuit board.
P2 fitted beep enabled
P2 removed beep disabled
12
.If for any reason you need to disable the Siren,
remove jumper link P3 on the circuit board. This
will prevent the Siren from sounding during an
alarm condition. However, the Siren will still beep
to acknowledge signals from the Remote Control,
(provided the beep feature is not disabled).
P3 fitted Siren enabled
P3 removed Siren disabled
13
.
To enable the Jamming Detect feature in the Solar
Siren fit the jumper link taped to the cover of the Siren
control unit across link pins P1 on the circuit board.
P1 fitted Jamming Detection enabled
P1 removed Jamming Detection disabled
14
.Refit the DIP switch cover and replace the three
cover fixing screws. Do not over tighten the screw
as this could damage the thread.
POWER-UP OF THE SOLAR SIREN
1. Connect the 9V PP3 initial power battery to the
battery clip.
Connect the rechargeable battery to the charging
leads. Connect the Red lead to the Red (+ve)
terminal and the Black lead the Black (-ve) terminals.
Both indicator LEDs will flash together in a single
long flash to indicate that the unit is operational.
Important: Once the batteries have been
connected, the Siren will be operational. It is
important that the solar panel receives sufficient
light to maintain the battery charge.
Tamper
switch
6 Volt 1.2Ahr
rechargeable
battery
9 Volt PP3 initial
power up battery
Siren
Printed circuit
board enclosure
Receiver
Aerial DIP switch
cover
Alarm duration
DIP switch 9
House Code
DIP switches 1-8
7.5 Volt DC
charging adaptor
input
Front cover
locating tabs
Beep Disable Lin
k
Siren Disable Link
Jamming
Detection Link
LED Indicator PCB
Solar Panel
C.U.
Main Configuration Switch
(in SIREN Position)
SIREN
C.U. SIREN
P1
P2
P3
ON
1 2 3 4 5 6 7 8 9
Alarm Duration DIP switch 9
(Always change from the factory setting)
House Code
ON
1 2 3 4 5 6 7 8 9
16 SA3
INSTALLATION
The Siren should not be operated repeatedly
during installation and testing, as this will
rapidly drain the battery. It is recommended
that the Siren be left for at least 24 hours in
order to charge the battery before the system
is Armed and fully tested.

2. Press the anti tamper switch, both indicator LEDs
will flash together four times.
3. Hinge the front cover locating tabs over the top
edge of the back plate and carefully push the base
of the siren cover into place. Secure the Siren
cover in place by refitting the fixing screw in the
bottom edge of the cover. Do not over tighten the
screw as this could damage the thread.
Important: Ensure that the rear tamper switch is
closed when you fit the siren cover to the back-
plate (i.e. listen for the switch to click). If the switch
does not close this will prevent the Solar Siren
from operating correctly. If necessary, remove the
siren cover again and adjust the screw on the
back-plate tamper plunger to ensure the switch
closes when the Siren is secured in position.
4. If fitted remove the protective film covering the
Solar Panel.
TESTING THE SOLAR SIREN
1. Press on the Control Panel.
The Control Panel alarm and Solar Siren will
operate for a period of approximately 5 seconds
with the Solar Siren switching ON and OFF a few
seconds after the Control Panel.
Zone LED 3 will be illuminated during the test.
Note: To stop the siren test before the 5s period
has elapsed press on the Control Panel.
EXTERNAL CONNECTIONS
The Control Unit incorporates a terminal block for
connection of an external Hard-wired Siren. The
connection terminal block is located inside the Control
Panel behind the front cover.
To access the terminal block press
, ,
This puts the system into Test Mode and prevents an
alarm occurring.
Undo the two fixing screws on the top edge of the
Control Panel and open the front cover.
Before making any connections, ensure that the
memory jumper link P1 is in the ’OFF’ position and
then remove the DC power jack and disconnect one of
the back-up batteries.
Note: Jumper link P51 should be fitted into the ON
position only if the tamper circuit for a wired siren is
used, otherwise it must be in the OFF position.
After making your external connections reconnect the
power supply and back-up Battery. Then close the
Control Panel cover and tighten the fixing screws on
the top edge of the Control Panel.
Press to leave Test mode and return to Standby.
TESTING THE SYSTEM
INITIAL TESTING
As the system is initially installed it is recommended
that each device is tested in turn as it is installed, (refer
to testing instructions for particular device).
TESTING AN INSTALLED SYSTEM
The Control Panel has a built in test facility to enable
you to test the system at any time. However it is
recommended that the system is tested at regular
intervals not exceeding 3 months.
With the system in Standby Mode press
, ,
The Arm and Part-Arm LEDs will flash.
The system is now in the Test Mode
? ? ? ? ENTER
ESC
ESC
User Access Code
123
3
4ENTER
Permanent
12Vdc power
supply output
(100mA max.)
V+
GND
Latching
relay contacts
(Volt-free)
N.O.
C
N.C.
Not used
GND
B+
GND
TAMP
Switched
12Vdc output
for wired
Siren
(300mA max.)
GND
OUT
Tamper circuit
connections
for wired Siren
Normally closed
tamper contact
Hardwired
Siren
Terminal
Block
External Tamper Switch
Jumper Link P51
Reset Jumper
Link P1
TAMP GND B+ GND N.C. C N.O. GND V+ OUT GND
Terminal Block Detail
User Access Code
SA3 17
INSTALLATION

Note: After completing all required test functions
press to leave Test mode and return to Standby.
DETECTOR TEST
Before commencing testing please ensure that there is
no movement in any PIR protected area, all doors/
windows protected by Magnetic Contact Detectors are
closed and that all battery covers are correctly fitted.
Press
Zone LED 1 will illuminate.
Trigger each detector on the system by either
walking into a PIR protected area or by opening a
door/window protected by a Magnetic Contact
detector. As each detector is triggered the Control
Panel will beep and the LED of the zone which the
detector is configured for will be illuminated. The
Tamper switches of devices may also be tested in
the same way in which case the Tamper Led on the
Control Panel will be illuminated.
Note: To conserve power and maximise battery
life the PIR detector will only detect movement if
there has been no movement detected within the
previous 2 minutes
Press to exit detector test.
HARD-WIRED SIREN TEST
Press
The internal relay driving the hardwired siren will be
switched ON for a period of approximately 5 seconds.
Zone LED 2 will be illuminated during the test.
SIREN TEST
Press
The Control Panel alarm and the External Solar
Siren will be operated for a period of
approximately 5 seconds with the external Solar
Siren switching ON and OFF a few seconds after
the Control Panel.
Zone LED 3 will be illuminated during the test.
CONTROL PANEL LED TEST
Press
Zone LED 4 will illuminate.
Use and buttons to scroll through
and illuminate each LED in turn.
Press to exit LED test.
SIREN SERVICE MODE
The Siren includes a Service Mode facility which
prevents the sirens tamper switch from triggering the
siren while it is removed from the wall for
maintenance or to change the batteries. After
changing the batteries and refitting in position, the
Siren must be put back into normal Operating Mode,
otherwise the siren will not sound in the event of an
alarm condition.
Press to switch the Siren between Service
Mode and normal Operating Mode.
LED 5 will illuminate to show that the appropriate
signal is being transmitted.
Service Mode: The Siren will produce two short
beeps/LED flashes and then after approx 6s a
single long beep/LED flash followed immediately
by two short beeps/LED flashes to indicate that it
has switched into service mode.
Operating Mode: After approx 6s the Siren will
produce a single long beep/LED flash to indicate
that it has switched into normal operating mode.
FACTORY DEFAULTS
User Access Code: 1 2 3 4
Alarm Duration: 3 minutes
Hardwird Siren: Equal to Alarm Duration
Zone Operating Mode: Intruder (all zones)
Part-Arm: Zones 1-4: Enabled
Zones 5-6: Disabled
Instant/Delay Zone 1: Delay
Zones 2-6: Instant
Entry/Exit Delay: 30s
Entry/Exit Warning Tone: On
Zone Lockout On
Jamming Detection: Off
1
2
3
4
ESC
ESC
ESC
18 SA3
5
INSTALLATION
Other manuals for SA3
1
Table of contents
Other Response Alarms Security System manuals

Response Alarms
Response Alarms RE3000S User manual

Response Alarms
Response Alarms SA3 Installation instructions

Response Alarms
Response Alarms E400 Wirefree Installation instructions

Response Alarms
Response Alarms PA6 User manual

Response Alarms
Response Alarms E100 Wirefree Installation instructions

Response Alarms
Response Alarms SAC1 Installation instructions

Response Alarms
Response Alarms RE5000S User manual