19
SIGNAL FAULT PROBABLE CAUSE SUGGESTED REMEDY
2 x blinks After pre-purge and
safety time, the burner
goes tolock-out and the
flame does not appear
1-The solenoid VR allows little gas through. . . . . . . . . . . . . .Increase
2-Solenoid valves VR or VS fail to open . . . . . . . . . . . . . . . .Renew the coil or rectifier panel
3-Gas pressure too low . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Increase pressure at governor
4-Ignition electrode wrongly adjusted. . . . . . . . . . . . . . . . . . . Adjust, see fig. (C)p. 6
5 - Electrode grounded due to brocken insulation . . . . . . . . . . Replace
6 - High voltage cable defective . . . . . . . . . . . . . . . . . . . . . . . . Replace
7 - High voltage cable deformed by high temperature . . . . . . . Replace and protect
8 - Ignition trasformer defective . . . . . . . . . . . . . . . . . . . . . . . . Replace
9 - Erroneous valve or trasformer electrical connections . . . . . Check
10 - Control box defective . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
11 - A cock down-line of the gas tr ain is closed . . . . . . . . . . . . . Open
12 - Air in pipework. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bleed air
13 - VS and VR gas valves unconnected or with interrupted coil . . Check connections or replace coil
3 x blinks The burner does not start
and lock-out warning
appears
14 - Air pressure switch in operating position Adjust or replace
The burner starts and
then locks out
Air pressure switch inoperative due to
insufficient air pressure:
15 - Air pressure switch adjusted badly . . . . . . . . . . . . . . . . . . . Adjust or replace
16 - Pressure switch pressure point pipe blocked . . . . . . . . . . . Clean
17 - Head wrongly adjusted . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust
18 - High negative draft in chamber . . . . . . . . . . . . . . . . . . . . . . . . . Connect air pressure switch to fan suction inlet
Lock-out during pre-purg-
ing
19 - Defective motor remote control switch . . . . . . . . . . . . . . . . Replace
20 - Defective electrical motor . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
21 - Motor protection tripped . . . . . . . . . . . . . . . . . . . . . . . . . . . Reset thermal cut-out when third phase
is re-connected
4 x blinks The burner starts and
then locks out
22 - Flame simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace control box
Lock out when burner
stops
23 - Flame remains in combustion head . . . . . . . . . . . . . . . . . . Eliminate persistence of flame
or flame simulation or replace control box
7 x blinks The burner goes to lock-
out right after flame
appearance
24 - The solenoid VR allows little gas through . . . . . . . . . . . . . . Increase
25 - Ionisation probe wrongly adjusted. . . . . . . . . . . . . . . . . . . . Adjust, see fig. (C)p. 6
26 - Insufficient ionisation (less than 5 µA). . . . . . . . . . . . . . . . . Check probe position
27 - Probe grounded . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Withdraw or replace cable
28 - Burner poorly grounded . . . . . . . . . . . . . . . . . . . . . . . . . . . Check grounding
29 - Phase and neutral wires inverted . . . . . . . . . . . . . . . . . . . . Correct by interventing
30 - Defective control box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
Burner locks out at transi-
tion between 1st and 2nd
stage or between 2nd and
1st stage
31 - Too much air or too little gas . . . . . . . . . . . . . . . . . . . . . . . . Adjust air and gas
During operation, the
burner stops in lock out
32 - Probe or ionisation cable grounded . . . . . . . . . . . . . . . . . . Replace worn parts
33 - Fault on air pressure switch . . . . . . . . . . . . . . . . . . . . . . . . Replace
10 x blinks The burner does not start
and lock-out warning
appears
34 - Erroneous electrical connections . . . . . . . . . . . . . . . . . . . . Check connections
The burner goes to lock-
out
35 - Control box defective . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
No blink The burner does not start 36 - No electrical power supply . . . . . . . . . . . . . . . . . . . . . . . . . Close all switches - Check connections
37 - A limiter or safety control device is open. . . . . . . . . . . . . . . Adjust or replace
38 - Control box fuses blown . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
39 - Control box lock-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reset control box
40 - No gas supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Open the manual valves between meter and train
41 - Mains gas pressure insufficient . . . . . . . . . . . . . . . . . . . . . . Contact your GAS COMPANY
42 - Minimum gas pressure switch fails to close . . . . . . . . . . . . Adjust or replace
The burner repeats the
starting cycle without lock
out
43 - Mains gas pressure is near the value to which the . . . . . . . Reduce operating pressure
min. gas pressure switch gas is adjusted. The of minimum gas pressure switch.
repeated drop in pressure which follows valve Replace gas filter
opening causes temporary opening of the pressure
switch itself, the valve immediately closes and the
burner comes to a halt. Pressure increases again, the
pressure switch closes again and the firing cycle is
repeated. The sequence repeats endlessly.
Ignition with pulsation 44 - Poorly adjusted head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust, see p. 7
45 - Ignition electrode wrongly adjusted. . . . . . . . . . . . . . . . . . . Adjust, see fig. (C)p. 6
46 - Poorly adjusted fan air gate: too much air. . . . . . . . . . . . . . Adjust
47 - Output during ignition phase is too high . . . . . . . . . . . . . . . Reduce
The burner does not pass
to 2nd stage
48 - Remote control device TR does not close . . . . . . . . . . . . . Adjust oe replace
49 - Defective control box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
50 - Servomotor faulty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
Burner stops with air gate
valve open
51 - Sevomotor faulty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace