2.CoolandHeatFunction:
Incoolmode:
A.Coolingsystemsworksinbelowsituation:
Themeasuringtemperature^ thesettemperature+ thetemperaturedifferential
B.Coolingsystemsstopworkinginbelowsituation:
Themeasuringtemperature^ thesettemperature
Inheatmode:
A.Heatingsystemsworksinbelowsituation:
Themeasuringtemperature^ thesettemperature- thetemperaturedifference;
B.Heatingsystemsstopworkinginbelowsituation:
Themeasuringtemperature^ thesettemperature
3.DelayTime:
Whenpoweronforthefirsttime,ifThemeasuringtemperature^ thesettemperature+ the
temperaturedifferentialorThemeasuringtemperature^ thesettemperature- the
temperaturedifference,theoutputwillnotbeactivatedimmediately,andwillbeactivatedafter
thedelaytime.
Ifthetimeperiodbetweenthepreviousstopandthisstartsislongerthanthedelaytime,the
outputwillbeactivatedimmediately;ifitisshorterthanthedelaytime,theoutputwillbe
activatedafterthedelaytime.Thedelaytimeiscalculatedfromthepreviousoutputstop.
4.Highandlowtemperaturelimit:
HSandLScansetthehighandlowlimitofthesettingtemperature:
Forexample:HSis+15,LSis-10,thetemperatureonlycanbesetbetween-10~+15*C;soif
youwanttoseta valuebeyondthisrange,pleaseresettheHSandLSfirstly.
1.Sensorerroralarm
Whenthecontrollerisinpoweronstatus,ifsensoropencircuit,LEDflashanddisplay"
__",ifsensorshortcircuit,display"HH".Wheninsensorerrorstatus,theoutputloadwillrunas
thecycle:stop15minutes,thenwork15minutes.
2.Overtemperaturealarm
Whenthesensortemperature>99*C,displayHH:Whenthesensortemperature<--40'C,
displayLL.